Akva Vita TDP-F - district heating flat station for direct HE and DHW

Instructions

DH-SMT/PL

VI.KR.Z1.02  ©

  Danfoss 09/2006

2

Safety notes

Following instructions refer to the standard 

design  of  the  Akva  Vita  TDP-F  flat  station. 

Special versions of flat stations are available 

on request.

To avoid injury of persons and damages to the 

device, it is absolutely necessary to carefully read 

and observe these instructions.

Necessary assembly, start-up and maintenance 

work must only be performed by qualified and 

authorized personnel. 

Please comply with the instructions of the system 

manufacturer or system operator.

Unused connections and shut-off valves must be 

sealed with a plug. The plugs can be removed by 

an authorized service technician only. 

Warning of high pressure and temperature

The maximum temperature of the flow medium in 

a flat station is 90 °C.

The maximum operating pressure of the flat station 

is 10 bar.

Be aware of the installation’s permissible system 

pressure and temperature. 

The risk of persons being injured and equipment 

damaged  increases  considerably  if  the 

recommended permissible operating parameters 

are exceeded. 

We recommend installation of safety valve, how-

ever, always in accordance with local regulations.

Warning of hot surface

The flat station has got hot surfaces, which can 

cause skin burns. Please be extremely cautious in 

close proximity to the flat station.

Warning of transport damage

Before installation of flat station, please make sure 

that the flat station has not been damaged during 

transport. 

Noise level

≤ 55 dB

Corrosion protection

All pipes and components are made of stainless 

steel and brass.

The maximum chloride compounds of the flow 

medium should not exceed 300 mg/l.

The  risk  of  equipment  corrosion  increases 

considerably if the recommended permissible 

chloride compounds are exceeded.

Delivery

The Akva Vita TDP-F flat station is delivered without 

cover as a standard.

Optional flat station equipment:

- thermostatic by-pass,

- connection pipe for circulation,

- circulation pump,

- safety valve / non-return valve,

- return temperature limiter,

- DHW flow limiter

- ball valves w. and w/o pocket for pressure/

thermometer gauge 3/4” ext. thread

- ball valves w and w/o pocket for pressure/

thermometer gauge 3/4 int. thread 

- thermometer Ø35

- zone valve with actuator

- connection rail with 7 connections 3/4” (int. 

thread), insulated or non-insulated,

- room thermostat with day and /or week 

program,

- heat meter (DH supply),

- cold water meter

- white-lacquered steel sheet cover

Standard delivery:

The flat station is prepared for by-pass or DHW 

circulation control. Equipment for by-pass or DHW 

circulation control is optional equipment and must 

be ordered separately.

In case of DHW circulation control remember to 

mount circulation pump and non-return valve 

(this is not part of the delivery and must be fitted 

remotely on site).

Transport and storage

If the flat station is stored before installation in a 

warehouse or any other room, make sure that the 

place is dry and heated.

During transport of the flat station to an installation 

place it is recommended to lift it with special straps 

attached to the bottom (by flat station support 

construction).

Summary of Contents for Akva Vita TDP-F

Page 1: ...s DH SMT PL VI KR Z1 02 Danfoss 09 2006 1 Akva Vita TDP F Table of contents Akva Vita TDP F 1 Table of contents 1 Safety notes 2 Delivery 2 Transport and storage 2 Mounting 3 Pipes connections 4 Elect...

Page 2: ...he at station has not been damaged during transport Noise level 55 dB Corrosion protection All pipes and components are made of stainless steel and brass The maximum chloride compounds of the ow mediu...

Page 3: ...pillary tube with union nut from pos 3 to pos 2 Screw the conical screw from pos 2 4 mm on to the mu at pos 3 Connect circulation installation system with connection pipe for circulation Remember pump...

Page 4: ...s the primary supply for the tted substations enabling the Danfoss Redan substations to be used in numerous schemes with di erent energy sources depending on the local operating conditions In order to...

Page 5: ...be equipped with an electronic programmable room thermostat and a zone valve with actuator In this case temperature is controlled by the room thermostat and radiator thermostats Please note that the r...

Page 6: ...If it is not possible to set the temperature according to the above recommendations it is recommended to change the standard controller setting PM controller The PM controller can operate in three ba...

Page 7: ...1 20 C 2 30 C 3 40 C 4 45 C I 50 C max temp 5 Filters Filtersshouldfrequentlybecleanedfromsediments by authorized personnel according to producer s instructions and depending on the at station s oper...

Page 8: ...logged Defective non return valve in thermostatic battery DHW tap temperature lower than DHW from at station Defective non return valve in hot water circulation circulation return pipe is getting cold...

Page 9: ...t in the zone valve housing Air pockets in the system Clean gate strainer Clean the lter after consulting the district heating plant Check the operation of the di erential pressure controller clean th...

Page 10: ...33 35 DK 8240 Risskov Denmark Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk Akva Vita TDP F district heating at station for direct HE and DHW Instructions DH SMT PL VI...