background image

User Guide | Stepper Valve Extension Module, Type EKE 1P

14 | BC320219567793en-000201

© Danfoss | DCS (vt) | 2020.03

Technical Data

General specification   

Electrical specification

Feature 

Description

Power supply

Galvanic isolation by switch mode power supply

Input voltage rating (AC): 24 V AC ± 20 % (19.2 – 28.8 V AC)

Input frequency (AC): 50 / 60 Hz

Input voltage rating (DC): 24 V DC (20 – 40 V DC)

Provides 5 W at 5 V and 15 V outputs isolated from the 24 V input

Insulation between power supply and the extra-low voltage

Power Consumption

Total Power consumption with following valve in operation and MMIGRS2 connected to the controller:

CCMT 16 - CCMT 42  : 15 V A /10 W

ETS 6 

: 11 V A / 7.5 W

ETS 12C - ETS 100C  : 20 V A / 14 W

KVS C 

: 20 V A / 14 W

ETS 12.5 - ETS 400  : 7 V A / 5 W

CCMT 2 - CCMT 8 

: 7 V A / 5 W

CCMT 3L - CCMT 8L  : 9 V A/ 6 W

CTR 20 

: 7 V A / 5 W

Plastic Housing

DIN rail mounting complying with EN 50022
Self-extinguishing V0 according to IEC 60695-11-10 and glowing / hot wire test at 960 °C according to IEC 60695-2-12
Material used for Enclosure are UL94-V0 and  RoHS compliant
Ball test: 125 °C according to IEC 60730-1

Leakage current: ≥ 250 V according to IEC 60112

Connectors 

Plug able Screw connector Pitch 3.5 mm, relay and power connector Pitch 5 mm, CAN MMI: Modular Jack 6P4C
Material used for connectors are RoHS and UL approved

Operating conditions

-20 – 60 °C, 90% RH non-condensing

Storage / Transport conditions

-30 – 80 °C, 90% RH non-condensing

Vibration and shock

According to IEC 60068-2-27 Ea

Integration

In Class I and / or II appliances

Index of protection

IP40 only on the front cover

PCB protection

None (no conformal coating)

Period of electric stress across 

insulating parts

Long

Resistance to heat and fire

Category D

Immunity against voltage surges

Category II

Software class and structure

Class A

Approvals

CE compliance:

This product is designed to comply with the following EU standards:

•  Low voltage guideline: 2014/35/EU

•  Electromagnetic compatibility EMC: 2014/30/EU and with the following norms:

 

– EN61000-6-1. EN61000-6-3 

(immunity and emission standard for residential. commercial and light-industrial environments)

 

– EN61000-6-2. EN61000-6-4 

(immunity and emission standard for industrial environments)

 

– EN60730-1 and EN60730-2-9 

(Automatic electrical controls for household and similar use)

RoHS compliance to 2011/65/EU and no components from negative list acc. to 500B0751

UL approval

Feature 

Type

Description

Protection Short circuit

Motor driver: dissipative over current protection

Over voltage

Analogue input: current limit and  internal clamp diode

Digital input: current limit and  internal clamp diode

Communication: transreceiver IC

Over temperature

Motor driver: thermal shutdown at 150 °C

Unstable Digital input

Continuous variation of the digital input state

Installation considerations

Accidental damage, poor installation, or site conditions, can give 

rise to malfunctions of the control system, and ultimately lead to a 

plant breakdown. 

Every possible safeguard is incorporated into our products to 

prevent this. However, a wrong installation, for example, could still 

present problems.

Electronic controls are no substitute for normal, good engineering 

practice. 

Danfoss will not be responsible for any goods, or plant 

components, damaged as a result of the above defects. It is the 

installer’s responsibility to check the installation thoroughly, and 

to fit the necessary safety devices. 

Special reference is made to the necessity of signals to the 

controller when the compressor is stopped and to the need of 

liquid receivers before the compressors. Your local Danfoss agent 

will be pleased to assist with further advice, etc.

Summary of Contents for 080G0325

Page 1: ...User Guide Stepper Valve Extension Module Type EKE 1P ADAP KOOL Refrigeration Control System www danfoss com...

Page 2: ...03 Introduction 3 Application 1 4 Application 2 4 User Interface 5 End user overview with graphical display 7 Service and commissioning with graphical display 7 Menu 8 Alarm list 11 ERR31 12 Connecti...

Page 3: ...guage only Two sets of LEDs on the EKE 1P indicate the EKE 1P application confirmation valve status and alarm condition see details further below Data communication The controller has a built in CANBU...

Page 4: ...lve will close in this case Application 2 Valve configuration The valve type can be selected from an extensive list of Danfoss standard valve types When a standard type is selected only a few paramete...

Page 5: ...G Configured as HP module will blink for 30 sec after power up 3 Receiver module 0s 2s 1s R R R R G G G G Configured as receiver module will blink for 30 sec after power up 0s 2s 1s R R R R G G G G R...

Page 6: ...fully closed V2 Valve closing 0s 2s 1s R R R R R R R R Flashing red 2 Hz valve closing V3 Valve idle 0s 2s 1s Running on target Both Red and Green off V4 Valve opening 0s 2s 1s G G G G G G G G Flashi...

Page 7: ...d outputs and will depend on how the set up is made application mode Click on the to view e g the following images Service and commissioning with graphical display To access the parameter menu press a...

Page 8: ...emperature and Pressure unit Metric C bar Imperial F psig Fac Metric C bar Backlight time out If no buttons have been pushed for a specific period of time the light in the display will be minimised Th...

Page 9: ...connected to the EKE 50 200 Fac 100 Valve acceleration current These features are used with valves running at higher speed i e 300 pps and above Typically at start up high torque is required to operat...

Page 10: ...tting of the CANBUS baudrate 20k 50k 125k 250k 500k 1M Fac 50k Service Actual OD Read out of the valve opening degree in percentage Actual step Read out of the valve opening degree in number of steps...

Page 11: ...oning set Half step operation is possible Correct either I029 or I064 Valve speed too fast Number of micro steps sec is too high higher than 12800 micro step sec Reduce valve speed or use less micro s...

Page 12: ...rner The software version must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until...

Page 13: ...le Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 B1 B2 Bipolar and unipolar stepper motor output Danfoss CCMT 3L CCMT 8L CCMT 0 CCMT 42 CCM 10 CCM 40 ETS 6 ETS 400 CTR 20 Other valves speed 10...

Page 14: ...inst voltage surges Category II Software class and structure Class A Approvals CE compliance This product is designed to comply with the following EU standards Low voltage guideline 2014 35 EU Electro...

Page 15: ...mounting only IP20 Type Function Operation Supply voltage Code no EKE 1P Stepper Valve Extension Module Via AK PC or MMIGRS2 24 V 080G0325 EKE 2U Back up power module 24 V 080G5555 AK PC 572 Capacity...

Page 16: ...Danfoss DCS vt 2020 03 BC320219567793en 000201 16 ADAP KOOL...