User Guide | Stepper Valve Extension Module, Type EKE 1P

8 | BC320219567793en-000201

© Danfoss | DCS (vt) | 2020.03

Menu

Start/Stop

Main switch

Main switch 
Start and stop regulating here. 
The configuration settings will require that regulating is stopped. 
If you try to enter a configuration setting when regulating has started, the controller will 
ask if regulating should be stopped. 
When all settings have been made and the main switch is set to “ON”, the controller will 
enable the display of the various measurements. Regulation will start. (One external 
main switch must be “ON” before regulation starts.)
Note: In application 1, the main switch automatically follows the main switch of the 
AK-PC.

On / Off
Fac: Off

Device config

Mode

Selection of the application mode and how the device is used in application 1.
Note: changing this setting also changes the EKE 1P address, causing communication 
with the graphical display to stop. Communication will resume after a power cycle.
AI HP/Rec.: Appl. 1 - selection by AI4
HP exp: Appl. 1 - High Pressure expansion module
Rec. exp.: Appl. 1 - Receiver Expansion module 
AI valve: Appl. 2 - Valve Driver

AI HP/Rec. / HP exp / Rec. exp. / AI valve
Fac: AI HP/Rec.

AI valve input scale

Configuration of the Analogue Input in application mode 2. If user defined is selected, 
the scaling is created via the two parameters, ”AI 0% OD” and ”AI 100%” OD which 
become visible.

0 – 5 V / 1 – 5 V / 0 – 10 V / 2 – 10 V / 
5 - 0 V / 5 – 1 V / 10 – 0 V / 10 – 2 V / 
User Defined 
Fac: 0 - 10V

System

Display

Login time-out

If buttons have not been pressed within a specified period of 
time, the screen will return to the overview display. Afterwards, 
the user will have to log on again. 
If the time is changed, the new time will apply the next time 
the user logs in. 
If you log out here without waiting for the time-out period 
to elapse, go to the overview display and hold down the “X” 
button for 3 seconds.

Min: 1 min. 
Max: 60 min. 
Fac: 2 min.

Display unit

Temperature and Pressure unit

Metric (°C & bar) / Imperial (°F & psig) 
Fac: Metric (°C & bar)

Backlight time-out

If no buttons have been pushed for a specific period of time, 
the light in the display will be minimised. 
The light level will be restored upon renewed activity.

Min: 1 min. 
Max: 60 min. 
Fac: 1 min.

Password

The settings in the controller can be protected with three levels of access codes. The three access codes are numbers between 
001 and 999.
Password daily

Level 1: End user settings, such as changing the main switch

Fac: 100

Password service

Level 2: Adjusting installer level

Fac: 200

Password commission Level 3: Configuration of system settings (configuration menu)

Fac: 300

Reset to Factory

Apply defaults

This will reset the controller back to default (factory) settings

On / Off 
Fac: Off

I/O

Input status

AI 1 … AI 4

Here you can see pressure and temperature values received by 
the analogue inputs. The values include calibration

DI 1 … DI2

Here you can see the status of the digital input function/alarm

Output

Relay state

Here you can see if the function is on or off

Relay control

Manual control of relay in application 2. In application 1 the 
manual control is done from the AK-PC controller. 
Under normal regulation, the function of the relay will be in 
“Auto”. In the event of an override, the function will be switched 
to either “On” or “Off”. Remember to switch to “Auto” when the 
override is to be completed. Otherwise it will remain in override 
until the device is power cycled or reset to factory settings

Auto / On / Off
Fac: Auto

Configure

DI1 Active at ... DI2 
Active at

Define whether the function/alarm will be active with terminals 
short-circuited (ON) or open-circuited (OFF)

On / Off 
Fac: On

Alarm config

Battery alarm

If a battery back-up is connected to EKE 1P terminals, the EKE 1P will close the stepper 
motor if the controller loses its supply voltage. The battery voltage must not be 
connected from main power supply connected to EKE 1P. A battery voltage lower than 
16.5 V will trigger the battery alarm.
The battery back-up may be the Danfoss module (EKE 2U) or a general type (Bat.).

No / Bat. / EKE2U
Fac: No

Summary of Contents for 080G0325

Page 1: ...User Guide Stepper Valve Extension Module Type EKE 1P ADAP KOOL Refrigeration Control System www danfoss com...

Page 2: ...03 Introduction 3 Application 1 4 Application 2 4 User Interface 5 End user overview with graphical display 7 Service and commissioning with graphical display 7 Menu 8 Alarm list 11 ERR31 12 Connecti...

Page 3: ...guage only Two sets of LEDs on the EKE 1P indicate the EKE 1P application confirmation valve status and alarm condition see details further below Data communication The controller has a built in CANBU...

Page 4: ...lve will close in this case Application 2 Valve configuration The valve type can be selected from an extensive list of Danfoss standard valve types When a standard type is selected only a few paramete...

Page 5: ...G Configured as HP module will blink for 30 sec after power up 3 Receiver module 0s 2s 1s R R R R G G G G Configured as receiver module will blink for 30 sec after power up 0s 2s 1s R R R R G G G G R...

Page 6: ...fully closed V2 Valve closing 0s 2s 1s R R R R R R R R Flashing red 2 Hz valve closing V3 Valve idle 0s 2s 1s Running on target Both Red and Green off V4 Valve opening 0s 2s 1s G G G G G G G G Flashi...

Page 7: ...d outputs and will depend on how the set up is made application mode Click on the to view e g the following images Service and commissioning with graphical display To access the parameter menu press a...

Page 8: ...emperature and Pressure unit Metric C bar Imperial F psig Fac Metric C bar Backlight time out If no buttons have been pushed for a specific period of time the light in the display will be minimised Th...

Page 9: ...connected to the EKE 50 200 Fac 100 Valve acceleration current These features are used with valves running at higher speed i e 300 pps and above Typically at start up high torque is required to operat...

Page 10: ...tting of the CANBUS baudrate 20k 50k 125k 250k 500k 1M Fac 50k Service Actual OD Read out of the valve opening degree in percentage Actual step Read out of the valve opening degree in number of steps...

Page 11: ...oning set Half step operation is possible Correct either I029 or I064 Valve speed too fast Number of micro steps sec is too high higher than 12800 micro step sec Reduce valve speed or use less micro s...

Page 12: ...rner The software version must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until...

Page 13: ...le Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 B1 B2 Bipolar and unipolar stepper motor output Danfoss CCMT 3L CCMT 8L CCMT 0 CCMT 42 CCM 10 CCM 40 ETS 6 ETS 400 CTR 20 Other valves speed 10...

Page 14: ...inst voltage surges Category II Software class and structure Class A Approvals CE compliance This product is designed to comply with the following EU standards Low voltage guideline 2014 35 EU Electro...

Page 15: ...mounting only IP20 Type Function Operation Supply voltage Code no EKE 1P Stepper Valve Extension Module Via AK PC or MMIGRS2 24 V 080G0325 EKE 2U Back up power module 24 V 080G5555 AK PC 572 Capacity...

Page 16: ...Danfoss DCS vt 2020 03 BC320219567793en 000201 16 ADAP KOOL...