Dale Power Solutions Ltd
User Manual
User Manual
…………………………………………………………………………………………………………
29
Output
Overload
105% to 110%, 1 h
110% to 125%, 10 min
125% to 150%, 1 min
≥150%, 200 ms
Overload for bypass
125%
Crest factor
3:1
Efficiency in normal mode
6 kVA,
≥88%: 10 kVA, ≥90%
Efficiency in battery mode
6 kVA,
≥85%: 10 kVA, ≥81%
Efficiency of inverter
6 kVA,
≥90%: 10 kVA, ≥92%
Dynamic response
5.0%, 20 ms
DC component
≤500 mV
Switch time
Between normal mode and
battery mode
0 ms
Between inverter and bypass
0 ms
unlock: <15 ms (50 Hz), <13.33 ms (60 Hz)
Parallel operation
Parallel equal current
1+1
≤8%
,
N+1
≤10%
Safety and EMC
Safety
IEC62040-1 GB4943
Isolation resistance
>2 M
Ω (500 Vd.c.)
Isolation voltage
2,820 Vd.c., <3.5mA 1 min
EMC
Conduction: IEC 62040-2
Radiation: IEC 62040-2
Harmonic: IEC 62040-2
EMS
IEC 62040-2
Surge
IEC60664-1 1.2/50
μs + 8/20 μs 6 kV/3 kA
Reliability
MTBF
250,000 h; 1+1 400,000 h
MTTR
30 min