Page 22 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
C.1.4.
Configuration
Settings
There
are
2
DIP
switches
set
on
the
PCB:
a)
DIPA
‐
S1
(8
positions)
SW1
–
SW6:
used
for
master
‐
slave
/
BMS
network
address.
SW7
–
SW8:
used
for
operating
mode
configuration.
b)
DIPB
‐
S2
(6
positions)
SW1:
Occupancy
/
economy
mode
selection.
SW2:
2
‐
pipe
/
4
‐
pipe
configuration
selection.
SW3:
Thermoelectric
valve
configuration
selection
(2
‐
pipe
system
only).
SW4:
Pre
‐
heat
protection
temperature
selection.
SW5
–
SW6:
brushless
DC
fan
motor
configuration.
1.
Default
DIP
Switch
Settings:
DIPA
–S1
DIPB
–S2
2.
Thermoelectric
Valve
Configuration:
On
board
DIP
switch
SW3
of
DIPB
is
used
for
this
configuration.
3.
Unit
Configuration:
On
board
DIP
Switches
of
DIPB
are
used
for
the
below
configurations.
SW1
PR
‐
O
contact
setting
0
Economy
contact
1
Window
contact
SW3
Thermoelectric
valve
(MTV)
1
With
valve
0
No
valve
Figure
¡Error!
Marcador
no
definido.
Figure
1
Unit
Configuration
WITHOUT
Valve
Unit
Configuration
WITH
Valve
0=OFF
1=ON
Summary of Contents for FMCD*ECM series
Page 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Page 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Page 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Page 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...