User Guide | Stepper Valve Extension Module, Type EKE 1P

12 | BC320219567793en-000201

© Danfoss | DCS (vt) | 2020.03

ERR31

Alarm on the external display - MMIGRS2

If the communication to the display is not carried out correctly, it 

will send an “ERR31” error notification.

This may be caused by the displayed wires H to R not being 

installed, or that there have been interruptions in data 

communication during the time when the display retrieves the 

basic information from the controller.

Once the terminations have been inspected, you should then 

check the software version of the external display. This is done by 

holding down the Enter key and the X key for 5 seconds, until the 

Bios menu appears.

Next, press the X key and read off the software version in the 

bottom right corner. The software version must be 1.13 or newer.

Once the display’s software version has been checked, check the 

display’s settings as follows:

1.  Hold the Enter key and the X key down for 5 seconds, until the 

Bios menu appears.

2.  Select the “MCX selection” menu

 

- Select the “Clear UI” line and press Enter

 

- Select the “Autodetect” line and press Enter

3.  Press the X key to return to the Bios menu

4.  Select the “COM selection” menu

 

- Select the “CAN” line and press Enter

5.  Press the X key to return to the Bios menu

6.  Select the “Start up mode” menu

 

- Select the “Remote application” line and press Enter

7.  Press the X key to return to the Bios menu

8.  Select the “CAN” menu

 

- Select the “Baudrate” line and check that it is 50K

 

- Select the “Node ID” line and check that it is 126

9.  Press the X key to return to the Bios menu

10.  Select the “Application” menu and press Enter.

The display will once again retrieve data from the controller.

This process will take about 5 minutes.

Danfos

s

80G399

Summary of Contents for 080G0325

Page 1: ...User Guide Stepper Valve Extension Module Type EKE 1P ADAP KOOL Refrigeration Control System www danfoss com...

Page 2: ...03 Introduction 3 Application 1 4 Application 2 4 User Interface 5 End user overview with graphical display 7 Service and commissioning with graphical display 7 Menu 8 Alarm list 11 ERR31 12 Connecti...

Page 3: ...guage only Two sets of LEDs on the EKE 1P indicate the EKE 1P application confirmation valve status and alarm condition see details further below Data communication The controller has a built in CANBU...

Page 4: ...lve will close in this case Application 2 Valve configuration The valve type can be selected from an extensive list of Danfoss standard valve types When a standard type is selected only a few paramete...

Page 5: ...G Configured as HP module will blink for 30 sec after power up 3 Receiver module 0s 2s 1s R R R R G G G G Configured as receiver module will blink for 30 sec after power up 0s 2s 1s R R R R G G G G R...

Page 6: ...fully closed V2 Valve closing 0s 2s 1s R R R R R R R R Flashing red 2 Hz valve closing V3 Valve idle 0s 2s 1s Running on target Both Red and Green off V4 Valve opening 0s 2s 1s G G G G G G G G Flashi...

Page 7: ...d outputs and will depend on how the set up is made application mode Click on the to view e g the following images Service and commissioning with graphical display To access the parameter menu press a...

Page 8: ...emperature and Pressure unit Metric C bar Imperial F psig Fac Metric C bar Backlight time out If no buttons have been pushed for a specific period of time the light in the display will be minimised Th...

Page 9: ...connected to the EKE 50 200 Fac 100 Valve acceleration current These features are used with valves running at higher speed i e 300 pps and above Typically at start up high torque is required to operat...

Page 10: ...tting of the CANBUS baudrate 20k 50k 125k 250k 500k 1M Fac 50k Service Actual OD Read out of the valve opening degree in percentage Actual step Read out of the valve opening degree in number of steps...

Page 11: ...oning set Half step operation is possible Correct either I029 or I064 Valve speed too fast Number of micro steps sec is too high higher than 12800 micro step sec Reduce valve speed or use less micro s...

Page 12: ...rner The software version must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until...

Page 13: ...le Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 B1 B2 Bipolar and unipolar stepper motor output Danfoss CCMT 3L CCMT 8L CCMT 0 CCMT 42 CCM 10 CCM 40 ETS 6 ETS 400 CTR 20 Other valves speed 10...

Page 14: ...inst voltage surges Category II Software class and structure Class A Approvals CE compliance This product is designed to comply with the following EU standards Low voltage guideline 2014 35 EU Electro...

Page 15: ...mounting only IP20 Type Function Operation Supply voltage Code no EKE 1P Stepper Valve Extension Module Via AK PC or MMIGRS2 24 V 080G0325 EKE 2U Back up power module 24 V 080G5555 AK PC 572 Capacity...

Page 16: ...Danfoss DCS vt 2020 03 BC320219567793en 000201 16 ADAP KOOL...

Reviews: