Cascade Controller Option
Standard Cascade
Controller Setup
■
Initial Setup
Instructions for programming Quick Menu items
1-20 are presented in Chapter 5,
VLT Drive and
Cascade Controller Card Setup
. Parameters
1-20 must be programmed before programming
additional options described below.
Quick Menu 021 Par. 712 Motor Pump
Combinations
(PUMP COMBINATION)
Value:
(See options in table below)
Function:
The combinations of pumps and their rated capacities
are selected in this parameter. The lead pump (or fan)
with the cascade contol option must have a capacity
of 100% and its speed is controlled by the VLT
adjustable frequency drive. This enables the highest
accuracy in regulation of the system. In Standard
cascade control mode, additional pumps can be either
100%, 200% or 300% relative to the VLT driven pump.
Description of choice:
Select the pump combination and capacities
from the choices offered.
Motor Pump Combinations
Value:
Additional Constant Speed Pumps Operated by Cascade Control
Display Option
100% Capacity
200% Capacity
300% Capacity
R6 @100%
1 pump controlled by
relay 6
R6, R7 @100%
2 pumps controlled by
relays 6, 7
R6-R8 @100%
3 pumps controlled by
relays 6, 7, 8
R6-R9 @100%
4 pumps controlled by
relays 6, 7, 8, 9
R6 @100%, R7 @200%
1 pump controlled by
relay 6
1 pump controlled
by relay 7
R6 @100%, R7, R8
@200%
1 pump controlled by
relay 6
2 pumps controlled
by relays 7, 8
R6, R7 @100%, R8
@300%
2 pumps controlled by
relays 6, 7
1 pump controlled
by relay 8
R6, R7 @100%, R8, R9
@300%
2 pumps controlled by
relays 6, 7
2 pumps controlled
by relays 8, 9
MG.60.I3.02 - VLT is a registered Danfoss trademark