Mains Supply 3x200-240 V AC - Normal overload 110% for 1 minute
IP20/Chassis
(B3+4 and C3+4 may be converted to IP21 using a conversion kit. (See
also items
Mechanical mounting
and
IP21/Type 1 Enclosure kit
in the
Design Guide.))
B3
B3
B3
B4
B4
IP21/NEMA 1
B1
B1
B1
B2
C1
IP55/Type 12
B1
B1
B1
B2
C1
IP66/NEMA 4X
B1
B1
B1
B2
C1
Frequency converter
Typical Shaft Output [kW]
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
P18K
18.5
Typical Shaft Output [HP] at 208 V
7.5
10
15
20
25
Output current
Continuous (3 x 200-240 V) [A]
24.2
30.8
46.2
59.4
74.8
Intermittent (3 x 200-240 V) [A]
26.6
33.9
50.8
65.3
82.3
Continuous kVA (208 V AC) [kVA]
8.7
11.1
16.6
21.4
26.9
Max. input current
Continuous (3 x 200-240 V) [A]
22.0
28.0
42.0
54.0
68.0
Intermittent (3 x 200-240 V) [A]
24.2
30.8
46.2
59.4
74.8
Additional Specifications
Estimated power loss at rated max. load [W]
4)
269
310
447
602
737
IP20 max. cable cross-section (mains, brake, motor and load sharing)
10, 10 (8,8-)
35,-,- (2,-,-)
35 (2)
50 (1)
IP21, IP55, IP66 max. cable cross-section (mains, motor) [mm
2
/AWG]
10, 10 (8,8-)
35, 25, 25
(2, 4, 4)
50 (1)
IP21, IP55, IP66 max. cable cross-section (brake, load sharing) [mm
2
/AWG]
16, 10, 16 (6, 8, 6)
35,-,- (2,-,-)
50 (1)
Weight enclosure IP20 [kg]
12
12
12
23.5
23.5
Weight enclosure IP21 [kg]
23
23
23
27
45
Weight enclosure IP55 [kg]
23
23
23
27
45
Weight enclosure IP66 [kg]
23
23
23
27
45
Efficiency
3)
0.96
0.96
0.96
0.96
0.96
Table 10.2 Mains Supply 3x200-240 V AC
Specifications
VLT
®
HVAC Drive Operating Instructions
MG11AI02 - VLT
®
is a registered Danfoss trademark
67
10
10
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]