DIO-32A Hardware user’s manual
DAINCUBE Corp.
12 / 21
DM-A35-35mm
First, hang part 1 of the Dain-rail adapter on the Dain-rail. Pull down the part2 and walk.
1
2
[Figure 7.4]
DM-A35-35mm
7.3. EtherCAT connection
EtherCAT supports a variety of connection topologies including tree, daisy chain, star, and ring. The simplest
connection method is to connect using the "daisy-chain" topology as shown below.
EtherCAT
Master
[Figure 7.5]
EtherCAT daisy-chain connection
Cautions
when wiring the EtherCAT cable
The Ethernet cable must be used the industrial EtherCAT dedicated cable.
Securely attach the connector of the EtherCAT cable. It causes severe problem in case of a faulty.
Make sure that the EtherCAT cable is at least 10 cm away from the power line or inductive noise.
Never disconnect the EtherCAT cable during operation.
7.3.1. EtherCAT
cable
Recommended specification for EtherCAT cable
Cable Minimum recommended: CAT.5e / 6 SFTP or higher
Plug: STP CAT.5e RJ-45 8P8C (Metal Housing)
⚠
Cautions :
Be sure to connect shield between cable and plug.
[Figure 7.6] STP CAT.5e
Metal plug