Page 29 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
HEAT
MODE
Without
Electrical
Heater
a)
MTV1,
AUX2
and
electric
heater
are
always
off.
b)
If
Tr
≤
Ts
‐
1ºC
(or
‐
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
MTV2
and
AUX1
are
turned
on.
Indoor
fan
runs
at
the
set
speed.
c)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
MTV2
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200RPM.
d)
The
range
of
Ts
is
16
‐
30ºC.
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
f)
When
turned
on,
MTV2
requires
30
seconds
before
it
is
fully
open.
g)
When
turned
off,
MTV2
requires120
seconds
before
it
is
fully
closed.
With
Electrical
Heater
as
Booster
a)
MTV1
and
AUX2
are
always
off.
b)
If
Tr
≤
Ts
‐
1ºC
(or
–
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
MTV2
and
AUX1
are
turned
on.
Indoor
fan
runs
at
the
set
speed.
c)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
MTV2
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200RPM.
d)
If
Ti1
<
40ºC,
then
the
electrical
heater
is
turned
on.
If
40ºC
≤
Ti1
<
45ºC,
then
the
electrical
heater
maintain
its
original
state.
If
Ti1
≥
45ºC,
then
the
electrical
heater
is
turned
off.
e)
The
range
of
Ts
is
16
‐
30ºC.
f)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
g)
When
turned
on,
MTV2
requires
30
seconds
before
it
is
fully
open.
h)
When
turned
off,
MTV2
requires120
seconds
before
it
is
fully
closed.
PRE
‐
HEAT
Without
Electrical
Heater
a)
If
Ti1
<
36ºC
[or
28ºC
depending
on
DIP
setting],
then
MTV2
and
AUX1
are
turned
on.
Indoor
fan
runs
at
200RPM.
b)
If
Ti1
≥
38ºC
[or
30ºC
depending
on
DIP
setting],
then
MTV2
and
AUX1
are
turned
on.
Indoor
fan
runs
at
set
speed.
c)
If
indoor
coil
temperature
sensor
is
damaged,
then
the
pre
‐
heat
time
is
set
for
2
minutes.
Indoor
fan
runs
at
set
speed.
Pre
‐
heat
with
Electrical
Heater
a)
MTV2
and
AUX2
are
turned
on.
b)
If
the
indoor
fan
speed
≥
300RPM,
then
the
electrical
heater
will
turn
on.
POST
‐
HEAT
Without
Electrical
Heater
a)
If
Ti2
≥
38ºC,
then
MTV2
and
AUX
1
are
turned
off.
Indoor
fan
continues
to
run
at
set
speed.
b)
If
36
F
≤
Ti2
≤
38
F,
then
MTV2
and
AUX1
are
turned
off.
Indoor
fan
maintain
its
original
state.
c)
If
Ti2
<
36ºC,
then
MTV2
and
AUX1
are
turned
off.
Indoor
fan
repeatedly
runs
for
30
seconds
and
then
stops
for
3
minutes.
d)
If
the
indoor
coil
temperature
sensor
is
damaged,
then
the
post
‐
heat
time
is
set
for
3
minutes.
Indoor
fan
running
at
set
speed.
With
Electrical
Heater
a)
Indoor
fan
runs
at
200RPM
after
the
unit
has
been
turned
off
for
20
seconds.
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...