On/Off Tab
The example below shows the Misc On/Off tab. Navigate down
the control lines and configure as required.
On/Off Tab
Depending on control require-
ments the screen layout may
differ.
Navigate though the options,
adding custom name, AK I/O
address, alarms
Example of On/Off Inputs Tab
Name:
Enter custom description for Input
Bd-Pt:
Enter a valid Board & Point address (using AK I/O modules)
Broadcast:
No:
The value of the point will not be broadcast to be used in
logic on other controllers.
Send:
The value of the point (whether it is ON or OFF) will be
available on the host network for use by other controllers. Be
sure that each sending Board-Point combination is unique
throughout the system. (If the controller at address #01 is
sending from its Bd-Pt address 1-02, then no other controller
can have an output at its Bd-Pt address 1-02 sending.
Rec
: The value of the point is being received from another
controller on the host network. You must enter, in the Bd-Pt
fields, the Bd-Pt address of the sending point.
Type:
Select from various option in the drop down list
Voltage:
Voltage Input
No Voltage:
No Voltage Input
Latching:
Latching Input
Closed:
Closed Input
Open:
Open Input
Number of alarms:
Enter the amount of alarms (max 3)
Alarm 1:
Enter the alarm level (Disabled, Log only, Normal,
Severe, Critical)
Type:
Alarm if above or if below limit (seen below)
Limit:
Enter the alarm limit
Delay:
Enter delay time
Units:
Seconds, Minutes, Hours
From:
Defines alarm output time window
To:
Defines alarm output time window
Days:
Define the days associated with alarm
Action:
Define the alarm action