Danfoss CCR3+ Operating Manual Download Page 3

© Danfoss | 2019.02 | 3

VI.GM.A2.02 

CCR3+ Controller

105 mm

60 mm

90 mm

122 mm

45 mm

50 mm

36 mm

CCR3+ Controller

MADE 

IN POLAND

Retu

rn

Temper

at

ur

e

Co

nt

ro

lle

r

CCR3+

20171213

V3.

12

003Z0396

Supply 24VDC

RoHS

Danf

oss 

A

/S

6430 Nordb

or

g,

 D

en

m

ar

k

G

S0

B3

B2

B1

G

S4

S3

S2

S1

G

S8

S7

S6

S5

G

S12

S11

S10

S9

G

S16

S15

S14

S13

G

S20

S19

S18

S17

C

O4

O3

O2

O1

V4

V3

V1

V8

V7

V5

V12

V11

V9

V16

V15

V13

V20

V19

V17

C

C

C

C

C

V2

V6

V10

V14

V18

A

B

G

24VDC

TCP/IP

RJ45

POWER

Master

Module 

1

Module 

2

Module 

3

Module 

4

Module 

5

Module 

0

POWER

Maste

r

Module 

1

Module 

2

Module 

3

Module 

4

Module 

5

Module 

0

Lbus

G

G

BO

TO

M

C

V13-16

C

V1-4

C

V5-8

C

V9-12

C

O1-4

0V

24VDC

LBus

RS485

S13-16

G

S1-4

G

S5-8

G

S9-12

G

B1-3 S0

G

TCP/IP

LAN

C

V17-20

S17-20

G

Connector/port

Description

0V

24VDC

0V

 – ground (-) power supply

24 VDC(+)

 power supply

Lbus

RS485

G

 – ground Lbus port (for system expansion)

Lbus

 – Lbus port (for system expansion)

G

 – ground (Modbus RS 485)

B

 – port B (Modbus RS 485)

A

 - port A (Modbus RS 485)

C

O1,..,O4

C

 – common port dedicated to outputs O1-O4

O1 -

 output: Alert Broken Sensor

O2 -

 output: Alert Low Temp

O3 -

 output: Alert High Temp

O4 -

 output: not in use

C

V1-4

C

 – common port  dedicated to actuators V1-4

V1..V4

 – outputs to actuators

C

V5-8

C

 – common port  dedicated to actuators V5-8

V5..V8

 – outputs to actuators

C

V9-12

C

 – common port  dedicated to actuators V9-12

V9..V12

 – outputs to actuators

C

V13-16

C

 – common port  dedicated to actuators V13-16

V13..V16

 – outputs to actuators

Connector/port

Description

C

V17-20

C

 – common port  dedicated to actuators V17-20

V17..V20

 – outputs to actuators

TCP/IP, LAN

TCP/IP

 port or IP Modbus port

B1-3, S0

G

B1,B2, B3 defined inputs

S0

 – temp. sensor

G

 – common ground dedicated to inputs/sensor

S1-4

G

S1..S4

 – inputs from sensors

G

 – common ground dedicated to sensor S1-4

S5-8

G

S5..S8

 – inputs from sensors

G

 – common ground dedicated to sensors S5-8

S9-12

G

S9..S12

 – inputs from sensors

G

 – common ground dedicated to sensors S9-12

S13-16

G

S13..S16

 – inputs from sensors

G

 – common ground dedicated to sensors S13-16

S17-20

G

S17..S20

 – inputs from sensors

G

 – common ground dedicated to sensors S17-20

Fig. 3

 Wiring scheme - CCR3+ Master Controller

Summary of Contents for CCR3+

Page 1: ...Danfoss 2019 02 VI GM A2 02 1 ENGLISH CCR3 Controller www danfoss com CCR3 Controller Operating Guide...

Page 2: ...2 Danfoss 2019 02 VI GM A2 02 CCR3 Controller Fig 1 Installation with CCR3 Controller up to 20 risers loops Fig 2 Installation with CCR23 Controller Master and CCR Slave Unit more that 20 risers...

Page 3: ...bus RS 485 C O1 O4 C common port dedicated to outputs O1 O4 O1 output Alert Broken Sensor O2 output Alert Low Temp O3 output Alert High Temp O4 output not in use C V1 4 C common port dedicated to actu...

Page 4: ...efined output O2 Defined output O3 Defined output O4 Risers temperature sensors S1 S20 Type of sensor PT1000 B1 Def input B1 B2 Def input B2 B3 Def input B3 CCR3 Master Wiring diagram S0 main sensor P...

Page 5: ...it Connector port Description 0V 24VDC 0V ground power supply 24 VDC power supply C V21 24 C common port dedicated to actuators V21 V24 outputs to actuators C V24 28 C common port dedicated to actuato...

Page 6: ...e 30 C Transport temperature 10 60 C IP rating IP 20 Power supply 24 VDC Power consumption Controller only 1 10 VA Power consumption Slave Unit only 1 3 VA Weight 0 3 kg Installation DIN rail 35 mm 1...

Page 7: ...connected to the controllers input and output connectors 1 Set all parameters on the controller 2 Make sure that there is no external voltage on the temperature sensor plugs 3 Make sure that the volta...

Page 8: ...password admin1234 Important Change of password to secure any unauthorized interaction from 3rd parties Note You can Skip login for access to data only in CCR3 reading overview only When the setup and...

Page 9: ...6 1 open valve output closed to C powered up taking PWM into account 0 valve closed valve output closed to C powered down taking PWM into account Valve is 1 Open if PWM min Valve PWM max 9 Valve valve...

Page 10: ...for Output which Over temperature or Broken Sensor Higher the value longer the reaction time alarm signal Factory setting 0 min 33 Alarm diff temp Set upper lower deviation temperature counted from R...

Page 11: ...ed Factory setting Odd 57 Modbus address Unit Address for Mobus RTU RS485 Factory setting 1 58 LAN IP address The IP address that the router assigned to this device when it joined the network This num...

Page 12: ...s reset to admin00X where x is the number of BT blue LED blinks Reset the setting only Go to firmware menu and click on Return Defaults Reset password only but not change other parameters Go to firmwa...

Page 13: ...sed B4 open closed RTC year RTC month RTC day RTC hour RTC minute B1 open closed B2 open closed B3 open closed S0 temp Ret Set Temp Status alert from 300 to 331 300 301 302 303 304 305 306 307 308 309...

Page 14: ...14 Danfoss 2019 02 VI GM A2 02 CCR3 Controller...

Page 15: ...Danfoss 2019 02 15 VI GM A2 02 CCR3 Controller...

Page 16: ...VI GM A2 02 16 Danfoss DHS SRMT SI 2019 02 CCR3 Controller...

Reviews: