DEVIreg™ Smart
9
Installation Guide
Note for thermostat:
A floor sensor is recommend-
ed in all floor heating applications and
mandatory
to thin mats and under wooden floors to reduce the
risk of over-heating the floor.
• Place the floor sensor in a protecting plastic conduit
in the floor construction in an appropriate place,
where the floor is not exposed to sunlight or draft
from door openings
.
1
2
≥
• Equally distant and
>2 cm from the
heating cables on
both sides.
• The conduit should
be flush with the
floor surface, coun-
tersink the conduit
if necessary and
possible.
• Route the conduit to the connection box.
• The bending radius of the conduit must be min 50 mm.