FXLQ20~63P7VEB
VRV System air conditioners
4PW53089-1B

Installation and operation manual

4

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for the used refrigerant.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

Use copper alloy seamless pipes (ISO 1337).

The outdoor unit is charged with refrigerant.

To  prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C. Use insulation which is sufficiently
heat resistant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.

Use annealed material only for flare connections.

Refer to the table below for the dimensions of flare nut spaces
and the appropriate tightening torque. (Overtightening may
damage the flare and cause leaks.)

When connecting the flare nut, coat the flare inner surface with
ether oil or ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc. If the
refrigerant gas leaks during the work, ventilate the area.

Finally, insulate as shown in the figure below.

NOTE

When mounting the unit to a wall, operating sound may
become bigger.

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

13

9

10

8

9

8

10

13

12

12

11

1

2

4

3

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe gauge 

(mm)

Tightening 

torque (N•m)

Flare dimension 

A (mm)

Flare shape

Ø6.4

15~17

8.7~9.1

Ø9.5

33~39

12.8~13.2

Ø12.7

50~60

16.2~16.6

Ø15.9

63~75

19.3~19.7

1

Insulation for gas pipe (accessory part)

2

Sealing pad (accessory part) (wrapped over union)

3

Clamp (4x accessory part)

4

Gas pipe

5

Insulation for liquid pipe (accessory part)

6

Liquid pipe

Be sure to insulate local piping all the way into the
pipe connections inside the unit.

Exposed piping may cause condensation or may
cause burns when touched.

R=0.4~0.8

45

° ±

2

90

°±

2

A

1
2
3
4

6

5

Summary of Contents for VRV

Page 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P7VEB FXLQ25P7VEB FXLQ32P7VEB FXLQ40P7VEB FXLQ50P7VEB FXLQ63P7VEB System air conditioners...

Page 2: ...UT D F1 F2 F1 F2 Control box L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 NOTES L N IN D OUT D...

Page 3: ...em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enlig...

Page 4: ...Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as a...

Page 5: ...asures Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical a...

Page 6: ...fasten to the wall using the holes provided or fasten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement m...

Page 7: ...propriate tightening torque Overtightening may damage the flare and cause leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turn...

Page 8: ...ne A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that...

Page 9: ...the terminals Keep wiring in neat order so that they do not obstruct other equipment such as popping open the control box cover Make sure the cover closes tight Incomplete connections could result in...

Page 10: ...g rods or crossground with telephones Improper grounding could result in electric shock 1 Control box 2 Power supply wiring field supply 3 Remote controller wiring field supply 4 Transmission wiring f...

Page 11: ...the wiring again MAINTENANCE Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25 mm2 Length Max 100 m External terminal Contact that can ensure the minimum applicable load of 15 V D...

Page 12: ...g the front as a leverage To install use the opposite method How to clean the drain strainer The drain strainer clears dirt out of the drain water and prevents the piping from clogging However if the...

Page 13: ...d of other parts must be done in accordance with relevant local and national legislation WIRING DIAGRAM A1P PRINTED CIRCUIT BOARD C1 CAPACITOR M1F F1U FUSE B 5 A 250 V HAP LIGHT EMITTING DIODE SERVICE...

Page 14: ...4PW53089 1B Copyright Daikin...

Reviews: