AK-PI 

100 

Manual RS8FB102 © Danfoss 03-2008 

7

Overview of functions in the 

AK-PI 100

Example of IP addresses

Examples of controller addresses

The overview display will show the following:

• Status of alarm transmission

• Date and time

• Quality of the signal for communication with the Woodley MDM 

unit or to Woodley TPI unit (the value is always 0 if the service 

tool is attached).

The configuration display gives access to the following:

• The configuration lock is used with the following settings:

- Communication setting (MDM or WTP)

- Address offset setting (addresses are configured for all units on 

the communication line. If these address values conflict with 

other addresses, the entire connected group can be “offset”. For 

example a group of units has the addresses 20 to 31. By setting 

“Address offset” to 50, the address will become 70 to 81 in the 

AK-SC 255. This removes the need to change the addresses of 

the existing units). 

- Adjustment of a static IP address.

• In “System setup” you can give the unit a name

• You can change the IP setup

Summary of Contents for AK-PI 100

Page 1: ...Woodley Protokol interface AK PI 100 User Guide ADAP KOOL Refrigeration control systems...

Page 2: ...orward connection the two units can be linked by a switch In this case the IP addresses are set to static addresses You can choose any addresses but only if nothing else is connected It is easiest to...

Page 3: ...200 screen Each PI unit is configured with a different address You can choose 11 12 or above e g 21 Addresses 1 to 10 are reserved for sub nets Connection When you configure the system controller the...

Page 4: ...d In the AK PI 100 set IP addressing to either static or dynamic Choose static if the AK SC 255 and AK PI 100 are linked by a switch Then configure the IP address request an IP address from the IT of...

Page 5: ...ith Communications I O Network Rescan channels Select the Channel PI 100 200 field Activate the Rescan Network function Click the PI 100 200 button to switch to the next screen Select the addresses to...

Page 6: ...rols Specify the description file Select No for Pack controller Select the number of controllers in this example 10 Click the Setup button to switch to the next screen Click Edit on the first controll...

Page 7: ...ss to the following The configuration lock is used with the following settings Communication setting MDM or WTP Address offset setting addresses are configured for all units on the communication line...

Page 8: ...VA Supply 080Z0053 RS 232 cable between AK PI 100 and Woodley MDM 4 way TPI card 080Z0263 Type Function Application Language Code no AK PI 100 Protokol interface Intermediary link between System cont...