6 | © Danfoss | 2016.12

VI.AD.B3.8C 

AME 25 SU, AME 25 SD

ENGLISH

Safety Note

To avoid injury of persons and 
damages to the device, it is absolutely 
necessary to read and observe these 

instructions carefully.

Necessary assembly, start-up, and maintenance 
work must be performed by qualified and 
authorized personnel only.

Please comply with the instructions of the 
system manufacturer or system operator.

Do not remove the cover before the 
power supply is fully switched off.

Disposal instruction

This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 
disposal.

Always follow the local disposal regulations.

Mounting

Fix the actuator on the valve. 

Admissible Installation Positions. 

Wiring 

Do not touch anything on the PCB!
Switch off the power line before wire 
the actuator! Lethal voltage!

Wire the actuator according to the wiring 
diagram.

Control signal

Control signal from the controller must be 
connected to terminals Y (input signal) and SN 
(common) on the AME printed board.

Output signal

Output signal from the terminal X can be used 
for indication of the current position. Range 
depends on the DIP switch settings.

Supply voltage

Supply voltage  
(24 V~ –15 to +10 %, 50/60 Hz) must be 
connected to the terminals SN and SP.

DIP switch settings  

U

I

2 V_---V

0 V_---V

Direct

Inverse

---

Sequential

0(2) V_5(6) V

5(6) V_10 V

Proportional

3 point/RL

LOG. flow

LIN. flow

100 % k

VS

RED. k

VS

Reset

Reset

  Factory settings: 

ALL switches are on OFF position! 

❹①

 

Note:

 All combinations of DIP switches are 

allowed. All functions that are selected are 
added consecutively. There is only one logic 
override of functionalities i.e. the switch No.6 
Proportional/3 point, which sets actuator to 
ignore control signal and works as a “simple” 
3-point actuator.

SW1:   U/I 

❹②

  Factory setting: 

voltage control signal (0-10 V).

SW2:  2-10 V/0-10 V 

❹③

  Factory setting is:  

2-10 V.

SW3:   Direct/Inverse 

❹④

  Factory setting is:  

DIRECT

SW4:---/Sequential 

❹⑤

Two actuators can be set to work parallel with 
one control signal. If the SEQUENTIAL is set then 
an actuator responds to split control signal (see 
0(2)-5(6) V/5(6)-10 V).

 

Note:

 This combination works in combination 

with switch No. 5: 0(2)-5(6) V/5(6)-10 V

SW5:  0(2)-5(6) V/5(6)-10 V 

❹⑥

 

Note:

 This function is available if switch No. 4:  

--- / Sequential is set.

SW6:  Proportional/3 point 

❹⑦

Actuator can operate as “simple” 3-point 
actuator, if the 3-point function is selected. 
Power supply should be connected on SN 
and SP ports. On port 1 or 3 24 VAC signal is 
connected for rising or lowering of actuator. 
Return signal X indicates the correct position.

 

Note: 

if 3 point function is selected actuator 

does not respond to any control signal on 
port Y. It only rises and lowers spindle if power 
is supplied on port 1 or 3.

SW6:  Proportional/3 point 

❹⑦

 

Actuator needs to perform Self 
stroking prior changing DIP 6 to ON.
Output signal depends on DIP 2, 3&5 
setting.

Actuator can operate in modulating (DIP 6 to 
OFF) or in “simple” 3-point mode, if the 3-point 
function is selected (DIP 6 to ON).

Connect power supply on terminals SN and SP 
terminals.

Factory set DIP 6 to OFF for operating actuator 
in Modulating mode.

Actuator’s stem will run to its totally extended 
or retracted position by bridging SN signal to 
terminals 1 or 3 and will remain in this positron 
as long as potential is present.

Set DIP 6 to ON for operating actuator in 3 point 
mode.

Look carefully wiring diagram as wiring is 
different for controllers with triac output (ECL) 
in comparison to controllers with relay output.

Return signal X indicates the correct position.

 

Note:

 If 

3 point

 function is selected actuator 

does not respond to any control signal on 
port Y. It only rises and lowers spindle if power 
is supplied on port 1 or 3.

SW8:  100% K

VS

/RED. K

VS

 

❹⑨

 

Note:

 This function works proper only with 

logarithmic (equal percentage) valves.

SW9:   Reset 

❹⑩

After the actuator has been connected to 
power supply, the actuator will start the 
self-adjustment procedure. The indicator LED 
flashes until self adjustment is finished. The 
duration depends on the spindle travel and will 
normally last a few minutes. The stroke length 
of the valve is stored in the memory after self 
adjustment has been completed. To restart 
self adjustment, change the position of RESET 
switch (switch No. 9). If the supply voltage is 
switched off or falls below 80 % in more then 
0.1 s, the current valve position will be stored 
in the memory and all data remain saved in the 
memory also after a power supply cut-out.

Function test

The indicator light shows whether the 
positioner is in operation or not. Moreover, the 
indicator shows the control status and faults.
Constant light

-  normal operation
No light
-  no operation or no power supply
Intermittent light (1 Hz)  
-  self adjusting-mode
Intermittent light (3 Hz):
-  power supply too low
-  insufficient valve stroke (<20 s)
-  end-position cannot be reached.

Dimensions 

Part Name

Hazardous Substances Table

Lead (Pb)

Mercury (Hg)

Cadmium (Cd)

Hexavalent Chromium (Cr(VI))

Polybrominated biphenyls (PBB)

Polybrominated diphenyl ethers (PBDE)

Bush

X

O

O

O

O

O

Electromagnet

X

O

O

O

O

O

Housings

X

O

O

O

O

O

Brake Weights

X

O

O

O

O

O

Clamp

X

O

O

O

O

O

Yoke

X

O

O

O

O

O

Summary of Contents for AME 25 SU

Page 1: ...25 SU AME 25 SD www danfoss fi Sivu 11 NEDERLANDS AME 25 SU AME 25 SD www danfoss nl Bladzijde 12 POLSKI AME 25 SU AME 25 SD www danfoss pl Strona 13 AME 25 SU AME 25 SD www danfoss com cn 14 AME 25...

Page 2: ...H no condensing MAINTENANCE FREE 4 6mm 1mm T 10 2 4 mm 4 or 4 AME 25 SD AME 25 SU Tmax 150 C AME 25 SD SU VRB VRG VF and VL Tmax 200 C AME 25 SD SU VFS Adapter for VFS Code No 065Z7548 5o 5o Tmax 150...

Page 3: ...ntroller with triacs output Proportional 3 point RL SN 0 V Neutral SP 24 VAC Power supply 1 24 VAC Input 3 X 0 2 10 VDC Output Proportional 3 point RL SN 0 V Neutral SP 24 VAC Power supply Y 0 2 10 V...

Page 4: ...4 Danfoss 2016 12 VI AD B3 8C AME 25 SU AME 25 SD...

Page 5: ...1 11 2 95 29 222 32 11 4 2 112 35 226 40 11 2 21 4 132 43 237 50 2 2 160 47 242 VRB 3 VRG 3 15 1 80 40 216 20 11 4 80 45 218 25 1 11 2 95 50 222 32 11 4 2 112 58 226 40 11 2 21 4 132 75 255 50 2 2 160...

Page 6: ...r rising or lowering of actuator Return signal X indicates the correct position Note if 3 point function is selected actuator does not respond to any control signal on port Y It only rises and lowers...

Page 7: ...rtional 3 punkt N rDIP6erp Aktuatorskaludf re automatiskekalibreringforudat DIP 6 Udgangssignalafh ngerafDIP 2 3 5 Indstilling Aktuator kan k re i modulerende DIP 6 til OFF eller i simple 3 punkts fun...

Page 8: ...er Schalter No 4 Sequentiell eingestellt ist SW6 Proportion l 3 Punkt WennderDIP 6istaufStellmotor mussVentilhubvordem ndernder DIP6aufON Ausgangssignalistabh ngigvonDIP 2 3 5 Einstellung Stellmotor k...

Page 9: ...r gl e SW6 Proportionnel 3 points LorsqueleDIP6estSURActuateur doitex cuterautor gulationavantle DIPenperp tuelle volution6sur ON Signaldesortied pendducommutateurDIP2 3et5R glage Actuateur permet de...

Page 10: ...adordeberealizarajuste autom ticodelalongituddecarrera antesdelconmutadorDIP6enlaposici nON Se aldesalidadependedelosinterruptoresDIP 2 3 5Ajuste Actuador puede funcionar en modulante DIP 6 a OFF o en...

Page 11: ...5 kanssa 0 2 5 6 V 5 6 10 V SW5 0 2 5 6 V 5 6 10 V HUOMAUTUS T m toiminto on k ytett viss jos kytkin 4 vaiheittainen on m ritetty SW6 Suhteellinen 3 pisteinen JosDIP6onON asennossa moottorilletarvits...

Page 12: ...W3 Direct Inverse Direkt Omgekeerd Fabrieksinstelling Direct SW4 Sequential volgorde Twee motoren kunnen naar hetzelfde signaal luisteren Als Sequential is ingesteld reageert de motor op een gedeeld s...

Page 13: ...funkcja jest dost pna gdy ustawiony jest prze cznik nr 4 Sequential SW6 Proportional 3 point Gdyprze cznikDIP6jestNA Si ownikmusiwykonywa samodostrajaniaprzedzmian ustawie prze cznikaDIP6naON W Sygna...

Page 14: ...I SW2 2 10 V 0 10 V 2 10 V SW3 SW4 0 2 5 6 V 5 6 10 V 5 0 2 V 5 6V 5 6 V 10 V SW5 0 2 V 5 6 V 5 6 10 V 4 SW6 DIP6 DIP6 ON DIP2 3 5 DIP 6 DIP 6 ON SP SN DIP 6 OFF SN 1 3 DIP 6 On 3 ECL caparison Y SW7...

Page 15: ...5 10 50 SN SP DIP U I 2 V_ V 0 V_ V 0 2 V_5 6 V 5 6 V_10 V 3 RL 100 Kvs Red Kvs OFF DIP 6 SW1 U I 0 10 B SW2 2 10B 0 10 B 2 10 B SW3 SW4 0 2 5 6 5 6 10 5 0 2 5 6 5 6 10 SW5 0 2 5 6 5 6 10 4 SW6 DIP 6...

Page 16: ...products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed All trademarks in this mate...

Reviews: