The ‘Suction group mapping’ screen allows for the defined
evaporator devices to be ‘mapped’ under the required Pack
controller. This mapping forms a relationship or grouping
between the pack and the evaporator devices. This grouping
association will then be seen in the AK-SM configuration and
dashboard screens (and can be used to easily set up master
control functions like Suction optimization).
As the user description indicates, use a drag and drop action to
group your controls. Use the CTRL key and multi-select cases to
save time when making bulk actions. You can remove any case
devices by simply dragging back to the available case list.
The check box labelled ‘Allow multi-case circuit creation’ is to
support Centralized refrigeration control configuration, where
multiple case circuits are available’. Leave this check box empty if
you are using a de-centralized control strategy (i.e. Case and pack
controllers)
Once satisfied with the mapping, press the forward button and
the summary screen will be shown. Pressing the finish button
will then send your configuration layout to the AK-SM. During
this time a progress bar will be shown and finally a status
dialogue box.
This completed wizard process will layout your refrigeration
application. Typically some additional configuration tasks will
then need to be completed (i.e. define alarms, setpoint changes,
configure history), please refer to the following section for further
details on detailed configuration.