Rail heat control
The rail heat can be controlled in several ways:
0: The function is not used
1: Pulse control is used with a timer function following the day/night operation (o41 and
o42)
2: Pulse control is used with a dew point function. This function requires that a signal is
received about the dew point value. The value is measured by a system manager and sent
to the controller via the data communication.
o85
Railh. mode
Dew point value where the rail heat is minimum
This function is discussed earlier in the manual.
o86
DewP Min lim
Dew point value where the rail heat is maximum
This function is discussed earlier in the manual.
o87
DewP Max lim
Lowest permitted rail heat effect
Here the % part of the effect to be achieved when the dew point value is minimum.
o88
Rail Min ON%
Start of refrigeration when door is open
If the door has been left open, refrigeration must be started after a set time. That time can
be set here. (DI config = 2)
o89
DoorInjStart
Alternative display
A reading can be displayed on the controller or on the display by pressing the lower
button. This reading is set from the factory so that the defrosting stop temperature is
displayed.
A different setting will give the following reading:
1: (Defrost stop temperature = factory setting)
2: S6 temperature
o92
Displ menu 2
Display of temperature during normal operation
1: Air temperature. Weighted S3 + S4
2: Product temperature S6
o97
Disp. Ctrl.
Light and night blind definition
0: Light is switched off and night blind is open when the main switch is off
1: Light and night blind is independent of main switch.
o98
Light MS = Off
Configuration of the alarm relay
The alarm relay will be activated upon an alarm signal from the following groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input is activated for alarm
16 - Defrost alarms
32 - Miscellaneous
The groups that are to activate the alarm relay must be set by using a numerical value
which is the sum of the groups that must be activated.
(E.g. a value of 5 will activate all high temperature alarms and all sensor errors. 0 will cancel
the relay function)
P41
Al.Rel. Conf.
Fan pause while the night blinds are rolling down.
Here it is possible to set a pause time for the fans so that the night blinds can roll down
into the correct position unobstructed.
P65
BlindFanStop
Service
Service
Temperature measured with S5 sensor
u09
S5 temp.
Status on DI1 input. on/1=closed
u10
DI1 status
Read the duration of the ongoing defrost or the duration of the last completed defrost.
u11
Defrost time
Temperature measured with S3 sensor
u12
S3 air temp
Status at the day-/night operation (night operation: on/off)
u13
Night Cond.
Temperature measured with S4 sensor
u16
S4 air temp
Thermostat temperature
u17
Ther. air
Read the ongoing cutin time for the thermostat or the duration of the last completed
cutin
u18
Ther runtime
Read the temperature at the S6 sensor
u36
S6 temp
Status on DI2 input. on/1=closed
u37
DI2 status
Readout of the actual compressor capacity in %
u52
CompCap %
Air temperature. Weighted S3 +S4
u56
Display air
Measured temperature for alarm thermostat
u57
Alarm air