© Danfoss | 2019.02 | 11
VI.GM.A2.02
CCR3+ Controller
LANGUAGE
ENGLISH
CORRECTIONS MENU:
No. Name
Description
48
S0, … , S36
Sensor calibration: S0 … S36 in range: ±9.9 °C
Do not make calibration when sensor cables are shorter than 10 meters.
For longer cable then 10 meters, used correction factors from table below.
49
Cable Length
Cable Calculator
Useful tool for calculating cable corrections by selecting cable length (m) and cross (mm
2
).
Save settings
Click »Save Settings« to confirm changes.
TESTS MENU:
No. Name
Description
50
O1…O4
Open:
Selected output contact is open
Close:
Selected output is closed to common (C)
Auto
Factory setting: Auto
51
V1, …, V36
Open
: selected valve is open, contact open
Close
: selected valve is closed, shortcuted to common (C)
Auto OnOff
: selected valve works in On/off mode
AutoPWM
: selected valve works in PWM mode
Factory setting: AutoPWM
Save settings
Click »Save Settings« to confirm changes
Set all as Open
All Open
Set all as Close
All Close
Set all as AutoPWM
All Auto PWM
DATA MENU
Delete all logs
No. Name
Description
52
Delete all logs
Erasing of log file
53
GO to
By selecting time period, log files will be shown and ready for download (*.CSV)
NETWORK MENU:
No. Name
Description
54
Modbus
Enable –
Modbus is switch on
Disable –
Modbus is switched off
55
Modbus baud rate
Type of date transmission:
ModBus 96
(9.600)
Mod Bus 19
(19.000)
ModBus 38
(38.400)
FBus
Factory setting: ModBus 96
56
Modbus parity
None
(transmission parity disabled)
Even
(»Even« type of transmission parity enabled)
Odd
(»Odd« type of transmission parity enabled)
Factory setting: Odd
57
Modbus address
Unit Address for Mobus RTU RS485
Factory setting: 1
58
LAN IP address
The IP address that the router assigned to this device when it joined the network. This number
can change if a device is disconnected and rejoins the network
Factory setting: 192.168.1.100
59
LAN IP address mask
Identify network address of an IP address
Factory setting: 255.255.255.0
60
LAN Gateway address
The gateway address (or default gateway) is a router interface connected to the local network
that sends packets out of the local network
Factory setting: 192.168.1.1
61
LAN name (min. 2
char., max. 15 char.)
Name of CCR3+ (relevant for network search)
Please note that after changing this value, local network dns server need to be refreshed. This
process is depend on current network configuration and can take up to few hours.
Factory setting: ccrplus
62
LAN DHCP
Dynamic Host Configuration Protocol
Disable
Enable
Factory setting: Disable
63
LAN connected clients Number of LAN connected clients to CCR3+
64
WIFI name (min. 2
char., max. 15 char.)
Wi-Fi name (can be changed)
Factory setting: ccrwifi
65
WIFI pass (min. 8 char.,
max. 15 char.)
Password name (can be changed)
Factory setting: admin1234
66
WIFI connected client
Shows IP and name of Wi-Fi connected device
67
Change Login
password:
Password name for access to CCR3+ App
Factory setting: admin1234
68
Slave Unit Comm.
Status
Shows Slave Unit communication status between CCR3+ Controller
0% –
no communication
100% –
communication OK
Possible (readable values): 0 – 100%
Save Settings
Click »Save Settings« to confirm changes
11. CCR3+ DASHBOARD
(Web App Screen)
(continuous)
Note:
In case of changing IP address in
CCR+ Controller, changes should also be
applied in PC local network settings.