background image

English

4

3.

SELECTION OF LOCATION

Select a location for installation that meets the following conditions. 
Get the customer’s permission.

1.

There is no danger of fire due to leakage of inflammable gas.

2.

Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.

3.

The foundation is strong enough to support the weight of the unit 
and the floor is flat to prevent vibration and noise generation.

4.

The piping length between the outdoor unit and the indoor unit 
may not exceed the allowable piping length. (Refer to

 

“6. REFRIGERANT PIPING”

)

5.

Locations where the unit’s suction vent and outlet vent do not gen-
erally face the wind. 
Wind blowing directly into the suction or outlet vents will interfere 
with the unit’s operation.
If necessary, install some kind of obstruction to block the wind.

6.

The space around the unit is adequate for servicing and the min-
imum space for air inlet and air outlet is available. 
(See the “ Installation Space Examples” for the minimum space 
requirements.)

Installation Space Examples

The installation space requirement shown in figure 3 is a refer-
ence for cooling operation when the outdoor temperature is 35°C. 
If the design outdoor temperature exceeds 35°C or the heat load 
exceeds maximum capacity in all the outdoor unit, take an even 
large space on the intake shown in figure 3.

During installation, install the units using the most appropriate of 
the patterns shown in figure 3 for the location in question, taking 
into consideration human traffic and wind.

If the number of units installed is more than that shown in the pat-
tern in figure 3, install the units so there are no short circuits.

As regards space in front of the unit, consider the space needed 
for the local refrigerant piping when installing the units. 

If the work conditions in figure 3 do not apply, contact your dealer 
or Daikin directly.

(Refer to figure 3)

1.

Front side

2.

No limit to wall height

3.

Service space of front side

4.

Service space of suction side

For Patterns 1 and 2 in figure 3:

Wall height for front side – no higher than 1500 mm.

Wall height on the suction side – no higher than 500 mm.

Wall height for sides – no limit.

If the height is exceeded the above, calculate h1 and h2 shown 
in the figure below, and add h1/2 to the service space of front 
side and h2/2 to the service space of suction side.

Note

1.

An inverter air conditioner may cause electronic noise gener-
ated from AM broadcasting. Examine where to install the main 
air conditioner and electric wires, keeping proper distances 
away from stereo equipment, personal computers, etc. 
Particularly for locations with weak reception, ensure there is 
a distance of at least 3 meters for indoor remote controllers, 
place power wiring and transmission wiring in conduits, and 
ground the conduits.

 (Refer to figure 4)

1.

Indoor unit

2.

Branch switch, overcurrent breaker

3.

Remote controller

4.

COOL/HEAT selector

5.

Personal computer or radio

2.

When installing in a locations where there is heavy snowfall, 
implement the following snow measures.

Ensure the base is high enough that intakes are not clogged 
by snow.

Remove the rear intake grille to prevent snow from accumu-
lating on the fins.

3.

If condensate may drip on downstairs (or walkway) depending 
on the floor condition, take a measure such as the installation of 
central drain pan kit (sold separately).

4.

The refrigerant R410A itself is nontoxic, nonflammable and is 
safe. If the refrigerant should leak however, its concentration 
may exceed the allowable limit depending on room size. Due to 
this it could be necessary to take measures against leakage. 
See “14. CAUTION FOR REFRIGERANT LEAKS” for details.

4.

INSPECTING AND HANDLING THE UNIT

At delivery, the package should be checked and any damage 
should be reported immediately to the carrier claims agent.

When handling the unit, take into account the following:

1.

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

2.

Decide on the transportation route.

3.

If a forklift is to be used, insert forks into the opening of the skid 
under the unit. 

(Refer to figure 5)

4.

If hanging the unit, use a cloth sling to prevent damaging the unit. 
Keeping the following points in mind, hang the unit following the 
procedure shown in figure 6.

Use a sling sufficiently strong to hold the mass of the unit.

Use 2 belts of at least 8m long.

Place extra cloth or boards in the locations where the casing 
comes in contact with the sling to prevent damage. 

Hoist the unit making sure it is being lifted at its center of gravity.

5.

After installation, remove the transportation clasp attached to the 
large openings. 

(Refer to figure 6)

(Refer to figure 5)

1.

Forklift

2.

Hook

3.

Skid opening

4.

Transport protector (Yellow)

(Refer to figure 6)

1.

Belt sling

2.

Rag

3.

Skid opening

Note

Apply a filler cloth on a fork to prevent coating of the bottom frame 
from coming off and rust from occurring when bringing in the unit with 
anti-corrosion treatment type using a forklift.

5.

PLACING THE UNIT

Make sure the unit is installed level on a sufficiently strong base to 
prevent vibration and noise. 

(Refer to figure 7)

The base should be bigger around than the width of the unit’s legs 
(66 mm), and should support the unit. 

(Refer to figure 8)

 

If protective rubber is to be attached, attach it to the whole face of 
the base.

The height of the base should be at least 150mm from the floor.

Secure the unit to its base using foundation bolts. (Use four com-
mercially available M12-type foundation bolts, nuts, and washers.)

The foundation bolts should be inserted 20 mm.

(Refer to figure 7)

1.

Unit can not be supported with the 
independent footing in four corners 
only.

2, 3. 

Make sure to install on the base that faces four corners 
and centers of the unit.

(Refer to figure 8)

1.

Foundation bolt point (

φ

15 dia. : 4 positions)

2.

Depth of product

3.

Width of support leg

Note

There are restrictions on the refrigerant pipe connecting order 
between outdoor unit in the case of the multi system.
See the Note in “2-1 Combination” for detail.

When installing on a roof, make sure the roof floor is strong 
enough and be sure to water-proof all work.

Make sure the area around the machine drains properly by setting 
up drainage grooves around the foundation.
Drain water is sometimes discharged from the outdoor unit when 
it is running.

1500

500

h1

h2

Front side

Suction side

B

A

h1 = A (Actual height) – 1500
h2 = B (Actual height) – 500

Model

A

B

Q8 · 10 · 12 type

930

792

Q14 · 16 type

1240

1102

20

01_EN_3P226891-13Q.fm  Page 4  Thursday, December 2, 2010  10:15 AM

Summary of Contents for VRVIII-Q Series

Page 1: ...B RQYQ18PY1B RQYQ20PY1B RQYQ22PY1B RQYQ24PY1B RQYQ26PY1B RQYQ28PY1B RQYQ30PY1B RQYQ32PY1B RQYQ34PY1B RQYQ36PY1B RQYQ38PY1B RQYQ40PY1B RQYQ42PY1B RQYQ44PY1B RQYQ46PY1B RQYQ48PY1B English Deutsch Fran a...

Page 2: ...00_CV_3P226891 13Q fm Page 2 Thursday December 2 2010 1 08 PM...

Page 3: ...200 300 Pattern 3 2 1 1500 3 1 4 2 5 2 mm 1000 1 0 0 0 1000 1 5 0 0 1500 1500 figure 2 2 4 5 1 8 9 10 3 6 7 11 figure 6 1 2 4 3 figure 7 1 2 3 100 100 100 2 3 100 100 100 1 2 6 3 3 4 5 figure 14 figur...

Page 4: ...6 7 8 ABC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 ABC I P A1P TOIN DUNIT TOOUT DUNIT TOMULTIUNIT F1 F2 F1 F2 F1 F2 1 2 3 4 5 6 A F1 F2 F1 F2 Q1 Q2 Q1 Q2 B C ABC I P A1P A1P TOIN DUNIT TOOUT DUNIT TOMULTIUNIT T...

Page 5: ...of Q14 16 type 1 13 2 3 4 14 5 6 7 8 9 11 10 12 15 1 2 3 4 5 6 7 8 9 10 13 13 15 16 17 14 11 12 1 6 5 4 2 3 1 2 3 4 5 figure 28 1 2 3 1 5 6 7 3 4 1 2 3 4 11 12 13 14 9 15 10 10 5 6 7 8 9 figure 31 fi...

Page 6: ...r qualified personnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air co...

Page 7: ...imum refrigerant charge of a VRVIII system must be below 100kg this to be in accordance with CE requirement EN60335 2 40 standard This means that in case the total maximum refrigerant charge of the sy...

Page 8: ...l 3 Clamps 4 Accessory pipes Note Do not throw away any of the accessories until installation is com plete 2 3 Option accessory To install the outdoor units the following optional parts are also requi...

Page 9: ...to prevent snow from accumu lating on the fins 3 If condensate may drip on downstairs or walkway depending on the floor condition take a measure such as the installation of central drain pan kit sold...

Page 10: ...gen permutation or nitrogen blow when brazing Refer to figure 10 Brazing without performing nitrogen permutation or nitrogen blow into the piping will create large quantities of oxidized film on the i...

Page 11: ...ing piping between outdoor units Refer to the installation manual that comes with the kit when doing this piping work 4 Precautions when connecting piping between outdoor units In case of multi system...

Page 12: ...18 1 Do not install vertically Refer to figure 18 2 Maintain a straight portion of 500 mm or more until the split of the joint without wrapping any onsite piping around this area Over 500 mm of straig...

Page 13: ...r unit 1 8 a a u r s t i i b b a a s t r u b c d e f g h i i c d e f g h j k REFNET Header REFNET Header 1 2 3 4 5 6 1 2 3 4 5 6 7 H2 b r s u t c d e f g h 1 2 3 4 5 6 7 8 8 c d e f g h 1 2 3 4 5 6 7...

Page 14: ...920 x 15 9 19 1 22 2 28 6 34 9 41 3 19 1 25 4 28 6 34 9 54 1 9 5 12 7 15 9 19 1 12 7 15 9 19 1 22 2 Total capacity of indoor units gas pipe liquid pipe standard size max size standard size max size u...

Page 15: ...r ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circuit see the following table must be provided for con nection of the unit This circuit must be protected with...

Page 16: ...be finished simul taneously with the local refrigerant piping and wound with tape field supply as shown in figure 25 Refer to figure 25 1 Liquid pipe 2 Gas pipe 3 Transmission wiring 4 Insulation mat...

Page 17: ...ve A C in figure 28 should be open or closed as shown in the table below Refer to figure 28 1 Gauge manifold 2 Nitrogen 3 Measuring device 4 R410A tank with siphon 5 Vacuum pump 6 Charge hose 7 Liquid...

Page 18: ...of a nut See 7 4 Transmission Wiring Connection Procedure 2 Make sure there is no faulty power wiring or loosing of a nut See 7 5 Power Wiring Connection Procedure 3 Has the insulation of the main pow...

Page 19: ...3 9 12 7 8 1 9 9 18 0 22 0 15 9 13 5 16 5 Hexagonal wrench 6 mm 22 5 27 5 19 1 27 0 33 0 Hexagonal wrench 8 mm 25 4 LED display h OFF i ON j Blinking Uncertain LED display H1P H2P H3P H4P H5P H6P H7P...

Page 20: ...med in recovery or other service modes About re charging of refrigerant When sizes and length of field pipings are certain figure out the re charging amount of refrigerant by calculation method of ref...

Page 21: ...Perform the refrigerant charging operation according to check operation and charge the remaining refrigerant of the additional charging amount For performing the refrigerant charging opera tion the pu...

Page 22: ...cate to open the valve of the refrigerant tank as on the right in approx 6 min after the re start Operation for re charging of refrigerant 1 60 min Contamination prevention is opearted at the same tim...

Page 23: ...t according to the list on the installation manual 1 11 Test operate again after the repair To check operate again press the RETURN button BS3 to turn the LED back to normal indications as procedure 1...

Page 24: ...it are reversed Exchange two of the three phases L1 L2 L3 and connect with the correct phase U3 Check operation has been completed normally Perform the check operation again U1 U4 LC Power is not bein...

Page 25: ...hecks After Test Run Perform the following checks after the test run is complete Record the contents of field setting Record them on the accessory REQUEST FOR THE INDI CATION label And attach the labe...

Page 26: ...results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum con centration level then make similar calculations for the second then third smallest ro...

Page 27: ...3P226891 13Q EM10A040 1012 HT 00_CV_3P226891 13Q fm Page 6 Thursday December 2 2010 1 08 PM...

Reviews: