User Guide | Stepper Valve Extension Module, Type EKE 1P

© Danfoss | DCS (vt) | 2020.03

BC320219567793en-000201 | 13

Connections

Technical specifications

CO

M

5V

+

DI

2

DI

1

CO

M

AI

4

AI

3

AI

2

AI1

CO

M

D+

RGND

CAN RJ

–/

~

+/

~

GN

D

Bat+

A1

A2

B1

B2

NO

1

C1

NC

1

CO

M

5V+

DI2

DI1

CO

M

AI

4

AI

3

AI

2

AI

1

CO

M

D+

RGND

CAN RJ

ANALOG / DIGITAL INPUT

CAN - RJ

RS-485

–/~

+/~

GND

Bat+

A1

A2

B1

B2

NO1

C1

NC1

PWR 24V

Vbat

STEPPER VALVE

DIGITAL OUTPUT

Superheat controller
EKE 1P 

ANALOGUE / DIGITAL INPUT

DIGITAL OUTPUT

STEPPER VALVE

Stepper Valve Module

Danf

oss

80G398

I/O

Type

No. Specification

Analogue inputs

Max. 15 V input voltage

Do not connect voltage sources to unpowered units without limiting the current to analogue inputs (overall 80 mA). 

Open circuit HW diagnostics available for voltage input on: 

AI4

Voltage

2

AI3

*

0 – 5 V ratiometric

AI4

0 – 5 V, 0 – 10 V

PT1000

2

AI1

*, 

AI2

*

Auxiliary

Supplies

1

5 V +

Sensor supply: 5 V DC / 15 mA, overload protection approximately 150 mA

Digital inputs

Voltage free

contacts

2

DI1*, DI2

Steady current minimum 1mA

Cleaning current 100 mA at 15 V DC

On: RIL < = 300 Ω

Off: RIH > = 3.5 k Ω

Digital output

Relay

1

C1-NO1*

Normally Open: 3 A General purpose, 250 V AC, 100 k cycle

Normally Open: 3 A Inductive (AC-15), 250 V AC, 100 k cycle

Normally Closed: 2 A General purpose, 250 V AC, 100 k cycle

Stepper motor

Bipolar / 

unipolar

1

Stepper valves: A1, A2, B1, B2

Bipolar and unipolar stepper motor output:

 

- Danfoss CCMT 3L- CCMT 8L / CCMT 0 – CCMT 42 / CCM 10 - CCM 40/ETS 6 - ETS 400/ CTR 20

Other valves:

 

- speed 10 – 400 pps

 

- drive mode 1/8 microstep

 

- max. peak phase current: 1.2 A (848 mA RMS)

 

- max. drive voltage 40 V

 

- max. output power 12 W

Battery backup

1

VBATT: 

18 – 24 V DC (24 V DC recommended)

 

- Leakage: <15 μA @30 V DC

 

- max. battery current: 850 mA at 18 V

 

- battery alarm will be activated below 16 V DC

Required power to do one closing of stepper valve:

ETS 6

 

: 110 J / 30 V mAh

ETS 12.5 - ETS 400

 

: 60 J / 17 V mAh

KVS 15 / KVS 42

 

: 60 J / 17 V mAh

ETS 12C - ETS 100C

  : 55 J / 15 V mAh

KVS 2C / KVS 5C

 

: 55 J / 15 V mAh

CCMT 2 - CCMT 8

 

: 60 J / 17 V mAh

CCMT 16 - CCMT 42

  : 175 J / 49 V mAh

CCMT 3L - CCMT 8L

  : 60 J / 17 V mAh

CTR 20

 

: 60 J / 17 V mAh

Communication

RS-485 RTU

1

RS-485*

Galvanic isolation

No built-in termination

CAN

1

CAN – RJ

Application 1: Connect directly to AK-PC

Application 2: Connect directly to graphical display, MMIGRS2. Activate the termination on the graphical display.

* Only used in application 1

Valve connection

Application 1 driver configuration

Recommended wire size and cable distance between 
EKE controller and stepper motor valve 

CCMT/ETS/CCM

ETS 6

EKE 1P

White

Orange

A1

Black

Yellow

A2

Red

Red

B1

Green

Black

B2

AI4 open circuit or connected to 0 V (COM): high-pressure valve driver

AI4 connected to 5 V+: receiver valve driver

Cable length

1 – 15 m

Wire diameter

0.52 / 0.33 mm2 (20 / 22 AWG)

Summary of Contents for 080G0325

Page 1: ...User Guide Stepper Valve Extension Module Type EKE 1P ADAP KOOL Refrigeration Control System www danfoss com...

Page 2: ...03 Introduction 3 Application 1 4 Application 2 4 User Interface 5 End user overview with graphical display 7 Service and commissioning with graphical display 7 Menu 8 Alarm list 11 ERR31 12 Connecti...

Page 3: ...guage only Two sets of LEDs on the EKE 1P indicate the EKE 1P application confirmation valve status and alarm condition see details further below Data communication The controller has a built in CANBU...

Page 4: ...lve will close in this case Application 2 Valve configuration The valve type can be selected from an extensive list of Danfoss standard valve types When a standard type is selected only a few paramete...

Page 5: ...G Configured as HP module will blink for 30 sec after power up 3 Receiver module 0s 2s 1s R R R R G G G G Configured as receiver module will blink for 30 sec after power up 0s 2s 1s R R R R G G G G R...

Page 6: ...fully closed V2 Valve closing 0s 2s 1s R R R R R R R R Flashing red 2 Hz valve closing V3 Valve idle 0s 2s 1s Running on target Both Red and Green off V4 Valve opening 0s 2s 1s G G G G G G G G Flashi...

Page 7: ...d outputs and will depend on how the set up is made application mode Click on the to view e g the following images Service and commissioning with graphical display To access the parameter menu press a...

Page 8: ...emperature and Pressure unit Metric C bar Imperial F psig Fac Metric C bar Backlight time out If no buttons have been pushed for a specific period of time the light in the display will be minimised Th...

Page 9: ...connected to the EKE 50 200 Fac 100 Valve acceleration current These features are used with valves running at higher speed i e 300 pps and above Typically at start up high torque is required to operat...

Page 10: ...tting of the CANBUS baudrate 20k 50k 125k 250k 500k 1M Fac 50k Service Actual OD Read out of the valve opening degree in percentage Actual step Read out of the valve opening degree in number of steps...

Page 11: ...oning set Half step operation is possible Correct either I029 or I064 Valve speed too fast Number of micro steps sec is too high higher than 12800 micro step sec Reduce valve speed or use less micro s...

Page 12: ...rner The software version must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until...

Page 13: ...le Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 B1 B2 Bipolar and unipolar stepper motor output Danfoss CCMT 3L CCMT 8L CCMT 0 CCMT 42 CCM 10 CCM 40 ETS 6 ETS 400 CTR 20 Other valves speed 10...

Page 14: ...inst voltage surges Category II Software class and structure Class A Approvals CE compliance This product is designed to comply with the following EU standards Low voltage guideline 2014 35 EU Electro...

Page 15: ...mounting only IP20 Type Function Operation Supply voltage Code no EKE 1P Stepper Valve Extension Module Via AK PC or MMIGRS2 24 V 080G0325 EKE 2U Back up power module 24 V 080G5555 AK PC 572 Capacity...

Page 16: ...Danfoss DCS vt 2020 03 BC320219567793en 000201 16 ADAP KOOL...

Reviews: