Relay Tab
Depending on control require-
ments the screen layout may
differ.
Navigate though the options,
adding custom name, AK I/O
address, alarms, pre and post
delays etc.
Note: Setting Broadcast to yes
will make available the relay
status on the AK-SM host
network.
If a control input is needed to
operate your misc relay, this can
be selected on the Control Input
line (you will need to configure
your control input in advance)
Name:
Enter custom description for relay
Bd-Pt:
Enter a valid Board & Point address (using AK I/O modules)
Broadcast:
No:
The value of the point will not be broadcast to be used in
logic on other controllers.
Send:
The value of the point (whether it is ON or OFF) will be
available on the host network for use by other controllers. Be
sure that each sending Board-Point combination is unique
throughout the system. (If the controller at address #01 is
sending from its Bd-Pt address 1-02, then no other controller
can have an output at its Bd-Pt address 1-02 sending.
Rec
: The value of the point is being received from another
controller on the host network. You must enter, in the Bd-Pt
fields, the Bd-Pt address of the sending point.
Type:
Normally Closed or Normally Open
Control Input:
It is possible to use other defined points (includ-
ing calculations) to act as the control Input - these will be seen in
a drop down list
Minimum Off:
Define a min off time period to stop short cycling
Pre Delay:
Define a pre time delay before the relay activates
Minimum On:
Define a min on time period to stop short cycling
Post Delay:
Define a post time delay to minimize short cycling
Number of alarms:
Enter the amount of alarms (max 3)
Alarm 1:
Enter the alarm level (Disabled, Log only, Normal,
Severe, Critical)
Type:
Alarm if ON, Alarm if OFF, Cycles (enter number of
cycles)
Delay:
Enter delay time
Units:
Seconds, Minutes, Hours
From:
Defines alarm output time window
To:
Defines alarm output time window
Days:
Define the days associated with alarm
Action:
Define the alarm action
Example of Misc Relays Tab
If configured,
navigate to
additional relays via
the drop down box
Relays Tab
The example below shows the Misc Relays tab. Navigate down
the control lines and configure as required.
Any Misc points configured in the AK-SM
system will be shown in the ‘System View’
under the Power/Misc window
AK-SM 850
User Guide