Tetra

®

 PowerStrip Snap DS 

Installation Guide

6

When retrofitting a sign, ensure the 

rail is cut to the appropriate length to 

properly seat in the lamp socket, and 

use Tetra® Snap Socket Endcaps to 

secure rails to existing lamp sockets.
NOTE: When utilized, ensure the rail 

is properly seated in the lamp sockets. 

For horizontal installations greater than 

5 ft. in  length, the rail assembly should 

be centrally supported.

Tetra Snap 

Socket Endcap

Lamp 

socket

#8 screw

Nominal T12 

Tube Length 

Nominal Rail

 Cut Length 

1.5 ft.

15” (381.5mm)

2 ft.

21” (533.1mm)

2.5 ft.

20” (686.1mm)

3 ft.

33” (837.9mm)

3.5 ft.

39” (980.8mm)

4 ft.

45” (1142.7mm)

5 ft.

57” (1447.5mm)

5.33 ft.

61” (1549.5mm)

6 ft.

69” (1752.3mm)

7 ft.

81” (2057.1mm)

8 ft.

93” (2361.9mm)

Tetra

®

 Snap Nominal LFL 

Rail Length Requirements

1.   (Existing Signs Only) Prior to installation, survey the site for information regarding power and accessibility inside 

and outside the building.  Ensure that the branch circuit supplying the existing transformer or ballast will be within 

the voltage ratings of the new LED power supply, and have a current rating not exceeding 20A, or that permitted by 

applicable local, state, or country electrical codes (whichever is less). 

2.   (Existing Signs Only) Remove the existing lighting equipment to be replaced, such as neon tubing or fluorescent 

tubes; and associated transformers and ballasts. Care should be taken not to break the existing neon or fluorescent 

tubes.  NOTE: Follow all federal and local regulations when disposing of neon tubing, fluorescent tubes, transformers 

and ballasts.

3.   (Existing Signs Only)  If removal of the existing lighting equipment eliminates the disconnect switch, as required by 

applicable local, state, or country electrical codes; a new disconnect switch must be installed.

4.   (Existing Signs Only) Repair and seal any unused openings in the electrical enclosure. Openings greater than 

12.7-mm (1/2-in) diameter require a metal patch secured by screws or rivets and caulked with non-hardening caulk. 

Smaller openings may be sealed with non-hardening caulk.

5.  Using the layout guidelines above, determine required number of LED modules required to illuminate the sign.

6.  A Tetra

®

 24VDC Class 2 Power Supply, as listed below, must be used with this retrofit kit. Using the Maximum Loading 

chart below, determine the number of Tetra

®

 Class 2 Power Supplies required to power the number of LED modules 

required to illuminate the sign, so as not to overload the Tetra

®

 Class 2 Power Supply chosen.

7.  Follow the instructions above to properly mount the LED modules. 

8.  Connect the DC output of the power supply to the LED modules using the Electrical Connections instructions below.

9.  Connect the power unit to the supply in accordance with the applicable local, state, and country electrical codes, and 

the instructions found in the power supply installation guide.

10. If required, the disconnect switch shall be installed by qualified personnel, in accordance with applicable  local, state, and 

country electrical codes.

Retrofit Instructions

FOR UL ONLY

Using Tetra

®

 Snap Socket Endcap

Summary of Contents for GE current Tetra PowerStrip Snap DS

Page 1: ...rentbyge com eu HU A telep t si tmutat s a biztnos gi inform ci k magyar nyelv v ltozata az al bbi c men tal lhat https products currentbyge com eu IT La versione italiana del manuale di installazione...

Page 2: ...lation RISQUE D INCENDIE OU DE CHOC LECTRIQUE L installation de l quipement de remplacement DEL exige Ia connaissance des syst mes lectriques pour enseignes Si non qualifi ne tentez pas d installation...

Page 3: ...y Dow Corning RTV 748 Non Corrosive Sealant White UL certified 18 AWG 0 82 mm2 supply wire UL certified 22 14 AWG 0 33 2 08 mm2 wire connectors or 18 14 AWG 0 82 2 08 mm2 inline IDC connectors 6 and 8...

Page 4: ...spacing Installation Using Tetra Snap Rails Align peg on top of the light module with hole on top of the Tetra Snap Rail and push module into rail until it snaps into place For added security fasten m...

Page 5: ...Connector must be secured with screws to the mounting rail Using Tetra Snap Interconnectors Alternative Mounting Using Tetra Snap T Connectors The modules may be attached to any structural member of t...

Page 6: ...low all federal and local regulations when disposing of neon tubing fluorescent tubes transformers and ballasts 3 Existing Signs Only If removal of the existing lighting equipment eliminates the disco...

Page 7: ...e non corrosive silicone for additional weather protection NOTES Exceeding maximum load will cause the power supply to shut down If overload occurs remove excess load recycle the input power to restar...

Page 8: ...wer Supply 20 ft 6 1 m 25 ft 7 6 m 35 ft 10 6 m 40 ft 12 1 m 100W Power Supply 20 ft 6 1 m 25 ft 7 6 m 35 ft 10 6 m 40 ft 12 1 m 180W Power Supply 20 ft 6 1 m 25 ft 7 6 m 35 ft 10 6 m 40 ft 12 1 m 300...