![Daikin VRVIII RXYQ-PR1 Installation Manual Download Page 25](http://html1.mh-extra.com/html/daikin/vrviii-rxyq-pr1/vrviii-rxyq-pr1_installation-manual_2459239025.webp)
RXYQ8~18P7W1BR1
VRVIII System air conditioner
4PW44039-1D
Installation manual
20
Location of the dip switches, LEDs and buttons
LED state
Throughout the manual the state of the LEDs is indicated as follows:
Setting the dip switches
(only in case of a heat pump unit)
Setting the push button switch (BS1~5)
Function of the push button switch which is located on the outdoor
unit PCB (A1P):
The figure shows state of the LED indications when the unit is
shipped from the factory.
Check operation procedure
1
Turn the power on for the outdoor unit and the indoor unit.
Be sure to turn the power on at least 6 hours before operation
inorder to have power running to the crank case heater.
2
Make sure that transmission is normal by checking the LED
display on the outdoor unit circuit board (A1P). (If transmission
is normal, each LED will be displayed as shown below.)
Setting the mode
The set mode can be changed with the
button according
to the following procedure:
■
For setting mode 1: Press the
button once, the
H1P LED is off
x
.
■
For setting mode 2: Press the
button for
5 seconds, the H1P LED is on
w
.
If the H1P LED is blinking
c
and the
button is pushed
once, the setting mode will change to setting mode 1.
Setting mode 1
The H1P LED is off (COOL/HEAT selection setting).
Setting procedure
1
Push the
button and adjust the LED indication to the
settings as shown below in the field marked
:
2
Push the
button and the setting is defined.
1
LED H1~8P
2
Push button switches
BS1~BS5
3
Dip switch 1 (DS1: 1~4)
4
Dip switch 2 (DS2: 1~4)
5
Dip switch 3 (DS3: 1~2)
x
OFF
w
ON
c
Blinking
What to set with dip switch DS1
1
COOL/HEAT selector (refer to
transmission wiring and cool/heat selection" on page 12
)
(
= not installed = factory setting)
2~4
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
What to set with dip switch DS2
1~4
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
What to set with dip switch DS3
1+2
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
For changing the set mode
For field setting
For field setting
For test operation
For resetting the address when the wiring is changed or
when an additional indoor unit is installed
1
2
4
3
5
OFF
BS2
SET
BS1
MODE
BS3
RETURN
BS4
TEST
BS5
RESET
H1P
H2P
H3P
H4P
H5P
H6P
H7P
MODE
TEST:
HWL:
IND
MASTER
SLAVE
L.N.O.P DEMAND
C/H SELECT
H8P
MULTI
BS1 MODE
BS2 SET
BS3 RETURN
BS4 TEST
BS5 RESET
LED
display
(Default
status
before
delivery)
Micro-
computer
operation
monitor
Mode
Ready
/Error
Cooling/Heating
changeover
Low
noise
Demand
Multi
Indivi-
dual
Bulk
(master)
Bulk
(slave)
HAP
H1P
H2P
H3P
H4P
H5P
H6P
H7P
H8P
c
x
x
w
x
x
x
x
x
NOTE
If you get confused in the middle of the setting
process, push the
button. Then it returns to
setting mode 1 (H1P LED is off).
H1P
H2P
H3P
H4P
H5P
H6P
H7P
x
x c x
x
x
x
BS1 MODE
BS1 MODE
BS1 MODE
BS1 MODE
BS1 MODE
BS2 SET
BS3 RETURN
Summary of Contents for VRVIII RXYQ-PR1
Page 30: ...NOTES NOTES...
Page 32: ...4PW44039 1D Copyright Daikin...