Akva Vita TDP-F - district heating flat station for direct HE and DHW

Troubleshooting  

HE

If operating disturbances occur, the following basic 

features should be checked before carrying out 

actual troubleshooting:

- the substation is connected to electricity  

(applies only to substations with room  

thermostat),

- the strainer on the district heating supply pipe 

is clean,

- the supply temperature of the district heating 

is at the normal level (summer, at least 60 °C 

- winter, at least 70 °C), 

- the differential pressure is higher than or equal 

to the normal (local) differential pressure in the 

district heating network – if in doubt, ask the 

district heating plant,

- there is pressure on the system.

Problem

Possible cause

Solution

No heat

Strainer clogged on DH or HE side 

(radiator circuit).

Filter in the district heating meter 

clogged.

Defective or wrongly adjusted 

differential pressure controller.

Defective room thermostat/actuator  

- or possibly dirt in the zone valve 

housing.

Air pockets in the system.

Clean gate/strainer. 

Clean the filter (after 

consulting the district 

heating plant).

Check the operation of the 

differential pressure 

controller – clean the valve 

seat if required.

Check the operation of the 

room thermostat/actuator 

- clean the zone valve seat if 

required. 

Air the installation 

thoroughly.

Uneven heat 

distribution

Air pockets in the system.

Air the installation 

thoroughly

Supply temperature

too low

Strainer clogged.

Clean gate/strainer.

Poor cooling

Too small heating surface/too small 

radiators in relation to the total 

heating requirement of the building.

Poor utilization of existing heating 

surface.

The system is single-pipe.

Increase total heating 

surface. 

Make sure the heat is 

distributed evenly across 

the full heating surface. It 

is recommended to avoid 

fully opened thermostats 

on some radiators and fully 

shut-off thermostats on 

others. Higher temperature 

at the top and lower 

temperature at the bottom 

part of radiators means that 

the system operation is 

correct.

It is extremely important to 

keep the flow temperature to 

the radiators as low as ever 

possible, while maintaining a 

reasonable level of comfort. 

Summary of Contents for Akva Vita TDP-F

Page 1: ...s DH SMT PL VI KR Z1 02 Danfoss 09 2006 1 Akva Vita TDP F Table of contents Akva Vita TDP F 1 Table of contents 1 Safety notes 2 Delivery 2 Transport and storage 2 Mounting 3 Pipes connections 4 Elect...

Page 2: ...he at station has not been damaged during transport Noise level 55 dB Corrosion protection All pipes and components are made of stainless steel and brass The maximum chloride compounds of the ow mediu...

Page 3: ...pillary tube with union nut from pos 3 to pos 2 Screw the conical screw from pos 2 4 mm on to the mu at pos 3 Connect circulation installation system with connection pipe for circulation Remember pump...

Page 4: ...s the primary supply for the tted substations enabling the Danfoss Redan substations to be used in numerous schemes with di erent energy sources depending on the local operating conditions In order to...

Page 5: ...be equipped with an electronic programmable room thermostat and a zone valve with actuator In this case temperature is controlled by the room thermostat and radiator thermostats Please note that the r...

Page 6: ...If it is not possible to set the temperature according to the above recommendations it is recommended to change the standard controller setting PM controller The PM controller can operate in three ba...

Page 7: ...1 20 C 2 30 C 3 40 C 4 45 C I 50 C max temp 5 Filters Filtersshouldfrequentlybecleanedfromsediments by authorized personnel according to producer s instructions and depending on the at station s oper...

Page 8: ...logged Defective non return valve in thermostatic battery DHW tap temperature lower than DHW from at station Defective non return valve in hot water circulation circulation return pipe is getting cold...

Page 9: ...t in the zone valve housing Air pockets in the system Clean gate strainer Clean the lter after consulting the district heating plant Check the operation of the di erential pressure controller clean th...

Page 10: ...33 35 DK 8240 Risskov Denmark Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk Akva Vita TDP F district heating at station for direct HE and DHW Instructions DH SMT PL VI...

Reviews: