Comp. on time when sensor fault
c86
1
0 min
240 min
15
Comp. off time when sensor fault
c87
1
0 min
240 min
30
Emergency speed for compressor if sensor error
c93
1
25 Hz
100 Hz
60
Max. slope rate (max allowed speed change per second)
c96
1
0.1 Hz/s
5 Hz/s
1
Max. proportional factor (Kp) for PI control
n95
1
5
50
20
Defrost
Defrost method
: 0=Off, 1= EL
d01
1
1
0/Off
1/EL
1/EL
Defrost stop temperature
d02
1
1
0 °C
50 °C
6
Interval between defrost starts
d03
1
1
0 hrs/Off 240 hrs
8
Max. defrost duration
d04
1
1
0 min.
360 min.
45
Displacement of time on cutin of defrost at start-up
d05
1
1
0 min.
240 min.
0
Drip off time
d06
1
1
0 min.
60 min.
0
Delay for fan start after defrost
d07
1
1
0 min.
60 min.
0
Fan start temperature
d08
1
1
-50 °C
0 °C
-5
Fan cutin during defrost
0: stopped
1 and 2: Running
d09
1
1
0
2
1
Defrost sensor:
0 =Stop on time, 1=S5, 2=S4, 3=S5 and S6
d10
1
1
0
3
0
Pump down delay
d16
1
1
0 min.
60 min.
0
Max. aggregate refrigeration time between two defrosts
d18
1
1
0 hrs
48 hrs
0/OFF
Rail heat during defrost
0: off
1: on
2: Pulsing
d27
1
1
0
2
2
Max. duration of -d- in display
d40
1
1
5 min.
240 min.
30 min.
Fan
Fan stop temperature (S5)
F04
1
1
-50 °C
50 °C
50
Pulse operation on fans: 0=No pulse operation, 1=At thermostat cuts out
only, 2= Only at thermostat cut outs during night operation
F05
1
1
0
2
0
Period time for fan pulsation (on-time + off-time)
F06
1
1
1 min.
30 min.
5
On-time in % of period time
F07
1
1
0 %
100 %
100
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01 -
t06
1
1
0 hrs
23 hrs
0
Six start times for defrost.
Setting of minutes.
0=OFF
t11 -
t16
1
1
0 min.
59 min.
0
Clock - Setting of hours
t07
1
1
0 hrs
23 hrs
0
Clock - Setting of minute
t08
1
1
0 min.
59 min.
0
Clock - Setting of date
t45
1
1
1 day
31 day
1
Clock - Setting of month
t46
1
1
1 mon.
12 mon.
1
Clock - Setting of year
t47
1
1
0 year
99 year
0
Miscellaneous
Delay of output signals after power failure
o01
1
1
0 sec
600 sec
5
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door
alarm when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night
operation 7=
Thermostat band changeover
(activate r21). 8=alarm function
when closed. 9=alarm function when open. 10=case cleaning (pulse signal).
12=night cover. 15=application shutdown
o02
1
1
0
15
0
Network address (0= off)
o03
1
1
0
240
0
On/Off switch (Service Pin message)
IMPORTANT! o61
must
be set prior to o04
(used at LON 485 only)
o04
1
1
0/Off
1/On
0/Off
Access code 1 (all settings)
o05
1
1
0
100
0
Software Version
o08
1
1
Setting of mains supply frequency
o12
1
50 Hz
60 Hz
50
Max hold time after coordinated defrost
o16
1
1
0 min.
360 min.
20
Continued
code
Wiring diagram
Min.
Max.
Fac.
Actual