User Guide | Stepper Valve Extension Module, Type EKE 1P

© Danfoss | DCS (vt) | 2020.03

BC320219567793en-000201 | 3

Advantages

•   Simplified  settings:

 

–  For application 1, typically the controller needs no parameter 

adjustment

 

–  For application 2, only a few key parameter settings may be 

required

•  Power Supply: 

 

–  Easy wiring layout. With no risk of causing short circuits when 

connecting to other units through power supply

 

– 24 V AC or 24 V DC: flexibility in selecting different transformers 

•  Universal valve support:

 

–  Drives bipolar and unipolar valves

 

–  Danfoss standard valves selectable through drop-down

 

–  Flexible configuration of valve driver parameters for non-

Danfoss standard valves

Input and output

In application mode 1, all input and output are defined via the 

master controller AK-PC set-up.

In application mode 2, the input and output are intended for one 

specific function.

The overview of connections can be seen on page 12.

Operation

The daily operation can be set up via an external display device 

although this is normally not required for application 2.

The normal operation screen for application 1 is shown below.

During set-up, the display images will be adjusted so that only the 

relevant images are opened for additional setting and end-user 

operation. 

The operation is password protected, and three levels of access 

can be granted. 

The controller contains English language only.

Two sets of LEDs on the EKE 1P indicate the EKE 1P application 

confirmation, valve status and alarm condition – see details further 

below.

Data communication

The controller has a built-in CANBUS and a built-in MODBUS 

interface. The interfaces are used as shown in below table:

Application

The controller is used as an extension module for other Danfoss 

controllers (application 1 below) or as a stepper valve driver 

(application 2 below).

Introduction

Application 1

Application 2

CAN RJ

CAN

EKE 1P

AK-PC

CCMT/ETS/CCM

Danf

oss

80G394

100 

Min. 

Max. 

Danf

oss

80G395

Fig. 1

CAN RJ

V

EKE 1P

PLC

CCMT/ETS/CCM

Danf

oss

80G396

MMIGRS2

ACCCBI

080G0075

< 3m

CAN RJ

Fig. 2

CANBUS

MODBUS

Application 1

Interface to master 

controller, AK-PC

MODBUS master 

for establishing 

communication with other 

MODBUS devices to the 

master controller, AK-PC 

Application 2

Configuration of EKE 1P 

and daily use interface

Not used – must not 

be connected to any 

MODBUS network

Fail-safe valve closure

As a stepper valve is provided with step motor, it will remain open 

in a power failure situation.
For safety reasons, the liquid flow through the stepper valve must 

be cut off if a power failure occurs.
There are two ways of coping with this situation. 

One of the following two solutions can be applied in the system:
•  Mounting of a solenoid valve in front of EEV 
•  Connection of a battery back-up for EEV valve
If the battery back-up is used, the battery voltage may be 

continuously monitored to generate an alarm in case the battery 

voltage gets out of range. As default this alarm is disabled.

 

Summary of Contents for 080G0325

Page 1: ...User Guide Stepper Valve Extension Module Type EKE 1P ADAP KOOL Refrigeration Control System www danfoss com...

Page 2: ...03 Introduction 3 Application 1 4 Application 2 4 User Interface 5 End user overview with graphical display 7 Service and commissioning with graphical display 7 Menu 8 Alarm list 11 ERR31 12 Connecti...

Page 3: ...guage only Two sets of LEDs on the EKE 1P indicate the EKE 1P application confirmation valve status and alarm condition see details further below Data communication The controller has a built in CANBU...

Page 4: ...lve will close in this case Application 2 Valve configuration The valve type can be selected from an extensive list of Danfoss standard valve types When a standard type is selected only a few paramete...

Page 5: ...G Configured as HP module will blink for 30 sec after power up 3 Receiver module 0s 2s 1s R R R R G G G G Configured as receiver module will blink for 30 sec after power up 0s 2s 1s R R R R G G G G R...

Page 6: ...fully closed V2 Valve closing 0s 2s 1s R R R R R R R R Flashing red 2 Hz valve closing V3 Valve idle 0s 2s 1s Running on target Both Red and Green off V4 Valve opening 0s 2s 1s G G G G G G G G Flashi...

Page 7: ...d outputs and will depend on how the set up is made application mode Click on the to view e g the following images Service and commissioning with graphical display To access the parameter menu press a...

Page 8: ...emperature and Pressure unit Metric C bar Imperial F psig Fac Metric C bar Backlight time out If no buttons have been pushed for a specific period of time the light in the display will be minimised Th...

Page 9: ...connected to the EKE 50 200 Fac 100 Valve acceleration current These features are used with valves running at higher speed i e 300 pps and above Typically at start up high torque is required to operat...

Page 10: ...tting of the CANBUS baudrate 20k 50k 125k 250k 500k 1M Fac 50k Service Actual OD Read out of the valve opening degree in percentage Actual step Read out of the valve opening degree in number of steps...

Page 11: ...oning set Half step operation is possible Correct either I029 or I064 Valve speed too fast Number of micro steps sec is too high higher than 12800 micro step sec Reduce valve speed or use less micro s...

Page 12: ...rner The software version must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until...

Page 13: ...le Stepper motor Bipolar unipolar 1 Stepper valves A1 A2 B1 B2 Bipolar and unipolar stepper motor output Danfoss CCMT 3L CCMT 8L CCMT 0 CCMT 42 CCM 10 CCM 40 ETS 6 ETS 400 CTR 20 Other valves speed 10...

Page 14: ...inst voltage surges Category II Software class and structure Class A Approvals CE compliance This product is designed to comply with the following EU standards Low voltage guideline 2014 35 EU Electro...

Page 15: ...mounting only IP20 Type Function Operation Supply voltage Code no EKE 1P Stepper Valve Extension Module Via AK PC or MMIGRS2 24 V 080G0325 EKE 2U Back up power module 24 V 080G5555 AK PC 572 Capacity...

Page 16: ...Danfoss DCS vt 2020 03 BC320219567793en 000201 16 ADAP KOOL...

Reviews: