Mains Supply 3x200-240 V AC - Normal overload 110% for 1 minute
IP20/Chassis
(B3+4 and C3+4 may be converted to IP21 using a conversion kit. (See also
items
Mechanical mounting
and
IP21/Type 1 Enclosure kit
in the Design Guide.))
C3
C3
C4
C4
IP21/NEMA 1
C1
C1
C2
C2
IP55/Type 12
C1
C1
C2
C2
IP66/NEMA 4X
C1
C1
C2
C2
Frequency converter
Typical Shaft Output [kW]
P22K
22
P30K
30
P37K
37
P45K
45
Typical Shaft Output [HP] at 208 V
30
40
50
60
Output current
Continuous (3 x 200-240 V) [A]
88.0
115
143
170
Intermittent (3 x 200-240 V) [A]
96.8
127
157
187
Continuous kVA (208 V AC) [kVA]
31.7
41.4
51.5
61.2
Max. input current
Continuous (3 x 200-240 V) [A]
80.0
104.0
130.0
154.0
Intermittent (3 x 200-240 V) [A]
88.0
114.0
143.0
169.0
Additional Specifications
Estimated power loss at rated max. load [W]
4)
845
1140
1353
1636
IP20 max. cable cross-section (mains, brake, motor and load sharing)
150 (300 MCM)
IP21, IP55, IP66 max. cable cross-section (mains, motor) [mm
2
/AWG]
150 (300 MCM)
IP21, IP55, IP66 max. cable cross-section (brake, load sharing) [mm
2
/AWG]
95 (3/0)
Weight enclosure IP20 [kg]
35
35
50
50
Weight enclosure IP21 [kg]
45
45
65
65
Weight enclosure IP55 [kg]
45
45
65
65
Weight enclosure IP66 [kg]
45
45
65
65
Efficiency
3)
0.97
0.97
0.97
0.97
Table 10.3 Mains Supply 3x200-240 V AC
Specifications
VLT
®
HVAC Drive Operating Instructions
68
MG11AI02 - VLT
®
is a registered Danfoss trademark
10
10