Installa
tion
10g
10.5
Indirectly connected heating system with
or without mixing loop and secondarily
connected storage tank
System settings
Circuit Line Description
Recomm.
setting
I
17
Influence on desired flow temp.
3
I
43
Priority or parallel operation
99
I
51
DHW charging pump /
changeover valve
OFF
I
53
Desired flow temperature at
DHW charging
OFF
I
67
Adaptive function of S2 flow
temperature during DHW
charging
20
I
140 Function of temperature sensor
S5
2
I
152 Max limitation temperature at
sensor S2 during DHW charging
70*
* Line 152 = desired charging temperature
Heating circuit II can only be operated against heating circuit I.
This means that heating circuit II cannot be supplied if heating
circuit I is deactivated.
Summary of Contents for C67
Page 4: ......
Page 15: ...Installation 11b...
Page 23: ...Installation...
Page 45: ...Control overviews...