Installation manual

15

RXYQ8~18P7W1BR1

VRVIII System air conditioner

4PW44039-1D

11. C

HARGING

 

REFRIGERANT

The outdoor unit is factory charged, but depending on the length of
the piping when installed, the outdoor unit may require additional
charging.

For charging the additional refrigerant follow the procedure as
described in this chapter.

11.1. Important information regarding the 

refrigerant used

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Please fill in with indelible ink,

 the factory refrigerant charge of the product,

 the additional refrigerant amount charged in the field and

+

➁ 

the total refrigerant charge

on the fluorinated greenhouse gases label supplied with the product.

The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).

11.2. Precautions when adding R410A

Be sure to charge the specified amount of refrigerant in liquid state to
the liquid pipe.

Since this refrigerant is a mixed refrigerant, adding it in gas form may
cause the refrigerant composition to change, preventing normal operation.

Before charging, check whether the refrigerant cylinder is
equipped with a siphon tube or not.

Be sure to use tools exclusively for R410A to ensure required
pressure resistance and to prevent foreign materials from mixing
into the system.

11.3. Stop valve operation procedure

Size of stop valve

The sizes of the stop valves connected to the system are as listed in
the table below.

Opening stop valve 

(See figure 15)

1.

Remove the cap and turn the valve counterclockwise with the
hexagon wrench.

2.

Turn it until the shaft stops.

3.

Make sure to tighten the cap securely. Refer to the table below

Closing stop valve 

(See figure 15)

1.

Remove the cap and turn the valve clockwise with the hexagon
wrench.

2.

Securely tighten the valve until the shaft contacts the main body
seal.

3.

Make sure to tighten the cap securely.
For the tightening torque, refer to the table above.

Refrigerant can not be charged until all field wiring and
field piping has been completed.

Refrigerant may only be charged after performing the leak
test and the vacuum drying.

For factory charge, refer to the unit name plate.

NOTE

National implementation of EU regulation on certain
fluorinated greenhouse gases may require to provide
the appropriate official national language on the unit.
Therefore, an additional multilingual fluorinated
greenhouse gases label is supplied with the unit.

Sticking instructions are illustrated on the backside of
that label.

Charge the liquid 
refrigerant with the 
cylinder in upright 
position.

Charge the liquid 
refrigerant with the 
cylinder in up-side-down 
position.

3

5

6

2

1

4

1

factory refrigerant 
charge of the product:
see unit name plate

2

additional refrigerant 
amount charged in the 
field

3

total refrigerant 
charge

4

Contains fluorinated 
greenhouse gases 
covered by the Kyoto 
Protocol

5

outdoor unit

6

refrigerant cylinder 
and manifold for 
charging

Charging with an unsuitable substance may cause
explosions and accidents, so always make sure that the
appropriate refrigerant (R410A) is charged.

Refrigerant containers must be opened slowly.

Do not open the stop valve until all piping and
electrical steps of 

"10. 

Checking of unit and

installation conditions" on page 14

  are completed. If

the stop valve is left open without turning on the
power, it may cause refrigerant to build up in the
compressor, leading to insulation degradation.

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant
leaks are present.

Type

5

8

10

12

14

16

18

Liquid line stop valve

Ø9.5

(a)

(a) The model RXYQ12 supports field piping of Ø12.7 on the accessory pipe 

supplied with the unit.

Ø12.7

(b)

(b) The model RXYQ18 supports field piping of Ø15.9 on the accessory pipe 

supplied with the unit.

Gas line stop valve

Ø15.9 Ø19.1

Ø25.4

(c)

(c) The model RXYQ10 supports field piping of Ø22.2 on the accessory pipe 

supplied with the unit.
The model RXYQ12~18 supports field piping of Ø28.6 on the accessory pipe 
supplied with the unit.

1

Service port

2

Cap

3

Hexagon hole

4

Shaft

5

Seal

Do not apply excessive force to the stop valve. Doing
so may break the valve body, as the valve is not a
backseat type. Always use the special tool.

Stop valve size

Tightening torque N•m (Turn clockwise to close)

Shaft

Cap (valve lid)

Service port

Valve body

Hexagonal 

wrench

Ø9.5

5.4~6.6

4 mm

13.5~16.5

11.5~13.9

Ø12.7

8.1~9.9

18.0~22.0

Ø15.9

13.5~16.5

6 mm

23.0~27.0

Ø19.1

27.0~33.0

8 mm

22.5~27.5

Ø25.4

Summary of Contents for VRVIII RXYQ-PR1

Page 1: ...INSTALLATION MANUAL RXYQ8P7W1BR1 RXYQ10P7W1BR1 RXYQ12P7W1BR1 RXYQ14P7W1BR1 RXYQ16P7W1BR1 RXYQ18P7W1BR1 System air conditioner...

Page 2: ...d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300...

Page 3: ...MULTI UNIT A1P 3 8 3 4 1 5 5 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N P1 P2 1 2 3 6 5 7 8 9 10 11 1 A 4 4 2 2 2 5 6 3 2 3 1 4 5 6 7 1...

Page 4: ...isesti 14 za p edpokladu e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m 15 u skladu sa slijede im standardom ima ili drugim normativnim dokumentom...

Page 5: ...ujam temperat ra TS TSmin Minim l temperat ra zem spiediena pus L C TSmax Pies tin t temperat ra saska ar maksim lo pie aujamo spiedienu PS M C Dzesin t js N Spiediena dro bas ier ces iestat ana P bar...

Page 6: ...nal heating capacities ranging from 16 0 to 56 5 kW The RXYQ P7 units can be combined with Daikin indoor units for air conditioning purposes and suitable for R410A The present installation manual desc...

Page 7: ...XYQ18 360 585 29 NOTE The table above shows the possible total capacity and number of possible indoor units If the total capacity of the connected indoor units exceeds the capacity of the outdoor unit...

Page 8: ...ake sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smok...

Page 9: ...ve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg 1 Packaging material 2 Opening large 3 Belt sling 4 Opening small 40x45 5 Protector NOTE Use a belt sling of 20 mm wide that adequately bears the we...

Page 10: ...pressure regulator for the nitrogen released when doing the brazing should be set to 0 02 MPa or less See figure 11 Do not use anti oxidants when brazing the pipe joints Residue can clog pipes and br...

Page 11: ...ns when connecting field piping Perform brazing at the gas stop valve before brazing at the liquid stop valve Add brazing material as shown in the figure Be sure to use the supplied accessory pipes wh...

Page 12: ...utdoor and BP units H2 40 m Between BP and BP units Difference in height Difference in height between BP and BP units H3 15 m Between indoor and indoor units Difference in height Difference in height...

Page 13: ...0 22 2 290 x 420 28 6 12 7 420 x 585 15 9 Between refrigerant branch kit and BP unit Pipe size for direct connection to BP unit must be based on the total capacity of the connected indoor units c d e...

Page 14: ...stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make...

Page 15: ...or discharge M1C M3C R50 R59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices in...

Page 16: ...in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrica...

Page 17: ...the electric box lid 2 Transmission wiring 3 Pipe opening 4 Conduit 5 Power wiring and ground wiring 6 Cut off the shaded zones before use 7 Through cover 1 Knockout hole 2 Burr 3 If there are any pos...

Page 18: ...res 3 core wire cables are allowable for the cooler heater changeover remote controller only Be sure to keep the power line and transmission line apart from each other Be careful about polarity of the...

Page 19: ...selector etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring w...

Page 20: ...ay only be charged after performing the leak test and the vacuum drying For factory charge refer to the unit name plate NOTE National implementation of EU regulation on certain fluorinated greenhouse...

Page 21: ...ter the unit has stopped Electric shock warning Close the electric box lid before turning on the main power Perform the settings on the circuit board A1P of the outdoor unit and check the LED display...

Page 22: ...display is shown open valve A and close the frontpanel If the frontpanel is left open the system can not operate properly during the refrigerant charging The state of this LED is not important 9 Compl...

Page 23: ...minute x c x x x x w Start up control for the next 2 minutes x c x x x w x Waiting for stable heating conditions for the next 15 minutes according to the system x c x x x w w H1P H2P H3P H4P H5P H6P...

Page 24: ...s a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing servi...

Page 25: ...adjust the LED indication to the settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip switch 1 DS1 1 4 4 Dip switc...

Page 26: ...on of low noise operation state x standard operation factory setting w operation 4 Indication of power consumption limitation setting x standard operation factory setting w operation Possible function...

Page 27: ...ose all front panels except the front panel of the electric box 2 Turn ON the power to all outdoor units and the connected indoor units Be sure to turn on the power 6 hours before operation in order t...

Page 28: ...concentration level of refrigerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration...

Page 29: ...to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local...

Page 30: ...NOTES NOTES...

Page 31: ...26 12 13 14 15 16 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 2 1 1 1 2 3 4 4 3N 50 Hz 1 50 Hz 26 27...

Page 32: ...4PW44039 1D Copyright Daikin...

Reviews: