background image

LineFit Light-LED (LFL-LED)

Installation Guide

3

Wire AC line to LED driver(s) in accordance with the 

applicable local, state, and country electrical codes. 

Connect black to black or brown, white to white or 

blue, and green to green using 18 AWG (0.82mm

2

wire connectors. 

Add up total footage of the system to determine the 

appropriate number of 24VDC Class 2 Tetra

®

 LED 

drivers to use based on the Power Supply Loading 

chart on last page.

Connect the red stripe wire (+) of the LED system to 

the red wire (+) of the power supply. Connect the white 

wire (-) of the LED system to the black or blue wire (-) of 

the power supply.

Connect Line Fit Lights using twist-on wire connectors or in-line (IDC) connectors. Join white wires together and red 

striped wires together. Cap all exposed wires with appropriate end caps or apply electric grade (non-corrosive) silicone for 

additional weather protection.
NOTEMake sure not to exceed LED driver power limits (see Step 1). Drawing above is for reference only; your lighting layout may differ. 
NOTE: All electrical connections should be suitably protected from mechanical damage and the environment. Seal all connections in 

locations that may be exposed to water with electrical grade RTV silicone.

AC line

GEPS24-180

NOTE:  All drivers except GEPS24-180U must be installed in a raceway or be provided with a GEPSJB60 LED driver extended enclosure.

If installing multiple LED drivers, keep them at least 

2” (50.8mm) apart end to end and 4” (101.6mm) 

apart along the sides.

AC line

Black to black 

or brown (-)

Green to green

White to white 

or blue (+)

Power supply

Electrical Connections

4”

2”

LED driver

LED driver

LED driver

LED driver

To Line Fit Light

Red (+)

Red stripe (+)

White (-)

Black or blue (-) 

23.0W

23.0W

23.0W

23.0W

23.0W

23.0W

Total: 161W

11.5W 11.5W

Add up total length of system

NOTE: Do not use connectors pre-filled with silicone grease/mineral base protective grease or use silicone grease to seal connections.

1

3

5

2

4

Reviews: