background image

English

12

When pulling the ground wire out, wire it so that it comes through 
the cut out section of the cup washer. (See the figure below.) An 
improper ground connection may prevent a good ground from 
being achieved.

When two wires are connected to a single terminal, connect them 
so that the rear sides of the crimp contacts face each other. Also, 
make sure the thinner wire is on top, securing the two wires simul-
taneously to the resin hook using the included clamp (1).

7-6 Procedure for Wiring Inside Units

Referring to figure 27, secure and wire the power and transmis-
sion wiring using the included clamp (1), (2), and (3).

(Refer to figure 27)

1.

Retain with accessory clamp (3).

2.

Electric conduit

3.

When routing out the power/ground wires from the left 
side.

4.

When routing out the transmission wiring from the open-
ing for piping.

5.

When routing out the power/ground wires from the front.

6.

Clear over 50 mm.

7.

When routing out the transmission wiring from the 
knockout hole.

8.

Retain to the back of the column support with the acces-
sory clamp (2).

9.

When routing out the power/ground wires from the right 
side.

10.

Power wiring

11.

Transmission wiring

12.

Ground wire

13.

Secure to the back side of the support beam using the 
accessory clamp (1).

14.

Retain to the back of the column support with the acces-
sory clamp (2).

15.

When wiring, exercise sufficient caution not to detach the 
acoustic insulators from the compressor.

CAUTION

• The transmission wiring must be at least 50 mm away from the 

power wiring.

Make sure all wiring do not contact to the pipes (hatching parts in 
the figure 27).

After wiring work is completed, check to make sure there are no 
loose connections among the electrical parts in the 
EL.COMPO.BOX.

8.

AIR TIGHT TEST AND VACUUM DRY-
ING

Note

Always use nitrogen gas for the airtightness test.

Absolutely do not open the shutoff valve until the main power cir-
cuit insulation measurement has been completed. (measuring 
after the shutoff valve is opened will cause the insulation value to 
drop.)

8-1 Preparations

<Needed tools>

 <The system for air tight test and vacuum drying>

Referring to figure 28, connect an nitrogen tank, refrigerant tank, 
and a vacuum pump to the outdoor unit.
The refrigerant tank and the charge hose connection to refrigerant 
charge port or the valve A, C in figure 28 are needed in “11. ADDI-
TIONAL REFRIGERANT CHARGE AND CHECK OPERATION”.

The shutoff valve and valve A~C in figure 28 should be open or 
closed as shown in the table below.

(Refer to figure 28)

1.

Gauge manifold

2.

Nitrogen

3.

Measuring device

4.

R410A tank (with siphon)

5.

Vacuum pump

6.

Charge hose

7.

Liquid side shutoff valve

8.

Gas side shutoff valve

9.

Shutoff valve service port

10.

Valve B

11.

Valve C

12.

Valve A

13.

Outdoor unit

14.

Refrigerant charge port

15.

To indoor unit

16.

Interunit pipings

17.

Refrigerant flow

Note

The airtightness test and vacuum drying 
should be done using the liquid side and 
gas side shutoff valve service ports.
See the [R410A] Label attached to the front 
plate of the outdoor unit for details on the 
location of the service port (see figure at 
right).

See 

[Shutoff valve operation procedure] 

in 

“11-1 Before working” for details on handling 
the shutoff valve.

The refrigerant charge port is connected to 
unit pipe.
When shipped, the unit contains the refrigerant, so use caution 
when attaching the charge hose.

8-2 Air tight test and vacuum drying method

 After finished piping work, carry out air tight test and vacuum drying.

<Air tight test>

Pressurize the liquid and gas pipes to 3.3MPa (33bar) (do not 
pressurize more than 3.3MPa (33bar)). If the pressure does not 
drop within 24 hours, the system passes the test.
If there is a pressure drop, check for leaks, make repairs and per-
form the airtight test again.

<Vacuum drying>

Evacuate the system from the liquid and gas pipes by using a vac-
uum pump for more than 2 hours and bring the system to 
–100.7kPa or less. After keeping the system under that condition 
for more than 1 hour, check if the vacuum gauge rises or not. If it 
rises, the system may either contain moisture inside or have leaks.

Crimp-style terminal

Cup washer

Cut out section 

Terminal 
block

Crimp-style 
terminal

Wire: narrow

Wire: thick

Resin hook

Gauge manifold
Charge hose 
valve

• To prevent entry of any impurities and insure suffi-

cient pressure resistance, always use the special 
tools dedicated for R410A.

• Use charge hose that have pushing stick for con-

necting to service port of shutoff valves or refriger-
ant charge port.

Vacuum pump

• The vacuum pump for vacuum drying should be able 

to lower the pressure to –100.7kPa 
(5 Torr –755mm Hg).

• Take care the pump oil never flow backward into the 

refrigerant pipe during the pump stops.

State of valve A, B and C and 

shutoff valves

Valve

shutoff valve

A

B

C

Liquid 

side 

Gas 
side 

Air tight test, Vacuum drying
(Close valve A and shutoff valves 
certainly. Otherwise the refrigerant 
in the unit are released.)

Close Open Open

Close

Close

[R410A] Label

01_EN_3P226891-13Q.fm  Page 12  Thursday, December 2, 2010  10:15 AM

Summary of Contents for VRVIII-Q Series

Page 1: ...B RQYQ18PY1B RQYQ20PY1B RQYQ22PY1B RQYQ24PY1B RQYQ26PY1B RQYQ28PY1B RQYQ30PY1B RQYQ32PY1B RQYQ34PY1B RQYQ36PY1B RQYQ38PY1B RQYQ40PY1B RQYQ42PY1B RQYQ44PY1B RQYQ46PY1B RQYQ48PY1B English Deutsch Fran a...

Page 2: ...00_CV_3P226891 13Q fm Page 2 Thursday December 2 2010 1 08 PM...

Page 3: ...200 300 Pattern 3 2 1 1500 3 1 4 2 5 2 mm 1000 1 0 0 0 1000 1 5 0 0 1500 1500 figure 2 2 4 5 1 8 9 10 3 6 7 11 figure 6 1 2 4 3 figure 7 1 2 3 100 100 100 2 3 100 100 100 1 2 6 3 3 4 5 figure 14 figur...

Page 4: ...6 7 8 ABC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 ABC I P A1P TOIN DUNIT TOOUT DUNIT TOMULTIUNIT F1 F2 F1 F2 F1 F2 1 2 3 4 5 6 A F1 F2 F1 F2 Q1 Q2 Q1 Q2 B C ABC I P A1P A1P TOIN DUNIT TOOUT DUNIT TOMULTIUNIT T...

Page 5: ...of Q14 16 type 1 13 2 3 4 14 5 6 7 8 9 11 10 12 15 1 2 3 4 5 6 7 8 9 10 13 13 15 16 17 14 11 12 1 6 5 4 2 3 1 2 3 4 5 figure 28 1 2 3 1 5 6 7 3 4 1 2 3 4 11 12 13 14 9 15 10 10 5 6 7 8 9 figure 31 fi...

Page 6: ...r qualified personnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air co...

Page 7: ...imum refrigerant charge of a VRVIII system must be below 100kg this to be in accordance with CE requirement EN60335 2 40 standard This means that in case the total maximum refrigerant charge of the sy...

Page 8: ...l 3 Clamps 4 Accessory pipes Note Do not throw away any of the accessories until installation is com plete 2 3 Option accessory To install the outdoor units the following optional parts are also requi...

Page 9: ...to prevent snow from accumu lating on the fins 3 If condensate may drip on downstairs or walkway depending on the floor condition take a measure such as the installation of central drain pan kit sold...

Page 10: ...gen permutation or nitrogen blow when brazing Refer to figure 10 Brazing without performing nitrogen permutation or nitrogen blow into the piping will create large quantities of oxidized film on the i...

Page 11: ...ing piping between outdoor units Refer to the installation manual that comes with the kit when doing this piping work 4 Precautions when connecting piping between outdoor units In case of multi system...

Page 12: ...18 1 Do not install vertically Refer to figure 18 2 Maintain a straight portion of 500 mm or more until the split of the joint without wrapping any onsite piping around this area Over 500 mm of straig...

Page 13: ...r unit 1 8 a a u r s t i i b b a a s t r u b c d e f g h i i c d e f g h j k REFNET Header REFNET Header 1 2 3 4 5 6 1 2 3 4 5 6 7 H2 b r s u t c d e f g h 1 2 3 4 5 6 7 8 8 c d e f g h 1 2 3 4 5 6 7...

Page 14: ...920 x 15 9 19 1 22 2 28 6 34 9 41 3 19 1 25 4 28 6 34 9 54 1 9 5 12 7 15 9 19 1 12 7 15 9 19 1 22 2 Total capacity of indoor units gas pipe liquid pipe standard size max size standard size max size u...

Page 15: ...r ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circuit see the following table must be provided for con nection of the unit This circuit must be protected with...

Page 16: ...be finished simul taneously with the local refrigerant piping and wound with tape field supply as shown in figure 25 Refer to figure 25 1 Liquid pipe 2 Gas pipe 3 Transmission wiring 4 Insulation mat...

Page 17: ...ve A C in figure 28 should be open or closed as shown in the table below Refer to figure 28 1 Gauge manifold 2 Nitrogen 3 Measuring device 4 R410A tank with siphon 5 Vacuum pump 6 Charge hose 7 Liquid...

Page 18: ...of a nut See 7 4 Transmission Wiring Connection Procedure 2 Make sure there is no faulty power wiring or loosing of a nut See 7 5 Power Wiring Connection Procedure 3 Has the insulation of the main pow...

Page 19: ...3 9 12 7 8 1 9 9 18 0 22 0 15 9 13 5 16 5 Hexagonal wrench 6 mm 22 5 27 5 19 1 27 0 33 0 Hexagonal wrench 8 mm 25 4 LED display h OFF i ON j Blinking Uncertain LED display H1P H2P H3P H4P H5P H6P H7P...

Page 20: ...med in recovery or other service modes About re charging of refrigerant When sizes and length of field pipings are certain figure out the re charging amount of refrigerant by calculation method of ref...

Page 21: ...Perform the refrigerant charging operation according to check operation and charge the remaining refrigerant of the additional charging amount For performing the refrigerant charging opera tion the pu...

Page 22: ...cate to open the valve of the refrigerant tank as on the right in approx 6 min after the re start Operation for re charging of refrigerant 1 60 min Contamination prevention is opearted at the same tim...

Page 23: ...t according to the list on the installation manual 1 11 Test operate again after the repair To check operate again press the RETURN button BS3 to turn the LED back to normal indications as procedure 1...

Page 24: ...it are reversed Exchange two of the three phases L1 L2 L3 and connect with the correct phase U3 Check operation has been completed normally Perform the check operation again U1 U4 LC Power is not bein...

Page 25: ...hecks After Test Run Perform the following checks after the test run is complete Record the contents of field setting Record them on the accessory REQUEST FOR THE INDI CATION label And attach the labe...

Page 26: ...results of the calcu lations in steps 1 and 2 above If the result of the above calculation exceeds the maximum con centration level then make similar calculations for the second then third smallest ro...

Page 27: ...3P226891 13Q EM10A040 1012 HT 00_CV_3P226891 13Q fm Page 6 Thursday December 2 2010 1 08 PM...

Reviews: