Installation Guide

Daintree

®

 Networked General Purpose Adapter (WSA10)

9

This equipment has been tested and found to comply with 

the limits for a Class B digital device, pursuant to Part 15 of 

the FCC Rules. These limits are designed to provide reasonable 

protection against harmful interference in a residential 

installation. This equipment generates, uses and radiates radio 

frequency energy and, if not installed and used in accordance 

with the instructions, may cause harmful interference to radio 

communications. However, there is no guarantee that 

interference will not occur in a particular installation. If this 

equipment does cause harmful interference to radio or television 

reception, which can be determined by turning the equipment 

off and on, the user is encourage to try to correct the 

interference by one or more of the following measures:
  •  Reorient or relocate the receiving antenna;
  •  Increase the separation between the equipment

    and receiver;
  •  Connect the equipment into an outlet on a circuit different    

    from that to which the receiver is connected;
  •  Consult the dealer or an experienced radio/TV technician 

    for help.

FCC Warning Message

Input Voltage

 

24VAC/VDC (10mA)

Battery Backup

 

Type: AA 3.6V lithium thionyl chloride,

   

internal, not replaceable

Operating Life: 

7 years or more

Battery Life: 

Min. 5,000 hours (@25°C op. temp),  

   

Backup operation only

Inputs

Resistance: 

(4) Thermistor, 10K Type 2

Accuracy: 

+/- 0.5°C @-10°C to 45°C (14°F to 113°F)

   

+/- 1°C @-30°C to 65°C (-22°F to 149°F)

Voltage: 

(2) 0-10VDC

Accuracy: 

+/- 2% of span (without calibration) 

Radio Properties

 

2.4 GHz, +8 dBm, Range dependent on 

   

RF propagation variables

Operating

 

Relative humidity 5% to 95%,

Environment

 non-condensing

   

Temperature: 32° to 122°F (0° to 50°C)

 

Compliance

 

US: FCC Part 15, Canada: IC

Mounting

 

Wall, ceiling, enclosure screw mount 

Dimensions

 

1.18” W x 0.98” H x 7.03” L

  

(30mm W x 25mm H x 178.5mm L)

ControlScope

 

Manager 

Release version 3.1 or later

Compatibility

Specifications 

These instructions do not purport to cover all details or variations in equipment nor to provide for every possible contingency to be met in connection with installation, operation 

or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be 

referred to GE Current, a Daintree company.

Questions: 

Web:

 products.gecurrent.com

Phone: 

1-866-855-8629

www.gecurrent.com

© 2021 Current Lighting Solutions, LLC. All rights reserved. GE and the GE monogram are trademarks of the  

General Electric Company and are used under license. Information provided is subject to change without notice.  

All values are design or typical values when measured under laboratory conditions. 
DT104 (Rev. 05/14/2021

CAUTION

RISK OF EXPOSURE IF BATTERY IS REPLACED BY AN 

INCORRECT TYPE. DISPOSAL OF USED BATTERIES 

ACCORDING TO THE INSTRUCTIONS.

WSA10

Summary of Contents for GE Current WSA10

Page 1: ...t and during Installation Test Mode red Joined On when the Wireless Adapter has joined a ZigBee network Flashes to indicate Reset and during sensor Installation Test Mode green Power On when power is applied to the Wireless Adapter green LED Indicators 1 Disconnect power to the 24V power supply before installation Confirm that power is off before continuing 2 IMPORTANT Use the provided Plan label ...

Page 2: ...ctions 0 10V sensors and NTC thermistors using a DC Power Supply Figure 3 WSA10 terminal connections for 0 10V sensors and NTC thermistors using a WFA100 SN for DC Power Supply NOTE WFA100 SN is inside an approved electrical fixture or enclosure to provide double insulation of the line voltage wiring ...

Page 3: ...or and NTC thermistors using a WGA100 or WA100 family adaptor for DC Power Supply Figure 5 WSA10 terminal connections for 0 10V sensors and NTC thermistors using an AC Power Supply adaptor for DC Power Supply To reduce AC noise on the sensor signal line install the AC to DC power supply near the WSA10 rather than near the sensor s ...

Page 4: ...h terminal can accept one conductor only Connect only one 24AWG to 16AWG wire to any terminal All installation and maintenance of line voltage equipment must be performed by a qualified electrician The WSA10 must be installed in accordance with all local state and national electrical codes and requirements If the sensor cable includes a shield terminate the end closest to the WSA10 as shown in the...

Page 5: ...SA10 or you can write the last 4 or 5 digits on the floor plan This information will be used during the commissioning process After the system installation is complete a marked up copy of the facility floor plan showing the identity and location of each wireless adapter including associated sensors should be available This will simplify and expedite the commissioning process After the WSA10 is pow...

Page 6: ...tside of the designated range 7 Reports The Zone Temperature Analysis report displays temperature and time as reported by a temperature sensor or thermostat It also displays a histogram representing the time spent at various temperatures over the report time period When a time is selected on the histogram the number of hours spent above or below the selected temperature also displays An input s De...

Page 7: ...temp Backup operation only Inputs Resistance 4 Thermistor 10K Type 2 Accuracy 0 5 C 10 C to 45 C 14 F to 113 F 1 C 30 C to 65 C 22 F to 149 F Voltage 2 0 10VDC Accuracy 2 of span without calibration Radio Properties 2 4 GHz 8 dBm Range dependent on RF propagation variables Operating Relative humidity 5 to 95 Environment non condensing Temperature 32 to 122 F 0 to 50 C Compliance US FCC Part 15 Can...