Danfoss AK-CC 460 User Manual Download Page 16

Digital input signal - D2

The controller has a digital input 2 which can be used for one of the following functions:

Off: The input is not used.

1)  Status display of a contact function

2)  Door function. When the input is open it signals that the door is open. The 

refrigeration and the fans are stopped. When the time setting in “A04” is passed, an 

alarm will be given. The refrigeration will be resumed when time in o89 has passed.

3)  Door alarm. When the input is open it signals that the door is open. When the time 

setting in “A04” is passed an alarm will be given.

4)  Defrost. The function is started with a pulse signal. The controller will register when 

the DI input is activated. The controller will then start a defrost cycle. If the signal is 

to be received by several controllers (coordnated defrost) it is important that ALL 

connections are mounted the same way (DI to DI and GND to GND).

5)  Main switch. Regulation is carried out when the input is closed, and regulation is 

stopped when the input is put in pos. OFF.

6)  Night operation. When the input is closed there will be regulation for night operation.

7)  Thermostat band changeover. Switch to thermostat 2 (r21) when the input is closed

8)  Separate alarm function. Alarm will be given when the input is closed.

9)  Separate alarm function. Alarm will be given when the input is opened.

10)  Case cleaning. The function is started with a pulse signal.

 

See also description on page 5.

11)  Not used

12)  Night blinds. Pulse signal activates the night blinds.

13)  The input is used for coordinated defrost in conjunction with other controllers of the 

same type

14)  Not used

15)  Case Shutdown when input is closed.

o37

DI2 config.

Configuration of light function

1) Light is controlled via day/night status

2) Light is controlled via data communication and "Light remote o39"

3) Light is controlled by door contact, defined in either o02 or o37 where the setting is 

selected to either 2 or 3. When the door is opened the relay will cut in. When the door is 

closed again there will be a time delay of two minutes before the light is switched off.

4) As "2" but if there are any 15-minute network errors, the light will switch on and the 

night blind will open. 

o38

Light config

Activation of light relay

The light relay can be activated here, but only if defined in o38 with setting 2.

o39

Light remote

Rail heat during day operation

The ON period is set as a percentage of the time

o41

Railh.ON day%

Rail heat during night operation

The ON period is set as a percentage of the time

o42

Railh.ON ngt%

Rail heat cycle

The period of time for the aggregate ON time + OFF time is set in minutes

o43

Railh. cycle

Case cleaning

The status of the function can be followed here or the function can be started manually.

0 = Normal operation (no cleaning)

1 = Cleaning with fans operating. All other outputs are Off.

2 = Cleaning with stopped fans. All outputs are Off.

If the function is controlled by a signal at the DI1 or DI2 input, the relevant status can be 

seen here in the menu.

o46

Case clean

Selection of application

The controller can be defined in various ways. Here you select which of the 3 application 

modes is used:

1: Two compressors – sequential mode

2: One compressor – variable speed controlled

3: Two compressors – cyclic mode  

This menu can only be set when regulation is stopped, i.e. “r12” is set to 0.

o61

Appl. Mode

Access code 2 (Access to adjustments) 

There is access to adjustments of values, but not to configuration settings. If the settings 

in the controller are to be protected with an access code you can set a numerical value 

between 0 and 100. If not, you can cancel the function with setting 0. If the function is 

used, access code 1 (o05) 

must also 

be used. 

o64

Acc. code 2

Save as factory setting

With this setting you save the controller’s actual settings as a new basic setting (the earlier 

factory settings are overwritten).

o67

-

User Guide | Controller for SemiPlugin appliance, AK-CC 460

16 | BC230086440483en-000201

© Danfoss | DCS (vt) | 2019.12

Summary of Contents for AK-CC 460

Page 1: ...User Guide Controller for SemiPlugin appliance AK CC 460 www danfoss com...

Page 2: ...iance The temperature of the evaporator is registered with the S5 sensor which can be used as a defrosting sensor In addition to the output for the compressors the controller has 5 relay outputs for d...

Page 3: ...ll continue until the temperature has reached the cut out value Then it will cut out When the temperature again reaches the middle of the differential compressor 1 will be cutin to the circuit again I...

Page 4: ...digital input Separate thermostat and alarm limits can be set for each thermo stat band also for the product sensor Night setback of thermostat value In refrigeration appliances there may be big load...

Page 5: ...methods Natural Here the fans are kept operating during the defrost Electric The heating element is activated Defrost sequence 1 Defrost 2 Waiting position after defrost 3 Drip off 4 Delay of fan Star...

Page 6: ...oup is in a waiting position refrigeration is again permitted in all the individual controllers Defrost on demand Based on refrigeration time When the aggregate refrigeration time has passed a fixed t...

Page 7: ...Pulse control can be accomplished in one of the following ways during the thermostat s cutout period cold room during night operation and during the thermostat s cutout pe riod appliance with night l...

Page 8: ...Main switch is set to off see o98 When the night blind rolls down the fans can be stopped so that the air circulation does not interrupt the positioning of the blind The desired stop time must be set...

Page 9: ...the display can advantageously be changed to a type with screw terminals I e the type EKA 163A or EKA 164A If connection of two displays is required one must be connected to the plug max 15 m and the...

Page 10: ...ust S4 Correction of signal from S3 Compensation possibility due to long sensor cable r10 Adjust S3 Start stop of refrigeration With this setting refrigeration can be started stopped or a manual overr...

Page 11: ...ediately after a defrost There will be change over to the normal time delay A03 when the temperature has dropped below the set upper alarm limit The time delay is set in minutes A12 Pulldown del Upper...

Page 12: ...c01 Min On time Min OFF time in minutes c02 Min Off time Time delay for couplings of two compressors Settings indicate the time that has to elapse from the first relay cuts in and until the next rela...

Page 13: ...take place the interval time will be used as max time between defrosts When there is defrost with clock function or data communication the interval time must be set for a somewhat longer period of tim...

Page 14: ...ill not provide heat to the appliance If the defrost sensor registers a higher temperature than the one set here the fans will be stopped There will be re start at 2 K below the setting The function i...

Page 15: ...the night blinds 13 14 Not used 15 Case Shutdown when input is closed o02 DI 1 Config Definition takes place with the numerical value shown to the left 0 off DI state Measurement The DI input s presen...

Page 16: ...setting is selected to either 2 or 3 When the door is opened the relay will cut in When the door is closed again there will be a time delay of two minutes before the light is switched off 4 As 2 but i...

Page 17: ...is off 1 Light and night blind is independent of main switch o98 Light MS Off Configuration of the alarm relay The alarm relay will be activated upon an alarm signal from the following groups 1 High...

Page 18: ...2 u86 Ther band Status on input DI3 on 1 230 V u87 DI3 status Readout of the actual cutin value for the thermostat u90 Cutin temp Readout of the actual cut out value for the thermostat u91 Cutout temp...

Page 19: ...compressor is stopped it must remain stopped for at least x minutes S3 3 The evaporator drips off and waits for the time to run out S4 4 Refrigeration stopped by main switch Either with r12 or a DI in...

Page 20: ...igh S6 1 A14 Low temp S6 Temperature alarm Low S6 2 A15 DI1 alarm DI1 alarm 8 A16 DI2 alarm DI2 alarm 8 A45 Standby mode Standby position stopped refrigeration via r12 or DI input A59 Case clean Case...

Page 21: ...If there are several alarm codes they are found in a rolling stack Push the uppermost or lowermost button to scan the rolling stack Set temperature 1 Push the middle button until the temperature value...

Page 22: ...ure alarm after defrost A12 1 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 1 50 C 50 C 30 High alarm limit for thermostat 2 A20 1 1 5...

Page 23: ...5 1 1 0 2 0 Period time for fan pulsation on time off time F06 1 1 1 min 30 min 5 On time in of period time F07 1 1 0 100 100 Real time clock Six start times for defrost Setting of hours 0 OFF t01 t06...

Page 24: ...s o67 1 1 0 Off 1 On 0 Off Rail heat control 0 not used 1 pulse control with timer function o41 and o42 2 pulse control with dew point function o85 1 1 0 2 0 Dew point value where the rail heat is min...

Page 25: ...rmostat temperature u17 1 1 Run time of thermostat cooling time in minutes u18 1 1 Temperature measured with S6 sensor product temperature u36 1 1 Status on DI2 output on 1 closed u37 1 1 Readout of t...

Page 26: ...nserted in the controller The module can be a LON RS485 DANBUSS or a MODBUS Terminal 51 screen Terminal 52 A A Terminal 53 B B For LON RS485 and gateway type AKA 245 the gateway must be version 6 20 o...

Page 27: ...Digital input signal Compressors safety circuit OK at 230V The signal must have a voltage of 0 230 V AC Data communication If data communication is used it is important that the installation of the da...

Page 28: ...nal for variable speed control Relays CE 250 V AC IBExU approved DO3 DO4 4 3 A DO2 DO5 DO6 DO7 4 3 A Environments 0 55 C During operations 40 70 C During transport 20 80 Rh not condensed No shock infl...

Page 29: ...ation 084B8016 EKA 175 Data communication module LON RS 485 084B8579 EKA 178B Data communication module MODBUS 084B8571 EKA 176 Data communication module DANBUSS Gateway 084B8583 EKA 176A Data communi...

Page 30: ...Danfoss DCS vt 2019 12 BC230086440483en 000201 30...