Akva Vita TDP-F - district heating flat station for direct HE and DHW

Control

1.  Differential pressure controller

The differential pressure controller reduces the 

fluctuating pressure in the district heating network 

to a small and invariable operating pressure in 

the flat station. The required room temperature 

is controlled on your radiator thermostats (fixed 

setting throughout the year). It is recommended that 

all

 radiators are opened a little in each room.

The flat station can be equipped with dp controller 

type  TD200  or  AVPL,  depending  on  customer 

demand.

TD200

The differential pressure controller is preset from 

factory and 

should not be

 adjusted afterwards. 

AVPL

The AVPL must be mounted in the return. The dp 

controller can be set at any differential pressure 

between 5 kPa and 25 kPa (0,05 bar and 0,25 bar). 

The dp controller is preset on 10 kPa (0,1 bar)  and 

can be adjusted afterwards.

2. HE temperature control

The HE temperature in the house is controlled 

by 

radiator thermostats

. As an option the Akva 

Vita TDP-F flat station can be equipped with an 

electronic programmable room thermostat

 

and  a 

zone  valve

  with 

actuator

.  In  this  case 

temperature is controlled by the room thermostat 

and radiator thermostats. Please note that the room 

thermostat keeps the temperature in the whole 

apartment according to setting room parameters. 

Consult additional maintenance instructions for 

room  thermostat  for  further  information.  It  is 

recommended to avoid fully opened thermostats 

on some radiators and fully shut-off thermostats 

on others. Higher temperature at the top and lower 

temperature at the bottom part of radiators means 

that the system operation is correct. To keep correct 

temperature and friendly microclimate for human 

beings in the apartment, it is recommended to 

ensure regular airing in rooms.

3. Limiting flow controller (return flow)

Optional substation equipment, which is mounted 

on district heating company request. Limiting flow 

controller should be set to the required maximum 

return temperature, in compliance with the local 

demands.

Approximate thermostat scale setting:

I  =  10 ° C

1 =  20 ° C 

2 =  30 ° C

3 =  40 ° C

4 =  45 ° C

I  =  50 ° C (max. temp.)

To ensure sufficient cooling and proper operation 

the HE return temperature (thermometer indication 

on  secondary  return)  must  be  lower  than  the 

temperature set on the flow controller.

Summary of Contents for Akva Vita TDP-F

Page 1: ...s DH SMT PL VI KR Z1 02 Danfoss 09 2006 1 Akva Vita TDP F Table of contents Akva Vita TDP F 1 Table of contents 1 Safety notes 2 Delivery 2 Transport and storage 2 Mounting 3 Pipes connections 4 Elect...

Page 2: ...he at station has not been damaged during transport Noise level 55 dB Corrosion protection All pipes and components are made of stainless steel and brass The maximum chloride compounds of the ow mediu...

Page 3: ...pillary tube with union nut from pos 3 to pos 2 Screw the conical screw from pos 2 4 mm on to the mu at pos 3 Connect circulation installation system with connection pipe for circulation Remember pump...

Page 4: ...s the primary supply for the tted substations enabling the Danfoss Redan substations to be used in numerous schemes with di erent energy sources depending on the local operating conditions In order to...

Page 5: ...be equipped with an electronic programmable room thermostat and a zone valve with actuator In this case temperature is controlled by the room thermostat and radiator thermostats Please note that the r...

Page 6: ...If it is not possible to set the temperature according to the above recommendations it is recommended to change the standard controller setting PM controller The PM controller can operate in three ba...

Page 7: ...1 20 C 2 30 C 3 40 C 4 45 C I 50 C max temp 5 Filters Filtersshouldfrequentlybecleanedfromsediments by authorized personnel according to producer s instructions and depending on the at station s oper...

Page 8: ...logged Defective non return valve in thermostatic battery DHW tap temperature lower than DHW from at station Defective non return valve in hot water circulation circulation return pipe is getting cold...

Page 9: ...t in the zone valve housing Air pockets in the system Clean gate strainer Clean the lter after consulting the district heating plant Check the operation of the di erential pressure controller clean th...

Page 10: ...33 35 DK 8240 Risskov Denmark Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk Akva Vita TDP F district heating at station for direct HE and DHW Instructions DH SMT PL VI...