Page 36 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
C.2.1.
LED
Indication
and
Error
Description
For
all
units
‐
Operation
LED
light
(Green)
Error
Description
Blink
Reason
Remedy
Electrical
heater
failure
Green
LED
blinks
1
times,
stops
for
3s
Only
for
unit
with
EH.
EH
safety
switch
is
open.
1.
Change
fan
speed
to
high.
2.
Replace
the
damaged
EH
safety
switch.
Indoor
coil
sensor
2
failure
Green
LED
blinks
2
times,
stops
for
3s
Ti2
sensor
unplugged
or
damaged.
1.
Check
if
Ti2
plug
is
connected
or
not.
2.
Check
if
sensor’s
resistance
is
correct
or
not.
Return
air
sensor
failure
Green
LED
blinks
3
times,
stops
for
3s
Room
sensor
unplugged
or
damaged.
1.
Check
if
Tr
plug
is
connected
or
not.
2.
Check
if
sensor’s
resistance
is
correct
or
not.
Indoor
coil
sensor
1
failure
Green
LED
blinks
4
times,
stops
for
3s
Ti1
sensor
unplugged
or
damaged.
1.
Check
if
Ti1
plug
is
connected
or
not.
2.
Check
if
sensor’s
resistance
is
correct
or
not.
Indoor
coil
low
temperature
protection
Green
LED
blinks
5
times,
stops
for
3s
Water
temperature
is
lower
than
3ºC.
Check
the
water
temperature.
Indoor
coil
over
heat
protection
Green
LED
blinks
6
times,
stops
for
3s
Water
temperature
is
higher
than
70ºC.
Check
the
water
temperature
EC
motor
failure
Green
LED
blinks
9
times,
stops
for
3s
No
EC
motor
feedback
1.
Check
DIPB
‐
SW5
and
SW6
setting.
2.
Check
the
EC
motor.
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...