Manual RS8FB102 © Danfoss 03-2008 

AK-PI 

100

Introduction

Function

The AK-PI 100 is an intermediary link allowing Woodley type units 

to be operated by an AK-SC 255 system controller. 

This way of operating the Woodley units replaces the previous 

Woodley S5 operating interface.

Application

The AK-PI 100 is used on systems with an AK-SC 255 system con-

troller, but which still contain older Woodley type units. 

These types can be:

• Woodley MDM units

• Woodley 4 way TPI cards

• Older units connected to the WTP bus (WTP = Woodley Third 

Party)

Measurements and status readings from the individual Woodley 

units are uploaded to the AK-PI 100 and on to the AK-SC 255, 

where the data is presented in the same way as other ADAP-

KOOL(r) units. 

Principle

The AK-SC 255 and the AK-PI 100 are linked by Ethernet.

 

For a straightforward connection, the two units can be linked by a 

switch.

In this case, the IP addresses are set to static addresses. You can 

choose any addresses, 

but only

 if nothing else is connected.

(It is easiest to use a router and dynamic address allocation. In this 

case, the router allocates one address to the AK-SC 255 and an-

other to the PI unit. You can only use this solution if the system is 

self-contained with no contact to an external operating interface.)

In larger systems or if IP communication takes place from the sys-

tem, the connection must be based on a router or a switch.

If a router is used, the IP address of the AK-PI 100 may be dynamic, 

but the address of the AK-SC 255 must be static.

If a switch is used, both must be static.

You will need to request static addresses from the IT department 

yourself, and then configure the addresses in both units. You 

should always use this solution if the system is accessed by an 

external service company, for example for log extraction, alarm 

handling or servicing. 

Summary of Contents for AK-PI 100

Page 1: ...Woodley Protokol interface AK PI 100 User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...orward connection the two units can be linked by a switch In this case the IP addresses are set to static addresses You can choose any addresses but only if nothing else is connected It is easiest to...

Page 3: ...200 screen Each PI unit is configured with a different address You can choose 11 12 or above e g 21 Addresses 1 to 10 are reserved for sub nets Connection When you configure the system controller the...

Page 4: ...d In the AK PI 100 set IP addressing to either static or dynamic Choose static if the AK SC 255 and AK PI 100 are linked by a switch Then configure the IP address request an IP address from the IT of...

Page 5: ...ith Communications I O Network Rescan channels Select the Channel PI 100 200 field Activate the Rescan Network function Click the PI 100 200 button to switch to the next screen Select the addresses to...

Page 6: ...rols Specify the description file Select No for Pack controller Select the number of controllers in this example 10 Click the Setup button to switch to the next screen Click Edit on the first controll...

Page 7: ...ss to the following The configuration lock is used with the following settings Communication setting MDM or WTP Address offset setting addresses are configured for all units on the communication line...

Page 8: ...VA Supply 080Z0053 RS 232 cable between AK PI 100 and Woodley MDM 4 way TPI card 080Z0263 Type Function Application Language Code no AK PI 100 Protokol interface Intermediary link between System cont...

Reviews: