DANFOSS HEATING
11
UK
Main menu > settings > bypass °C
Here you can set the activation temperature of the auto-
matic bypass function. When the outdoor air reaches the
defined temperature, the bypass function will automa-
tically begin. When the temperature drops below the
defined outdoor air temperature, the automatic bypass
function will stop again. A highly insulated house can
benefit from a lower than normal setting (default 16 °C)
- but be aware that setting the bypass activation too low,
can cause draught risk.
Main menu > settings > bypass dura.
Here you can adjust the run time of the ”manual bypass”
function (default run time is 3 hours from activation).
Main menu > settings > boost duration
Here you can adjust the run time of the ”boost” function
(default run time is 3 hours from activation).
Main menu > settings > time & date
Here you can adjust the time and date of your system.
Main menu > settings > night cooling
Here you can define whether or not you will allow night
cooling (disabled as default). Night cooling is a form of
automatic bypass, that can be used in the summertime.
The system automatically detects if it was a warm day
and only then will it be activated. The night cooling
function will allow the supply air to be +10 °C or higher.
The function runs from 24:00 until 06:00 am, and auto-
matically stops if the outdoor air fall below +10 °C or if
exhaust air temperature drops below +18 °C.
Main menu > settings > restore default
Restores all user settings to factory default values. The stored
basic step will not be affected by using this function.