Danfoss APP 5.1 User Manual Download Page 41

23

180R9263  /  IOM APP 5.1-10.2 Appendices - v02  /  01.2013

Hoyer Motors, Motor Manual, October 2011

2

1. General

This manual concerns the following types of standard 

 

induction motors from Hoyer:
HMA2, HMC2, HMD, HMT, MS, Y2E1, Y2E2, YDT
These motors are manufactured in accordance with IEC/EN 
60034-4 and IEC/EN 60072. 
Motors are rated for the ambient temperature range -20°C 
to +40°C and site altitudes 

1000 m above sea level.

Low-voltage motors are components for installation in 

 

machinery. They are CE marked according to the Low 

 

Voltage Directive 2006/95/EC

2. Transport and storage

Check the motor for external damage immediately upon  
receipt and, if found, inform the forwarding agent right 
away. Check all rating plate data, and compare it with the 
requirement of the motor.
Turn the shaft by hand to check free rotation, remove  
transport locking if used. 
Transport locking must be used again for internal transport 
also. It is also important that transport locking is used when 
motors are transported mounted on equipment.
All motors should be stored indoors, in dry, vibration- and 
dust-free conditions.

Lifting eyebolts must be tightened before use. Damaged 
eyebolts must not be used, check before use. Lifting eyes at 
motor must not be used to lift the motor when it is attached 
to other equipment.

Before commissioning, measure the insulation impedance. 
If values are 

 10M

Ω

 at 25°C, the winding must be oven dried. 

The insulation resistance reference is halved for each 20°C 
rise in motor temperature.
It is recommended that shafts are rotated periodically by 
hand to prevent grease migration.

3. Installation

The motor must be fixed on a stable, clear and flat founda-
tion. It must be sufficiently rigid to withstand possible short  
circuit forces. 
It is important to ensure that the mounting conditions do 
not cause resonance with the rotational frequency and the 
doubled supply frequency.
Only mount or remove drive components (pulley, coupling, 
etc.) using suitable tools, never hit the drive components 
with a hammer as this will cause damage to the bearing. 
The motor are balancing with half key, ensure that the drive 
components are also the same.

Correct alignment is essential to avoid bearing, vibration 
and shaft failure. 
Use appropriate methods for alignment. 
Re-check the alignment after the final tightening of the 
bolts or studs.
Check that drain holes and plugs face downwards. We  
recommend opening the drain hole for motors placed 

 

outdoors and not running 24 hours / day, so that the motor 
can breathe, thus ensuring a dry motor. 

4. Electrical connection

Work is only permitted to be carried out by qualified 

 

specialists and must to be carried out in accordance with 
local regulations. 
Before work commences, ensure that all power is switched 
off and cannot be switched on again. This also applies to the 
auxiliary power circuits, e.g. anti-condense heaters.
Check that supply voltage and frequency are the same as 
rated data. 
Motors can be used with a supply deviation of ± 5% voltage 
and ± 2% frequency, according to IEC60034-1

Connection diagrams for main supply and accessory as PTC 
or heater are located inside the terminal box. 

Connections must be made in such a way as to ensure that 
a permanently safe electrical connection is maintained, 
both for the main supply and the earth connection.
We recommend that crimped connections are made in  
accordance with IEC 60352-2.

Tightening torques for terminal board screws:

Ensure that the terminal box is clean and dry. 
Unused glands must be closed.
Check the terminal box gasket before it is remounted. 

5. Maintenance

Inspect the motor at regular intervals, keep it clean and  
ensure free ventilation air flow, check the condition of  
shaft seals and replace if necessary. Both electrical and  
mechanical connections must be checked and tightened if 
necessary. 

Thread 

M5 

M6 

M8 

M10 

M12 

M16 

M20

T.(Nm) 

2.5 

3.5 

12 

18 

35 

55

Motor Manual

Hoyer Motors, Motor Manual, October 2011

3

Bearing size and type are specified on the rating plate.  
Motor types HMA2 and HMC2 is as standard with lifetime 
greased bearing with motor size 

225. 

Motor types MS and Y2E is as standard with lifetime greased 
bearing with motor size 

160.

Typical duty hours for lifetime lubricated bearings.

Motors with a re-greasing system must be lubricated with 
high quality lithium complex grease, NLGI grade 2 or 3, with 
a temperature range of between -40°C to +150°C. 

Motors are normal fitted with a data plate with greasing 
information; if it is missing use the following re-greasing 
intervals.

Grease the motor while running, open the grease outlet plug 
and let the motor run 1-2 hours before the outlet grease 
plug is closed again.

Grease the motor for the first time during commissioning.

The following applies in general for both lifetime lubricated 
and re-lubricated bearings:
At 60Hz the time will be reduced by app. 20%.
Data for vertically mounted motors are half of the above 
values.

The table values are based on an ambient temperature of 
25°C. The values must be halved for every 15K increase in 
bearing temperature.
Higher speed operations, e.g. frequency converter drive will 
require shorter greasing intervals. Typically, doubling the 
speed will reduce the values by 50%. 

6. Special note for Atex Zone 22 motors.

Notice for the use of electrical equipment in areas with 
combustible dust.
Designation of motor according to EC directive:
Ex II 3D T125°C, IP55.

The dust hazardous 3-phase asynchronous motors are 

 

in accordance with European standard EN 50281-1-1. 

 

Combustible dust areas will be found in agricultural areas 
and in industrial environments.
Only one electrical installation may be installed in one 
specified area (zone).

Only certificated cable glands for category 2D may be used. 
Unused glands must be closed.
Connections must be made in such a way as to ensure that 
a permanently safe electrical connection is maintained, 
both for the main supply and earth connection.
Installations must be in accordance with actual standards 
for installation in the Zone 22 area.

It is recommended that EN 50281-2 is followed according 
temperature and dust on the motor surface.
The use of motors with so much surface dust that the  
motor temperature increases is not permitted.
Regularly cleaning is recommended.
The radial shaft sealing ring is part of the ATEX certification. 
It is important that the ring is always intact.
The shaft sealing must be regularly checked, and if dry 
it must be lubricated. It is recommended that the seal is  
re-lubricated regularly.
Always use the original seal ring when replaced.
Replacing bearings also means replacing the seals.

All machines must be inspected regularly for mechanical 
damage.
The user is responsible for changing parts in accordance 
with the lifetime of parts, in particular:
bearings, grease and lubrication of shaft sealing.

Maintenance, repairs and replacement on zone 22 motors 
must only be carried out by qualified specialists. 

Frame size 

Poles 

Typical lifetime

56 – 160 

2 – 8 

40.000h

180 

35.000h

200 

27.000h

225 

23.000h

180 – 225 

4 – 8 

40.000h

Frame  

Grease 

2 pole 

4 pole 

6 pole 

8 pole

size 

(g) 

(h) 

(h) 

(h) 

(h)

160 

20 

4200 

7000 

8500 

8500

180 

20 

4200 

7000 

8500 

8500

200 

25 

3100 

6500 

8500 

8500

225 

25 

3100 

6500 

8500 

8500

250 

35 

2000 

6000 

7000 

7000

280 

35 

2000 

6000 

7000 

7000

315 

50 

1500 

5500 

6500 

6500

355 

60 

1000 

4000 

5000 

6000

400 

80 

800 

3000 

4000 

6000

Motor Manual

Summary of Contents for APP 5.1

Page 1: ...ion and Maintenance Manual APP pumps APP 5 1 10 2 MAKING MODERN LIVING POSSIBLE Lenntech info lenntech com Tel 31 152 610 900 www lenntech com Fax 31 152 616 289 info lenntech com Tel 31 152 610 900 w...

Page 2: ...inspection transportation handling lifting and storage 9 4 1 Arrival inspection 9 4 2 Warning 9 4 3 General safety information 9 4 4 Transport and handling 9 4 5 Return to supplier 10 4 6 Storage 10 5...

Page 3: ...7 4 Disassembling and assembling the pump unit 15 7 5 Assembling the pump unit 16 7 6 Procedure for mounting pump back onto electric motor 16 7 7 Getting the pump unit back into operation 16 7 8 Stor...

Page 4: ...ps v01 01 2013 This manual is valid for APP pumps with the following code numbers serial numbers Validity APP 5 1 Code no 180B3005 Serial no 03 APP 6 5 Code no 180B3006 Serial no 03 APP 7 2 Code no 18...

Page 5: ...5 180R9263 IOM APP Pumps v01 01 2013 EU Declaration of Conform ity...

Page 6: ...ty regulations and laws It is the responsibility of the safety officer or the chief operator to assure compliance with all local regulations that are not taken into account in this manual Changing the...

Page 7: ...alves must be verified and free flow from safety valves must be ensured All pipe and hose connections must be stress free mounted securely fastened to the pumps and well supported Improper installatio...

Page 8: ...d replacement of the complete motor pump unit it is recommended having sufficient space around the unit For easy access to the unit at least 1 meter 40 inches available space should be kept free aroun...

Page 9: ...ved in lifting and transporting the equipment see Safety chapter 2 must be trained in handling and safety procedures when lifting heavy loads Many of the pumps and pump units weigh more than 20 kilos...

Page 10: ...hat the unit load is balanced before attempting to lift as the centre of the mass is different from pump to pump and pump unit to pump unit How to mount the pump and the electric motor correctly toget...

Page 11: ...or rust is not removed the pump and the valves can be damaged and in the worst case damaged beyond repair 5 3 Fluid temperature Before start up the fluid and pump housing temperature must be above the...

Page 12: ...pump in outlet CP13 Check piping for possible air gaps 5 7 Lifting and positioning Lift the pump unit onto base Remember vibration dampers if needed Fasten the motor to the base See also chapter 4 Arr...

Page 13: ...ling true the hole in the bell housing not available on all bell houses If the motor is turning the wrong direction switch two phases in the connection box of the motor or reprogram the direction in V...

Page 14: ...Very high temperatures can indicate one or more damaged parts inside the pump The pump then needs to be stopped immediately and inspected before running again Contact the maintenance depart ment G Dr...

Page 15: ...For instructions on lifting the complete pump unit see chapter 4 Arrival inspection transportation handling lifting and storage H For the small pumps unscrew the bolts holding the pump to the bell ho...

Page 16: ...m the coupling manufacturer Mount the flexible coupling and bell housing according to the Data sheet appendix 1 and APP pump instruction appendix 2 7 7 Getting the pump unit back into operation Find i...

Page 17: ...gh pressure can lead to eye or skin damage Leaking can result in flooding which again can cause a risk of slipping tripping or falling If water is dripping into the electric motor it can lead to elect...

Page 18: ...utor 6 8 Dimensions 8 11 Disassembling 15 16 E Electric motor 6 7 8 9 10 11 12 13 16 17 Electrical failure 17 Electrical hazard 6 Electrics 12 EU Declaration of Conformity 5 F Failure 8 17 Filter cond...

Page 19: ...Front page for Appendices APP 5 1 10 2 User manual Appendices for Installation Operation and Maintenance Manual APP pumps APP 5 1 10 2 MAKING MODERN LIVING POSSIBLE...

Page 20: ...1 2013 Table of Contents 1 Data sheet for APP 5 1 10 2 pumps 521B0851 3 2 APP pump instruction APP 5 1 10 2 180R9072 13 3 IOM Electric motors 180R9230 21 4 Recommended service intervals for APP pumps...

Page 21: ...1 Data sheet for APP 5 1 10 2 pumps 521B0851 ro solutions com Data sheet APP pumps APP 5 1 10 2 MAKING MODERN LIVING POSSIBLE...

Page 22: ...required The pumps are fixed displacement pumps in which the flow is proportional to the number of revolutions of the input shaft and the pump displacement regardless of any counter pressure 1 General...

Page 23: ...1 APP 6 5 APP 7 2 APP 8 2 APP 10 2 Geometric displace ment cm3 rpm 50 63 70 80 100 in3 rpm 3 05 3 84 4 27 4 88 6 10 Flow 1800 rpm 1 m3 h 5 0 6 4 7 2 8 2 10 2 gpm 22 0 28 2 31 7 36 1 44 9 Min pressure...

Page 24: ...PP 5 1 66 4 0 17 4 8 3kW 9 7 kW 11 1 kW 1460 475 2 APP 5 1 79 4 7 20 9 10 0 kW 11 7 kW 13 4 kW 1752 475 2 APP 6 5 83 5 0 22 0 10 5 kW 12 3 kW 14 0 kW 1460 475 2 APP 6 5 100 6 0 26 4 12 6 kW 14 7 kW 16...

Page 25: ...se will be reduced if speed is reduced and vice versa Use flexible hoses in order to minimize vibrations and noise Since the APP pump is typically mounted on a bell housing or frame the noise level ca...

Page 26: ...nlet water is filtered properly to minimize the wear of the pump The main filter must have a filtration efficiency of 99 98 at 10 m We recommend that you use precision depth filter cartridges rated 10...

Page 27: ...Outlet connection M42 x 1 5 x 13 mm 0 51 inch depth Pump mounting flange 125 A2 Pump A mm B mm C mm D mm E mm F mm IEC Electric motor APP 5 1 350 437 160 254 210 498 11 kW HUC2 160 M 4 APP 6 5 350 43...

Page 28: ...essure is always to be maintained at min 0 5 bar 7 3 psi and max 5 bar 72 5 psi 1 Place the filter 1 in the water supply line in front of the APP pump 2 Place a monitoring pressure switch 2 set at min...

Page 29: ...ately after startup regardless of any counter pressure M Brine Permeate APP Feed 1 2 3 5 4 5 7 6 Provided that the APP pump has been running according to the Danfoss specifications on pre filtration p...

Page 30: ...s reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in spe...

Page 31: ...2 APP pump instruction APP 5 1 10 2 180R9072 ro solutions com Instruction APP pump instruction APP 5 1 10 2 MAKING MODERN LIVING POSSIBLE...

Page 32: ...Problems with reversing pumps e design of the system must ensure that self emptying of the pump ing standstill is avoided e inlet pressure of the pump must never exceed the outlet pressure s may typic...

Page 33: ...ceed 5 bar abs 72 5 psi 2 3 Reversible pumps If exposed to high pressure in the outlet while the electric motor is not energized the pumps will start spinning backwards This will not harm the pumps as...

Page 34: ...ured Inlet from the water supply and inlet to the pump should be placed in opposite ends of the tank to calm and deaerate the water and to ensure optimum opportunity for particles to settle 521B0747 D...

Page 35: ...n 6 Servicio T cnico 1 Identi cation 1 Identi caci n 2 Conception du syst 2 1 Syst mes ouverts avec r servo 2 2 Syst mes ouverts avec alimen 2 3 Pompes r versibles La conception du syst me doit gar l...

Page 36: ...o de una v lvula reguladora de presi n o por medio de una v lvula bypass colocada en el lado de alta presi n La v lvula se debe colocar lo m s cerca posible a la bomba En la apertura de la v lvula no...

Page 37: ...g temperatures please contact the Danfoss Sales Organization 5 2 Pressure The inlet pressure must be min 0 9 bar 13 psi and max 4 bar 58 psi abs At lower pressures the pump will cavitate resulting in...

Page 38: ...signed so that lubrication follows from the water itself and there is thus no oil in the pump The pump requires no periodic replacements of seals and valve parts 6 2 Repair In case of irregular functi...

Page 39: ...3 IOM Electric motors 180R9230 Electric Motors Motor Manual hoyermotors com Manual 180R9230...

Page 40: ...l frequency and the doubled supply frequency Only mount or remove drive components pulley coupling etc using suitable tools never hit the drive components with a hammer as this will cause damage to th...

Page 41: ...Combustible dust areas will be found in agricultural areas and in industrial environments Only one electrical installation may be installed in one specified area zone Only certificated cable glands fo...

Page 42: ...ed supply frequency Only mount or remove drive components pulley coupling etc using suitable tools never hit the drive components with a hammer as this will cause damage to the bearing The motor are b...

Page 43: ...4 Recommended service intervals for APP pumps 180R9199 Instruction Recommended service intervals for APP pumps MAKING MODERN LIVING POSSIBLE...

Page 44: ...per Duplex No wear part 93 5 7 9 Back up ring Teflon 24 000 hours O ring overall NBR 24 000 hours Screw overall AISI 316 No wear part Pin overall AISI 316 Duplex or PEEK No wear part 152 1 Valve cone...

Page 45: ...ns must be replaced The pictures below is ment as a guideline for evaluating the wear of the sliding surface Cavitation of the piston shoes New inspection is required in 3 000 4 000 hours Cavitation o...

Page 46: ...material Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being n...

Page 47: ...5 APP parts list 521B0941 Parts list APP Pumps APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 MAKING MODERN LIVING POSSIBLE APP 5 1 10 2 APPW 5 1 10 2 APP 5 1 10 2...

Page 48: ...tion x x x x x x x x x x x x x Note The parts listed are not sold separately only in various kits Exploded view see next page Parts list APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 11 521B0941 DKCFN PC 073 A...

Page 49: ...list APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 13 521B0941 DKCFN PC 073 A11 02 12 2012 12 Exploded view APP 5 1 10 2 APPW 5 1 10 2 Parts list APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 13 521B0941 DKCFN PC 073 A...

Page 50: ...uper Duplex 218 8 Screw M8x20 AISI 316 x x x x x x x x 219 1 Screw AISI 316 x x x x x x Instruction x x x x x x x x x x x x x Parts list APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 12 521B0941 DKCFN PC 073 A...

Page 51: ...list APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 13 521B0941 DKCFN PC 073 A11 02 12 2012 12 Exploded view APP 5 1 10 2 APPW 5 1 10 2 Parts list APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 13 521B0941 DKCFN PC 073 A...

Page 52: ...w M8x20 x x x Screw M8x70 x x Screw M8x140 x Lifting eye x Note The parts listed are not sold separately only in various kits Parts list APP 0 6 38 APM 0 8 2 9 APPW 5 1 10 2 24 521B0941 DKCFN PC 073 A...

Page 53: ...6 Trouble shooting guide Guideline Trouble shooting guide for APP pumps MAKING MODERN LIVING POSSIBLE...

Page 54: ...umps 2 Trouble shooting guide for APP pumps Table of Contents Trouble shooting fish bone chart 1 No flow no pressure 2 Reduced flow reduced pressure 3 High torque on electric motor 4 Noise from pump 5...

Page 55: ...in filtration 2 1 Wear in pump internal leakage 2 1 9 Type of fluid 2 1 11 High fluid temperature 4 1 Air in fluid 4 2 Bleeding conditions of pump 4 3 Min max nominal inlet pressure 4 4 Pump reversing...

Page 56: ...ct pump from electric motor and check that the motor is capable of running with no load If motor type relay or the electrical fuse is blown check that electric motor is sized correctly 1 4 No rotation...

Page 57: ...ide is polished See index 6 3 If the ring is missing the piston is very worn The filters can be bypassed even if they are correctly mounted Some filters can create channelling where particles can pass...

Page 58: ...eck that electric motor is correctly sized 3 2 2 Check internal parts see item 2 1 3 2 3 Systems with more than one electric motor installed Start motors simultaneously Pumps run in parallel with casc...

Page 59: ...flow item 1 2 Pump reversing WARNING The pump must not run without water for more than a few seconds If the pump takes in water from the high pressure outlet line it builds up pressure and will eventu...

Page 60: ...oo many bends may create too fast flow turbulence through the pipes and thus increase the noise level 5 3 Hose stiffness 5 3 1 Use amore flexible hose Danfoss A S can provide flexible hoses Please con...

Page 61: ...as scratches and or a polished surface Even small scratches will give a loss of flow Picture 3 A good way to identify a worn valve plate is to hold a straight knife edge over the valve plate When hold...

Page 62: ...trademarks of Danfoss A S All rights reserved Danfoss A S High Pressure Pumps DK 6430 Nordborg Denmark Picture 1 If the port plate has scratches level differences or both between the arrows the port...

Page 63: ...7 Right and wrong 180R9042 MAKING MODERN LIVING POSSIBLE 180R9042 Right and wrong Trouble shooting guide for water hydraulic systems...

Page 64: ...ter upstream of the final load may damage the pump Pump location 4 Pump always to be placed below water surface level Pump location above water surface level will cause damage Water supply 7 System to...

Page 65: ...f grease prevent seizing Too much grease may develop biofilm causing operational failures Water supply 13 Fill system with water before starting to ensure lubrication and cooling Starting without wate...

Page 66: ...e self bleeding 2 Start and bleed the system without pressure by opening the bypass valve 3 Add the cleaning agent to give 3 agent water solution 4 Run the system for 60 min and activate all component...

Page 67: ...or provide better cooling Is the control light for low pump suction pressure on The filter is clogging Is the power supply ok Are control lights on Is the filter clogged Is the filter control light on...

Page 68: ...Is the filter clogged Is the filter control light on Replace filter element Contact serviceman Stamp Fill water into the system Trace leakage if any A blown fuse or short circuit Check power supply an...

Page 69: ...User manual Appendices for IOM APP Pumps APP 5 1 10 2 51 180R9263 IOM APP 5 1 10 2 Appendices v02 01 2013...

Page 70: ...products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the...

Reviews: