Cascade Controller Option
User Interface
Three operating data values can be shown in the
first display line and one in the large display line,
programmed via parameters 007, 008, 009, and 010.
Display mode I
´
In Display mode I, the drive is in Auto mode with
reference and control determined via the control
terminals. Below is an example in which the drive
is running in setup 1, in Auto mode, with a remote
reference, and at an output frequency of 40 Hz.
The text in line 1, FREQUENCY, describes the
meter shown in the large display. Line 2 (large
display) shows the current output frequency (40.0
Hz), direction of rotation (reverse arrow), and active
setup (1). Line 3 is blank. Line 4 is the status line
and the information is automatically generated for
display by the drive in response to its operation. It
shows that the drive is in auto mode, with a remote
reference, and that the motor is running.
175ZA683.10
SETUP
1
FREQUENCY
40.0Hz
40.0Hz
40.0Hz
40.0Hz
40.0Hz
AUTO REMOTE RUNNING
Status line (Line 4): Additional automatic displays
for the drive status line are shown below.
175ZA684.10
40.0Hz
80.0% 5.08A 2.15kW
SETUP
1
AUTO REMOTE RUNNING
HAND LOCAL STOP
OFF RAMPING
JOGGING
.
.
.
.
STAND BY
The left indicator on the status line displays the
active control mode of the VLT drive. AUTO is
displayed when control is via the control terminals.
HAND indicates that control is local via the keys
on the LCP. OFF indicates that the drive ignores
all control commands and will not run.
The center part of the status line indicates the
reference element that is active. REMOTE means that
reference from the control terminals is active, while
LOCAL indicates that the reference is determined
via the [+] and [-] keys on the control panel.
The last part of line 4 indicates the drive
’
s operational
status, for example: RUNNING, STOP, or ALARM.
Display mode II
This display mode shows three operating data values
in the top line programmed via parameters 007,
008, and 009. Pressing the [DISPLAY MODE] key
toggles between Display modes I and II.
175ZA685.10
50.0Hz
SETUP
1
AUTO REMOTE RUNNING
100% 7.8A 5.9kW
Display mode III
Press and hold the [DISPLAY MODE] key while in Mode
II. Mode III is visible as long as the key is depressed.
The top line changes to identify the data names and
units displayed. Lines 2 and 4 are unchanged. When
the key is released, the display returns to Mode II.
175ZA686.10
60.0Hz
SETUP
1
AUTO REMOTE RUNNING
REF% CURR.A.POW.,KW
Display mode IV
This display mode is used for local operation, where
the local speed reference is given from the keypad. In
this display mode, the reference is determined via the
[+] and [-] keys. Control is carried out through the
bottom keys on the keypad. The first line indicates
the required reference. The third line gives the relative
value of the output frequency in the form of a bar
graph in relation to the maximum frequency.
175ZA688.10
40.0Hz
HAND LOCAL RUNNING
USE +/- 40Hz
■
Changing data
Regardless of whether a parameter has been selected
under the Quick Menu or the Extend Menu, the
procedure for changing data is the same. Pressing
the [CHANGE DATA] key gives access to changing
the selected parameter. Line 3 displays the parameter
MG.60.I3.02 - VLT is a registered Danfoss trademark