Danfoss AK-CC 460 User Manual Download Page 27

Coordinated defrost via 
data communication

Coordinated defrost via 
cable connections

The following controllers can be connected 

up in this way:
EKC 204A, AK-CC 210, AK-CC 250, 
AK-CC 450, AK-CC 460, AK-CC 550,

Refrigeration is resumed when all 
controllers have “released” the signal for 
defrost.

The setting of controllers to coordinate 
their defrosting takes place in the 
gateway/system manager.

Refrigeration is resumed when all 
controllers have “released” the signal for 
defrost.

Supply voltage

230 V AC

DO1

Compressor 1 (only application 1 and 3)

Connection of relay for compressor. The coil must be a 230 V AC 
coil.

DO2

Alarm

There is a connection between terminal 7 and 8 in alarm 
situations and when the controller is without power.

DO3

Compressor 2,

There is connection between terminal 10 and 11 when the 
compressor must be active
In application 2 this output is used for compressor start signal

DO4

Defrost

There is connection between terminal 12 and 14 when 
defrosting takes place.

DO5

Fan

There is connection between terminal 15 and 16 when the fan 
is on.

DO6

Light relay

There is connection between terminal 17 and 18 when the 
light must be on. If night blinds are used, they should be 
connected here.

DO7

Rail heat

There is connection between terminal 20 and 21, when the rail 
heat is active.

DI3

Digital input signal.

  

Compressors safety circuit (OK at 230V)
The signal must have a voltage of 0 / 230 V AC. 

Data communication

If data communication is used, it is important that the installation 
of the data communication cable is performed correctly.
See separate literature No. RC8AC…

Electric noise

Cables for sensors, DI inputs and data communication must be 

kept separate from other electric cables:

- Use separate cable trays

- Keep a distance between cables of at least 10 cm

- Long cables at the DI input should be avoided

Installation considerations

Accidental damage, poor installation, or site conditions, can give 
rise to malfunctions of the control system, and ultimately lead to a 
plant breakdown.
Every possible safeguard is incorporated into our products to 
prevent this. However, a wrong installation, for example, could still 
present problems. Electronic controls are no substitute for normal, 
good engineering practice.
Danfoss wil not be responsible for any goods, or plant compo-
nents, damaged as a result of the above defects. It is the installer's 
responsibility to check the installation thoroughly, and to fit the 
necessary safety devices.
Special reference is made to the necessity of signals to the 
controller when the compressor is stopped and to the need of 
liquid receivers before the compressors.
Your local Danfoss agent will be pleased to assist with further 
advice, etc.
 

Max. 10

User Guide | Controller for SemiPlugin appliance, AK-CC 460

© Danfoss | DCS (vt) | 2019.12

BC230086440483en-000201 | 27

Summary of Contents for AK-CC 460

Page 1: ...User Guide Controller for SemiPlugin appliance AK CC 460 www danfoss com...

Page 2: ...iance The temperature of the evaporator is registered with the S5 sensor which can be used as a defrosting sensor In addition to the output for the compressors the controller has 5 relay outputs for d...

Page 3: ...ll continue until the temperature has reached the cut out value Then it will cut out When the temperature again reaches the middle of the differential compressor 1 will be cutin to the circuit again I...

Page 4: ...digital input Separate thermostat and alarm limits can be set for each thermo stat band also for the product sensor Night setback of thermostat value In refrigeration appliances there may be big load...

Page 5: ...methods Natural Here the fans are kept operating during the defrost Electric The heating element is activated Defrost sequence 1 Defrost 2 Waiting position after defrost 3 Drip off 4 Delay of fan Star...

Page 6: ...oup is in a waiting position refrigeration is again permitted in all the individual controllers Defrost on demand Based on refrigeration time When the aggregate refrigeration time has passed a fixed t...

Page 7: ...Pulse control can be accomplished in one of the following ways during the thermostat s cutout period cold room during night operation and during the thermostat s cutout pe riod appliance with night l...

Page 8: ...Main switch is set to off see o98 When the night blind rolls down the fans can be stopped so that the air circulation does not interrupt the positioning of the blind The desired stop time must be set...

Page 9: ...the display can advantageously be changed to a type with screw terminals I e the type EKA 163A or EKA 164A If connection of two displays is required one must be connected to the plug max 15 m and the...

Page 10: ...ust S4 Correction of signal from S3 Compensation possibility due to long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started stopped or a manual overr...

Page 11: ...ediately after a defrost There will be change over to the normal time delay A03 when the temperature has dropped below the set upper alarm limit The time delay is set in minutes A12 Pulldown del Upper...

Page 12: ...c01 Min On time Min OFF time in minutes c02 Min Off time Time delay for couplings of two compressors Settings indicate the time that has to elapse from the first relay cuts in and until the next rela...

Page 13: ...take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communication the interval time must be set for a somewhat longer period of tim...

Page 14: ...ill not provide heat to the appliance If the defrost sensor registers a higher temperature than the one set here the fans will be stopped There will be re start at 2 K below the setting The function i...

Page 15: ...the night blinds 13 14 Not used 15 Case Shutdown when input is closed o02 DI 1 Config Definition takes place with the numerical value shown to the left 0 off DI state Measurement The DI input s presen...

Page 16: ...setting is selected to either 2 or 3 When the door is opened the relay will cut in When the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but i...

Page 17: ...is off 1 Light and night blind is independent of main switch o98 Light MS Off Configuration of the alarm relay The alarm relay will be activated upon an alarm signal from the following groups 1 High...

Page 18: ...2 u86 Ther band Status on input DI3 on 1 230 V u87 DI3 status Readout of the actual cutin value for the thermostat u90 Cutin temp Readout of the actual cut out value for the thermostat u91 Cutout temp...

Page 19: ...compressor is stopped it must remain stopped for at least x minutes S3 3 The evaporator drips off and waits for the time to run out S4 4 Refrigeration stopped by main switch Either with r12 or a DI in...

Page 20: ...igh S6 1 A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigeration via r12 or DI input A59 Case clean Case...

Page 21: ...If there are several alarm codes they are found in a rolling stack Push the uppermost or lowermost button to scan the rolling stack Set temperature 1 Push the middle button until the temperature value...

Page 22: ...ure alarm after defrost A12 1 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 1 50 C 50 C 30 High alarm limit for thermostat 2 A20 1 1 5...

Page 23: ...5 1 1 0 2 0 Period time for fan pulsation on time off time F06 1 1 1 min 30 min 5 On time in of period time F07 1 1 0 100 100 Real time clock Six start times for defrost Setting of hours 0 OFF t01 t06...

Page 24: ...s o67 1 1 0 Off 1 On 0 Off Rail heat control 0 not used 1 pulse control with timer function o41 and o42 2 pulse control with dew point function o85 1 1 0 2 0 Dew point value where the rail heat is min...

Page 25: ...rmostat temperature u17 1 1 Run time of thermostat cooling time in minutes u18 1 1 Temperature measured with S6 sensor product temperature u36 1 1 Status on DI2 output on 1 closed u37 1 1 Readout of t...

Page 26: ...nserted in the controller The module can be a LON RS485 DANBUSS or a MODBUS Terminal 51 screen Terminal 52 A A Terminal 53 B B For LON RS485 and gateway type AKA 245 the gateway must be version 6 20 o...

Page 27: ...Digital input signal Compressors safety circuit OK at 230V The signal must have a voltage of 0 230 V AC Data communication If data communication is used it is important that the installation of the da...

Page 28: ...nal for variable speed control Relays CE 250 V AC IBExU approved DO3 DO4 4 3 A DO2 DO5 DO6 DO7 4 3 A Environments 0 55 C During operations 40 70 C During transport 20 80 Rh not condensed No shock infl...

Page 29: ...ation 084B8016 EKA 175 Data communication module LON RS 485 084B8579 EKA 178B Data communication module MODBUS 084B8571 EKA 176 Data communication module DANBUSS Gateway 084B8583 EKA 176A Data communi...

Page 30: ...Danfoss DCS vt 2019 12 BC230086440483en 000201 30...

Reviews: