HIGH PRESSURE MODULE
Supply voltage to high pressure module

The power supply can be taken from the main module.

Battery

Ensure that the valve closes if there is no supply voltage.

Stepper valve 

FX ventil type CCMT. 
Connector:
A1 5: WHITE
A2 6: BLACK
B1 7: RED
B2 8: GREEN

CANBUS

Data communication to the main module.

Sensor inputs

• Pt 1000 ohm, AKS 11 or  AKS 21.

Contact input AUX 2

Signal from oil level, 
or input for fan alarm or another alarm.

Relay output AUX 2

Activation of de-superheating or hot gas dump.

MODBUS

Data communication with other devices. 
It is important that the installation of the data communication 
cable is performed correctly.
See separate literature no. RC8AC...
Remember termination at the termination points. Use a twisted 
pair shielded cable, but do not connect the shield to the EKE 1P.

RECEIVER MODULE
Supply voltage to high pressure module

The power supply can be taken from the main module.

Battery

Ensure that the valve closes if there is no supply voltage.

Stepper valve 

FX valve type CCMT. 
Connector:
A1 5: WHITE
A2 6: BLACK
B1 7: RED
B2 8: GREEN

CANBUS

Data communication to the main module.
The section must be terminated using a 120 ohm resistor.

Contact input AUX 3

Signal from heat recovery, 
or input for fan alarm or another alarm.

Relay output AUX 3

Activation of heat recovery, 
or AUX 3 output for de-superheating or hot gas dump.

MAIN MODULE
AO - Analogue output, 3 pcs. AO1, AO3, AO4

Must be used if using frequency converters or EC motors. 
Connect 24 V on N and L (separate power supply) Avoid earth fault 
current.
 - Use double-insulated transformer. The secondary side must not 
be earthed. 
Obtain 0-10 volts from terminals Com-AO1, N-AO3 and N-AO4. 
PAY ATTENTION TO THE POLARITY of N.
(AO3 and AO4 are galvanically isolated. AO1 is not).

AI - Analogue inputs

Pressure transmitters, 4 pcs. AI1 - AI4

AKS 32R /
AKS 2050 /
MBS 8250

10 – 90% ratiometric

Temperature sensors, 4 pcs. AI5 - AI8

• Pt 1000 ohm, AKS 11 or AKS 21.

DI - Digital switch inputs, 8 pcs. DI1 - DI8

The connection may be a shut-down or interruption function. 
Select what is to be activated during configuration.
(DI3 can be used as an AUX1 input, but only if regulated with 2 MT 
compressors).

Supply

24 V AC or DC Class II is required.

AK-PC 572 

17 VA

EKE 1P 

20 VA

CANBUS

Communication to the high pressure module and to the receiver 
module
"L" to "L" and "H" to "H" 
A jumper must be connected between "H" and "R".
Terminate on the AK-PC with a resistance of 120 ohm. 
If mounting an external display, the termination must also be done 
at the display. See next page.

Important!
In order to establish communication with the extension modules, you 
must follow the recommended procedure. See next page.

MODBUS

It is important that the installation of the data communication 
cable is carried out correctly. See separate literature no. RC8AC...
Remember termination at the termination points.

DO - Digital outputs, 8 pcs.  DO1-DO8

DO5 and DO6 are solid state relays. The outputs are used for 
connecting a Bitzer CRII. If a Bitzer CRII is not being connected, 
output DO6 can be used for activation of an oil valve.
The relays are de-rated to the specified values.
The alarm relay will be driven under normal operation and 
will drop in the event of alarms and insufficient voltage to the 
controller.  
(DO3 can be used as an AUX1 output, but only if regulated with 2 
MT compressors).

Summary of Contents for AK-PC 572

Page 1: ...Dimens o Dimensie Dimension Dimensi n Identification Identifica o Identificatie Identification Identificaci n Power supply Fonte de energia Stroomvoorziening Source de courant Fuente de alimentaci n A...

Page 2: ...96 and 97 you must fol low the recommended procedure See page 4 ENGLISH Fan 0 10 V EKE 1P CAN RJ GND Bat A1 A2 B1 B2 NO1 C1 NC1 GND Bat A1 A2 B1 B2 NO1 C1 NC1 B A Oil DI Aux 2 DO AUX 2 Vhp LT Sd LT SS...

Page 3: ...ault current Use double insulated transformer The secondary side must not be earthed Obtain 0 10 volts from terminals Com AO1 N AO3 and N AO4 PAY ATTENTION TO THE POLARITY of N AO3 and AO4 are galvani...

Page 4: ...r module Alternatively the EKE 1P configuration may be set by connecting a graphical display to the EKE 1P See separate EKE 1P documenta tion If you wish to check the addresses of the two valve module...

Page 5: ...e 97 preciso seguir o procedimento recomendado Consulte a p gina 7 PORTUGU S EKE 1P CAN RJ GND Bat A1 A2 B1 B2 NO1 C1 NC1 GND Bat A1 A2 B1 B2 NO1 C1 NC1 B A Oil DI Aux 2 DO AUX 2 Vhp LT Sd LT SS 24 V...

Page 6: ...u motores EC Conecte 24 V em N e L fonte de alimenta o separada Evite a cor rente de falha de aterramento Use um transformador com isolamento duplo O lado secund rio n o deve ser aterrado Obtenha 0 10...

Page 7: ...icar os endere os dos dois m dulos de v lvula fa a o seguinte 1 conecte todos os m dulos fonte de alimenta o 2 Pressione imediatamente os bot es X e Enter enquanto o controlador estiver iniciando 3 En...

Page 8: ...vorgehen um die Adressen 96 und 97 zu festzulegen Siehe Seite 11 DEUTSCH EKE 1P CAN RJ GND Bat A1 A2 B1 B2 NO1 C1 NC1 GND Bat A1 A2 B1 B2 NO1 C1 NC1 B A Oil DI Aux 2 DO AUX 2 Vhp LT Sd LT SS 24 V M HR...

Page 9: ...Sie einen Erdschlussstrom Verwenden Sie doppelt isolierte Transformatoren Die sekund re Seite darf nicht geerdet werden 0 10 Volt erhalten Sie von den Klemmen Com AO1 N AO3 und N AO4 ACHTEN SIE AUF DI...

Page 10: ...an die Spannungsversorgung anschlie en Um die Adressen der beiden Ventilmodule zu berpr fen gehen Sie wie folgt vor 1 Schlie en Sie alle Module an die Spannungsversorgung an 2 Dr cken Sie dann sofort...

Page 11: ...les adresses 96 et 97 suivre la proc dure conseill e Voir page 13 FRAN AIS EKE 1P CAN RJ GND Bat A1 A2 B1 B2 NO1 C1 NC1 GND Bat A1 A2 B1 B2 NO1 C1 NC1 B A Oil DI Aux 2 DO AUX 2 Vhp LT Sd LT SS 24 V M...

Page 12: ...limentation distincte viter le courant de d faut la terre Utiliser un transformateur double isolation Le c t secondaire ne doit pas tre mis la terre Obtenir 0 10 V des bornes Com AO1 N AO3 et N AO4 VE...

Page 13: ...alimentation lire ce qui suit Pour v rifier les adresses des deux modules vanne proc der comme suit 1 Brancher tous les modules sur la prise d alimentation 2 Appuyer imm diatement sur les boutons X et...

Page 14: ...s direcciones 96 y 97 se debe seguir el procedimiento recomendado Consulte la p gina 16 ESPA OL EKE 1P CAN RJ GND Bat A1 A2 B1 B2 NO1 C1 NC1 GND Bat A1 A2 B1 B2 NO1 C1 NC1 B A Oil DI Aux 2 DO AUX 2 Vh...

Page 15: ...L fuente de alimentaci n independiente Evite la corriente de fallo a tierra Utilice un transformador con aislamiento doble El lado secundario no debe conectarse a tierra Obtenga 0 10 V de los terminal...

Page 16: ...antes de conectar el controlador y los dos m dulos de v lvulas a la tensi n de alimentaci n Si desea comprobar las direcciones de los dos m dulos de v lvulas debe llevar a cabo las siguientes acciones...

Reviews: