maximum floor temperature up to 45 °C. Furthermore, it
will be possible to use only a room sensor. However, this
option is not recommended due to an increased risk of
overheating the floor.
IMPORTANT:
When the thermostat is used to control a
floor heating element in connection with a wooden floor
or similar material, always use a floor sensor and never set
the maximum floor temperature to more than 35 °C.
Note:
Please contact the floor supplier before changing the
maximum floor temperature and be aware of the following:
• The floor temperature is measured there, where the
sensor is placed.
• The temperature of the bottom of a wooden floor
can be up to 10 ˚C higher than the top.
• Floor manufactures often specify the max. tempera-
ture on the top surface of the floor.