background image

Installation manual

11

RXYQ8~18P7W1BR1

VRVIII System air conditioner

4PW44039-1D

8.3.

Power circuit and cable requirements

A power circuit (see table below) must be provided for connection of
the unit. This circuit must be protected with the required safety
devices, i.e. a main switch, a slow blow fuse on each phase and an
earth leakage breaker.

When using residual current operated circuit breakers, be sure to use
a high-speed type 300 mA rated residual operating current.

Point for attention regarding quality of the public electric power
supply

This equipment complies with respectively:

EN/IEC 61000-3-11

(1)

 provided that the system impedance Z

sys

is less than or equal to Z

max

 and

EN/IEC 61000-3-12

(2)

  provided that the short-circuit power S

sc

is greater than or equal to the minimum S

sc

 value

at the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the equipment
to ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
respectively:

Z

sys

 less than or equal to Z

max

 and

S

sc

 greater than or equal to the minimum S

sc

 value.

Be sure to install a main switch for the complete system.

8.4.

General cautions 

Make sure to connect the power source wire to the power
source terminal block and to clamp it as shown in 

figure 16

 and

described in chapter 

"8.8. Field line connection: power wiring"

on page 13

.

For conditional connections, refer to the Technical Data.

As this unit is equipped with an inverter, installing a phase
advancing capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal
heating accident due to high-frequency waves. Therefore, never
install a phase advancing capacitor.

Keep power imbalance within 2% of the supply rating.

Large imbalance will shorten the life of the smoothing
capacitor.

As a protective measure, the product will stop operating and
an error indication will be made, when power imbalance
exceeds 4% of the supply rating.

Follow the "electrical wiring diagram" supplied with the unit when
carrying out any electrical wiring.

Only proceed with wiring work after all power is shut off.

Always ground wires. (In accordance with national regulations of
the pertinent country.)

Do not connect the ground wire to gas pipes, sewage pipes,
lightning rods, or telephone ground wires. This may cause
electric shock.

Combustion gas pipes: can explode or catch fire if there is a
gas leak.

Sewage pipes: no grounding effect is possible if hard plastic
piping is used.

Telephone ground wires and lightning rods: dangerous when
struck by lightning due to abnormal rise in electrical potential
in the grounding.

This unit uses an inverter, and therefore generates noise, which
will have to be reduced to avoid interfering with other devices.
The outer casing of the product may take on an electrical charge
due to leaked electrical current, which will have to be discharged
with the grounding.

Be sure to install an earth leakage breaker. (One that can
handle high-frequency electrical noise.)
(This unit uses an inverter, which means that an earth leakage
breaker capable of handling high-frequency electrical noise
must be used in order to prevent malfunctioning of the earth
leakage breaker itself.)

Earth leakage breakers that are especially designed for
protecting ground-faults must be used in conjunction with main
switch and fuse for use with wiring.

Never connect the power supply in reversed phase.
The unit can not operate normally in reversed phase. If you
connect in reversed phase, replace two of the three phases.

This unit has a reverse phase detection circuit. (If it is activated,
only operate the unit after correcting the wiring.)

Power supply wires must be attached securely.

If the power supply has a missing or wrong N-phase, equipment
will break down.

Make sure that all wiring is secure, the specified wires are used,
and no external forces act on the terminal connection or wires.

Improper connections or installation may result in fire.

When wiring the power supply and connecting the remote
controller wiring and transmission wiring, position the wires so
that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in electric
shocks, fire, or overheating of the terminals.

Phase and 

frequency

Voltage

Minimum 

circuit 

ampere

Recommended 

fuses

Transmission line 

section

RXYQ8

3N~ 50 Hz

400 V

18.5 A

25 A

0.75~1.25 mm

2

RXYQ10

3N~ 50 Hz

400 V

21.6 A

25 A

0.75~1.25 mm

2

RXYQ12

3N~ 50 Hz

400 V

22.7 A

25 A

0.75~1.25 mm

2

RXYQ14

3N~ 50 Hz

400 V

31.5 A

40 A

0.75~1.25 mm

2

RXYQ16

3N~ 50 Hz

400 V

31.5 A

40 A

0.75~1.25 mm

2

RXYQ18

3N~ 50 Hz

400 V

32.5 A

40 A

0.75~1.25 mm

2

(1) European/International Technical Standard setting the limits for voltage changes, 

voltage fluctuations and flicker in public low-voltage supply systems for equipment 
with rated current 

75 A.

(2) European/International Technical Standard setting the limits for harmonic currents 

produced by equipment connected to public low-voltage systems with input 
current >16 A and 

75 A per phase.

Z

max

 (

)

Minimum S

sc

 value

RXYQ8

910 kVA

RXYQ10

0.27

838 kVA

RXYQ12

0.27

849 kVA

RXYQ14

0.24

873 kVA

RXYQ16

0.24

873 kVA

RXYQ18

0.24

878 kVA

NOTE

Select the power supply cable in accordance with
relevant local and national regulations.

Wire size must comply with the applicable local
and national code.

Specifications for local wiring power cord and
branch wiring are in compliance with IEC60245.

WIRE TYPE H05VV(*)
*Only in protected pipes (use H07RN-F when
protected pipes are not used).

Summary of Contents for VRVIII RXYQ-PR1

Page 1: ...INSTALLATION MANUAL RXYQ8P7W1BR1 RXYQ10P7W1BR1 RXYQ12P7W1BR1 RXYQ14P7W1BR1 RXYQ16P7W1BR1 RXYQ18P7W1BR1 System air conditioner...

Page 2: ...d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300...

Page 3: ...MULTI UNIT A1P 3 8 3 4 1 5 5 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 P1 P2 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N P1 P2 1 2 3 6 5 7 8 9 10 11 1 A 4 4 2 2 2 5 6 3 2 3 1 4 5 6 7 1...

Page 4: ...isesti 14 za p edpokladu e jsou vyu v ny v souladu s na imi pokyny odpov daj n sleduj c m norm m nebo normativn m dokument m 15 u skladu sa slijede im standardom ima ili drugim normativnim dokumentom...

Page 5: ...ujam temperat ra TS TSmin Minim l temperat ra zem spiediena pus L C TSmax Pies tin t temperat ra saska ar maksim lo pie aujamo spiedienu PS M C Dzesin t js N Spiediena dro bas ier ces iestat ana P bar...

Page 6: ...nal heating capacities ranging from 16 0 to 56 5 kW The RXYQ P7 units can be combined with Daikin indoor units for air conditioning purposes and suitable for R410A The present installation manual desc...

Page 7: ...XYQ18 360 585 29 NOTE The table above shows the possible total capacity and number of possible indoor units If the total capacity of the connected indoor units exceeds the capacity of the outdoor unit...

Page 8: ...ake sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smok...

Page 9: ...ve which can evacuate to 100 7 kPa 5 Torr 755 mm Hg 1 Packaging material 2 Opening large 3 Belt sling 4 Opening small 40x45 5 Protector NOTE Use a belt sling of 20 mm wide that adequately bears the we...

Page 10: ...pressure regulator for the nitrogen released when doing the brazing should be set to 0 02 MPa or less See figure 11 Do not use anti oxidants when brazing the pipe joints Residue can clog pipes and br...

Page 11: ...ns when connecting field piping Perform brazing at the gas stop valve before brazing at the liquid stop valve Add brazing material as shown in the figure Be sure to use the supplied accessory pipes wh...

Page 12: ...utdoor and BP units H2 40 m Between BP and BP units Difference in height Difference in height between BP and BP units H3 15 m Between indoor and indoor units Difference in height Difference in height...

Page 13: ...0 22 2 290 x 420 28 6 12 7 420 x 585 15 9 Between refrigerant branch kit and BP unit Pipe size for direct connection to BP unit must be based on the total capacity of the connected indoor units c d e...

Page 14: ...stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make...

Page 15: ...or discharge M1C M3C R50 R59 Resistor R95 Resistor current limiting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH S3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices in...

Page 16: ...in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrica...

Page 17: ...the electric box lid 2 Transmission wiring 3 Pipe opening 4 Conduit 5 Power wiring and ground wiring 6 Cut off the shaded zones before use 7 Through cover 1 Knockout hole 2 Burr 3 If there are any pos...

Page 18: ...res 3 core wire cables are allowable for the cooler heater changeover remote controller only Be sure to keep the power line and transmission line apart from each other Be careful about polarity of the...

Page 19: ...selector etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring w...

Page 20: ...ay only be charged after performing the leak test and the vacuum drying For factory charge refer to the unit name plate NOTE National implementation of EU regulation on certain fluorinated greenhouse...

Page 21: ...ter the unit has stopped Electric shock warning Close the electric box lid before turning on the main power Perform the settings on the circuit board A1P of the outdoor unit and check the LED display...

Page 22: ...display is shown open valve A and close the frontpanel If the frontpanel is left open the system can not operate properly during the refrigerant charging The state of this LED is not important 9 Compl...

Page 23: ...minute x c x x x x w Start up control for the next 2 minutes x c x x x w x Waiting for stable heating conditions for the next 15 minutes according to the system x c x x x w w H1P H2P H3P H4P H5P H6P...

Page 24: ...s a ball point pen to avoid touching live parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished WARNING ELECTRIC SHOCK Caution when performing servi...

Page 25: ...adjust the LED indication to the settings as shown below in the field marked 2 Push the button and the setting is defined 1 LED H1 8P 2 Push button switches BS1 BS5 3 Dip switch 1 DS1 1 4 4 Dip switc...

Page 26: ...on of low noise operation state x standard operation factory setting w operation 4 Indication of power consumption limitation setting x standard operation factory setting w operation Possible function...

Page 27: ...ose all front panels except the front panel of the electric box 2 Turn ON the power to all outdoor units and the connected indoor units Be sure to turn on the power 6 hours before operation in order t...

Page 28: ...concentration level of refrigerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards Maximum concentration...

Page 29: ...to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local...

Page 30: ...NOTES NOTES...

Page 31: ...26 12 13 14 15 16 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 2 1 1 1 2 3 4 4 3N 50 Hz 1 50 Hz 26 27...

Page 32: ...4PW44039 1D Copyright Daikin...

Reviews: