Troubleshooting  

DHW

Problem

Possible cause

Solution

In general: Does the PM 

controller work incorrectly?

If the quantity of tapping water  

is normal (temperature 

unimportant) it indicates that the 

PM controller works correctly.

Locate defect in another part 

of the installation  

(see below)

In general: Are the operating  

conditions satisfactory?

The flat station requires a DH 

supply temperature of minimum 

60 °C and a differential pressure 

during operation according to the 

information stated in the product 

sheet for Akva Vita TDP-F.

Contact district heating 

supplier.

PM controller leaking; 

Water leaking from Allen

screws at the central part of

PM controller.

One of the two O-rings is defective 

(does not influence the PM 

operation). If a non-return valve is 

installed in the DCW inlet (e.g. in 

the house service connection or in 

DCW meter) a safety valve should be 

mounted between the non-return 

valve and the heat exchanger.

Replace PM controller  

(use new sealing).

DHW tap load too low

The diaphragm of the PM controller 

is defective.

Replace diaphragm 

or PM controller.

DHW tap load too low;

Tap temperature too low;

Tap temperature fluctuates;

PM controller wrongly  

adjusted,

Strainer in DH supply clogged,

Defective non-return valve in 

thermostatic battery (DHW tap 

temperature lower than DHW from 

flat station),

Defective non-return valve in hot-

water circulation (circulation return 

pipe is getting cold during tapping 

of hot water),

Lime scale precipitation in the plate 

heat exchanger for DHW (primary Δt 

too low during DHW tapping),

Dirt in PM controller,

DCW flow too high (big nominal 

diameter of pipe, high DCW 

pressure), in total max. 16-17 litres 

per minute.

Setting, see 

Regulation 

chapter.

Clean strainer.

Clean or replace non-return 

valve.

Clean or replace non-return 

valve.

Replace the plate heat  

exchanger.

Cleaning, see 

PM controller 

instruction.

DCW reduction. 

DH return water temperature 

too high while on standby;  

The plate heat exchanger is 

cold…

The by-pass thermostat is defective 

or wrongly adjusted.

Replace or adjust by-pass 

thermostat correctly

DH return water temperature 

too high while on standby;  

The plate heat exchanger is 

hot…

Dirt (sand, iron splinters or similar) 

in PM controller. Controller does not 

close. Noise from flow can often be 

heard.

Move handle several times 

between red and blue 

markings; at the same 

time do several hot-

water tappings. Clean PM 

controller.

Primary return temperature 

too high during hot water 

tapping.

Lime scale precipitation in the plate 

heat exchanger for DHW 

Replace plate heat exchanger 

Connecting pieces of the PM  

controller do not fit the flat 

station

In particular when replacing PM 

controller in old flat station

Loosen Allen screws; turn 

half of the PM controller 

180°

Summary of Contents for Akva Vita TDP-F

Page 1: ...s DH SMT PL VI KR Z1 02 Danfoss 09 2006 1 Akva Vita TDP F Table of contents Akva Vita TDP F 1 Table of contents 1 Safety notes 2 Delivery 2 Transport and storage 2 Mounting 3 Pipes connections 4 Elect...

Page 2: ...he at station has not been damaged during transport Noise level 55 dB Corrosion protection All pipes and components are made of stainless steel and brass The maximum chloride compounds of the ow mediu...

Page 3: ...pillary tube with union nut from pos 3 to pos 2 Screw the conical screw from pos 2 4 mm on to the mu at pos 3 Connect circulation installation system with connection pipe for circulation Remember pump...

Page 4: ...s the primary supply for the tted substations enabling the Danfoss Redan substations to be used in numerous schemes with di erent energy sources depending on the local operating conditions In order to...

Page 5: ...be equipped with an electronic programmable room thermostat and a zone valve with actuator In this case temperature is controlled by the room thermostat and radiator thermostats Please note that the r...

Page 6: ...If it is not possible to set the temperature according to the above recommendations it is recommended to change the standard controller setting PM controller The PM controller can operate in three ba...

Page 7: ...1 20 C 2 30 C 3 40 C 4 45 C I 50 C max temp 5 Filters Filtersshouldfrequentlybecleanedfromsediments by authorized personnel according to producer s instructions and depending on the at station s oper...

Page 8: ...logged Defective non return valve in thermostatic battery DHW tap temperature lower than DHW from at station Defective non return valve in hot water circulation circulation return pipe is getting cold...

Page 9: ...t in the zone valve housing Air pockets in the system Clean gate strainer Clean the lter after consulting the district heating plant Check the operation of the di erential pressure controller clean th...