background image

RXYQ8~18P7W1BR1
VRVIII System air conditioner
4PW44039-1D

Installation manual

18

Charging in cooling mode

6.

Start up
Wait while the unit is preparing for charging in cooling mode.

7.

Ready

Press the 

 button once within 5 minutes.

If the 

 button is not pushed within 5 minutes, 

P2

 will be

displayed on the remote controller. Refer to 

"2 Remote controller

malfunction code display" on page 18

.

8.

Operation
When the following LED display is shown, open valve A and
close the frontpanel. If the frontpanel is left open, the system
can not operate properly during the refrigerant charging.

*

 = The state of this LED is not important.

9.

Complete
If the display on the remote controller shows a flashing

 PE

 code,

charging is almost finished.
When the unit stops operating, close valve A immediately and
check the LEDs and check if the 

P9

  code is displayed on the

remote controller.

If it is not as shown above, correct the malfunction (as indicated
in the display of the remote controller) and restart the complete
charging procedure. When the charging amount is little, the 

PE

code may not be displayed, but instead the 

P9

  code will be

displayed immediately.

10. Press the 

 button once and the charging is complete.

Record the amount that was added on the additional refrigerant
charge label provided with the unit and attach it on the back side
of the front panel.
Perform the test procedure as described in 

"In case refrigerant

was added (charging in cooling mode)" on page 22

.

2

Remote controller malfunction code display

Remote controller heating mode malfunction codes

Remote controller cooling mode malfunction codes

11.5. Checks after adding refrigerant

Are the stop valves for both liquid and gas open?

Is the amount of refrigerant, that has been added, recorded?

H1P

H2P

H3P

H4P

H5P

H6P

H7P

Pressure control 
(for the first minute)

x c x

x

x

x w

Start up control 
(for the next 2 minutes)

x c x

x

x w x

Waiting for stable 
heating conditions 
(for the next ±15 
minutes (according to 
the system))

x c x

x

x w w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

c c c x w x w

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c

*

*

*

*

*

When a malfunction occurs, check the display of the
remote controller and refer to 

"2 Remote  controller

malfunction code display" on page 18

.

H1P

H2P

H3P

H4P

H5P

H6P

H7P

w c c w w w w

BS4  TEST

BS4  TEST

BS1  MODE

Error code 

P8 

recharge 
operation

Close valve A immediately and press the TEST OPERATION 
button once.
The operation will restart from the charging mode judgement 
onwards.

P2

charge 
hold

Close valve A immediately. Check 
following items:
- Check if the gas side stop valve is 

opened correctly

- Check if the valve of the refrigerant 

cylinder is opened

- Check if the air inlet and outlet of the 

indoor unit are not obstructed

After correcting the 
abnormality, restart 
the automatic 
charging procedure 
again.

Error code 

PA

replace 
cylinder

Close valve A and replace the empty cylinder. When renewed, 
open valve A (the outdoor unit will not stop operating).
After replacing the cylinder, open valve A again and continue the 
work.

P8 

recharge 
operation

Close valve A immediately.
Restart the automatic charging procedure again.

P2

charge 
hold

Close valve A immediately. Check 
following items:
- Check if the gas side stop valve is 

opened correctly

- Check if the valve of the refrigerant 

cylinder is opened

- Check if the air inlet and outlet of the 

indoor unit are not obstructed

- Check if the indoor temperature is not 

lower than 20°C DB

After correcting the 
abnormality, restart 
the automatic 
charging procedure 
again.

*
abnormal 
stop

Close valve A immediately. Confirm the 
malfunction code by the remote controller 
and correct the abnormality by following 
the 

"Correcting after abnormal completion 

of the test operation" on page 23

.

Make sure to open the stop valves after charging the
refrigerant.

Operating with the stop valves closed will damage the
compressor.

Summary of Contents for VRVIII RXYQ-PR1

Page 1: ...INSTALLATION MANUAL RXYQ8P7W1BR1 RXYQ10P7W1BR1 RXYQ12P7W1BR1 RXYQ14P7W1BR1 RXYQ16P7W1BR1 RXYQ18P7W1BR1 System air conditioner...

Page 2: ...d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300...

Page 3: ...MULTI UNIT A1P 3 8 3 4 1 5 5 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N P1 P2 1 2 3 6 5 7 8 9 10 11 1 A 4 4 2 2 2 5 6 3 2 3 1 4 5 6 7 1...

Page 4: ...isesti 14 za p edpokladu e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m 15 u skladu sa slijede im standardom ima ili drugim normativnim dokumentom...

Page 5: ...ujam temperat ra TS TSmin Minim l temperat ra zem spiediena pus L C TSmax Pies tin t temperat ra saska ar maksim lo pie aujamo spiedienu PS M C Dzesin t js N Spiediena dro bas ier ces iestat ana P bar...

Page 6: ...nal heating capacities ranging from 16 0 to 56 5 kW The RXYQ P7 units can be combined with Daikin indoor units for air conditioning purposes and suitable for R410A The present installation manual desc...

Page 7: ...XYQ18 360 585 29 NOTE The table above shows the possible total capacity and number of possible indoor units If the total capacity of the connected indoor units exceeds the capacity of the outdoor unit...

Page 8: ...ake sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smok...

Page 9: ...ve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg 1 Packaging material 2 Opening large 3 Belt sling 4 Opening small 40x45 5 Protector NOTE Use a belt sling of 20 mm wide that adequately bears the we...

Page 10: ...pressure regulator for the nitrogen released when doing the brazing should be set to 0 02 MPa or less See figure 11 Do not use anti oxidants when brazing the pipe joints Residue can clog pipes and br...

Page 11: ...ns when connecting field piping Perform brazing at the gas stop valve before brazing at the liquid stop valve Add brazing material as shown in the figure Be sure to use the supplied accessory pipes wh...

Page 12: ...utdoor and BP units H2 40 m Between BP and BP units Difference in height Difference in height between BP and BP units H3 15 m Between indoor and indoor units Difference in height Difference in height...

Page 13: ...0 22 2 290 x 420 28 6 12 7 420 x 585 15 9 Between refrigerant branch kit and BP unit Pipe size for direct connection to BP unit must be based on the total capacity of the connected indoor units c d e...

Page 14: ...stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make...

Page 15: ...or discharge M1C M3C R50 R59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices in...

Page 16: ...in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrica...

Page 17: ...the electric box lid 2 Transmission wiring 3 Pipe opening 4 Conduit 5 Power wiring and ground wiring 6 Cut off the shaded zones before use 7 Through cover 1 Knockout hole 2 Burr 3 If there are any pos...

Page 18: ...res 3 core wire cables are allowable for the cooler heater changeover remote controller only Be sure to keep the power line and transmission line apart from each other Be careful about polarity of the...

Page 19: ...selector etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring w...

Page 20: ...ay only be charged after performing the leak test and the vacuum drying For factory charge refer to the unit name plate NOTE National implementation of EU regulation on certain fluorinated greenhouse...

Page 21: ...ter the unit has stopped Electric shock warning Close the electric box lid before turning on the main power Perform the settings on the circuit board A1P of the outdoor unit and check the LED display...

Page 22: ...display is shown open valve A and close the frontpanel If the frontpanel is left open the system can not operate properly during the refrigerant charging The state of this LED is not important 9 Compl...

Page 23: ...minute x c x x x x w Start up control for the next 2 minutes x c x x x w x Waiting for stable heating conditions for the next 15 minutes according to the system x c x x x w w H1P H2P H3P H4P H5P H6P...

Page 24: ...s a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing servi...

Page 25: ...adjust the LED indication to the settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip switch 1 DS1 1 4 4 Dip switc...

Page 26: ...on of low noise operation state x standard operation factory setting w operation 4 Indication of power consumption limitation setting x standard operation factory setting w operation Possible function...

Page 27: ...ose all front panels except the front panel of the electric box 2 Turn ON the power to all outdoor units and the connected indoor units Be sure to turn on the power 6 hours before operation in order t...

Page 28: ...concentration level of refrigerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration...

Page 29: ...to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local...

Page 30: ...NOTES NOTES...

Page 31: ...26 12 13 14 15 16 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 2 1 1 1 2 3 4 4 3N 50 Hz 1 50 Hz 26 27...

Page 32: ...4PW44039 1D Copyright Daikin...

Reviews: