Installation Instructions 

 

 

Issue Date 

November 23, 2005 

 

©  2005 Johnson Controls, Inc. 

1

 

TEC220x-2 Series Non-Programmable L

ON

W

ORKS

®

 

Network Configurable

 Staged 

Thermostats 

 

Application Requirements 

The TEC220x-2 Series Non-Programmable 
L

ON

W

ORKS

® Network Configurable Staged 

Thermostats are specifically designed for single-stage 
and multi-stage control of heating/cooling equipment, 
such as rooftop and heat pump units. 

 

Code No. LIT-1201911 

www.johnsoncontrols.com 

 

 

Software Release 1.0 

Accurate temperature control is achieved with a time 
proportional control algorithm, which virtually 
eliminates the temperature offset associated with 
traditional, differential-based thermostats. For more 
advanced applications, an economizer control logic 
has been integrated onto the thermostat for use with 
proportional damper economizer actuators. 

All programmable models contain a Single-Pole 
Single-Throw (SPST) auxiliary switch, which can be 
used to control lighting or disable the economizer 
function. 

Mechanical Installation 

Location 

Install away from any heat source. 

Do not install the thermostat: 

 

on an outside wall 

 

near an air discharge grill 

 

in a location affected by direct sun radiation 

 

in an area that restrains vertical air circulation to 
the thermostat 

c

o

v

e

rr

e

m

o

v

a

l

 

Figure 1: Bottom of Thermostat 

Installation 

To install the thermostat: 

Note: 

Wall surface must be flat and clean. 

1. 

Remove security screw on the bottom of 
thermostat cover. 

2. 

Open up by pulling on the bottom side of 
thermostat (Figure 1). 

3. 

Swing the thermostat circuit board to the left by 
pressing the pull tabs (Figure 2). 

4. 

Pull cables 6” out of the wall. 

5. 

Insert cable in the central hole of the base. 

6. 

Align the base and mark the location of the two 
mounting holes on the wall. Install proper side of 
base up. 

m

o

u

n

ti

n

g

b

a

s

e

 

Figure 2: Pull Tabs 

7.  Install anchors in the wall. 

8.  Insert screws in mounting holes on each side of 

the base (Figure 2). 

9.  Gently swing the circuit board back on the base 

and push until the tabs lock. 

10.  Pull out the screw terminal blocks using the pull 

tabs on each connector (Figure 3). 

Summary of Contents for TEC2201-2

Page 1: ...o control lighting or disable the economizer function Mechanical Installation Location Install away from any heat source Do not install the thermostat on an outside wall near an air discharge grill in a location affected by direct sun radiation in an area that restrains vertical air circulation to the thermostat coverremoval Figure 1 Bottom of Thermostat Installation To install the thermostat Note...

Page 2: ...auxiliary output is used to toggle occupancy of the electronic control card inside the equipment configure the relay parameter Aux cont to the Normally Open N O setting A second relay can be added for additional functionality of the occupancy output Economizer output uses a half bridge rectifier Reference of the control signal is the common of the power supply of the thermostat terminal C Electrom...

Page 3: ...nfigured as a digital output Max Current 60 mA 12 VDC when configured as digital 200 ohm load 50 mA 10 VDC when configured as analog Protection Auto reset fuse 100 mA 68 F 20 C 0 mA 140 F 60 C Table 3 Thermostat Models Application 1 Heat 1 Cool 2 Heat 2 Cool 2 Heat 2 Cool and Economizer Heat Pump Model Non Programming without Scheduling TEC2201 2 TEC2203 2 TEC2204 2 TEC2202 2 TEC220x 2 Series Non ...

Page 4: ... Figure 4 TEC2201 2 Single Stage Thermostat TEC2203 2 Multi Stage Thermostat The TEC2203 2 features one fan two heating stages and two cooling stages Figure 5 shows a wiring example Thermostat Terminals TEC2203 2 W1 OS DI1 Y1 Y2 G RS DI 2 Scom RC C RH W2 24 Vac System wiring Jumper J1 Thermostat internal wiring T1 24 Vac Cool Stage 1 Cool Stage 2 Y2 Jumper J1 RC Fan Y1 G C RH Remote Outdoor Sensor...

Page 5: ... Mixed Air Sensor MS Scom OS Figure 6 TEC2204 2 Economizer Thermostat TEC2202 2 Heat Pump Thermostat The TEC2202 2 features one fan three heating stages and two cooling stages Figure 7 shows a wiring example Thermostat Terminals TEC2202 2 Y2 DI1 DI2 Y1 RC G O B Scom RS OS RH C W1 24 Vac System wiring Jumper J1 Thermostat internal wiring Compressor Stage 1 T1 24 Vac Compressor Stage 2 Y2 Jumper J1 ...

Page 6: ...to 50ºC 40 to 122ºF Proportional Band for Room temperature Control Both outputs 1 1ºC 2 0ºF Digital Inputs Relay dry contact only across C terminal to DI1 or DI2 Contact Output Rating Each relay output Y1 Y2 G W1 W2 and AU 30 VAC 1 A maximum 30 VAC 3 A in rush Economizer Analog Output Rating 0 to 10 VDC into 2 K ohm resistance minimum Economizer Analog Output Accuracy 3 typical Wire Gauge 18 gauge...

Reviews: