background image

 

FXLQ20~63P7VEB
VRV System air conditioners
4PW53089-1B

Installation and operation manual

8

F

IELD

 

SETTING

Field setting must be made on the remote controller in function of the
installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB". Refer to the installatoin manual of the remote
controller.

Computerised control (forced off and on/off operation)

1

Wire specifications and how to perform wiring

-

Connect input from outside to terminals T1 and T2 of the 
terminal board (remote controller to transmission wiring).

2

Actuation

-

The following table explains "forced off" and "on/off 
operations" in response to input A.

3

How to select forced off and on/off operation

-

Turn the power on and then use the remote controller to 
select operation.

-

Set the remote controller to the field set mode. For details, 
refer to the chapter "How to set in the field", in the remote 
controller manual.

-

When in the field set mode, select mode No. 12, then set the 
first code No. to "1". Then set second code (position) No. to 
"01" for forced off and to "02" for on/off operation. (forced off 
at factory set.)

Centralized control

For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.

T

EST

 

OPERATION

Refer to the installation manual of the outdoor unit.

The operation lamp of the remote controller will flash when an error
occurs. Check the error code on the liquid crystal display to identify
the trouble.

If any of the items in following table are displayed on the remote
controller, there may be a problem with the wiring or power, so check
the wiring again.

M

AINTENANCE

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 10 mA

Forced off

on/off operation

Input "on" stops operation 

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control 

input on 

 off: turns off the unit by 

remote controller

F2

T1

T2

FORCED
OFF

Input A

Error code

Meaning

A8

Error in power supply to indoor unit

C1

Transmission error between fan driver PCB and controller 
PCB of the indoor unit

C6

Improper combination of fan driver PCB of the indoor unit or 
setting failure in control PCB type

U3

Test operation of the indoor unit has not been finished

Error code

Meaning

There is a short circuit at the forced off terminals (T1, T2)

U4

 or 

UH

- The power on the outdoor unit is off
- The outdoor unit has not been wired for power supply
- Incorrect transmission of forced off wiring

no display

- The power on the indoor unit is off
- The indoor unit has not been wired for power supply
- Incorrect transmission wiring, forced off wiring or remote 

controller wiring

Caution

Only a qualified service person is allowed to perform
maintenance.

Before obtaining access to terminal devices, all power
supply circuits must be interrupted.

Do not use water or air of 50°C or higher for cleaning
air filters and outside panels.

Do not wash the air conditioner with water.
Doing so may result in an electric shock.

Do not operate for many hours with opened windows.
This may cause condensation.

Do not stand or place objects on the air conditioner.
This could result in injury due falling or turning over.

Do not place containers with water on the air
conditioner.
If the containers are turned over, the water could
result in equipment failure or electric shock and fire.

Do not operate the unit with the control panel lid open.
If water gets inside the panel, it could result in
equipment failure or electric shock.

If the main power supply is turned off during
operation, operation will restart automatically after the
power turns back on again.

Summary of Contents for VRV

Page 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P7VEB FXLQ25P7VEB FXLQ32P7VEB FXLQ40P7VEB FXLQ50P7VEB FXLQ63P7VEB System air conditioners...

Page 2: ...UT D F1 F2 F1 F2 Control box L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 NOTES L N IN D OUT D...

Page 3: ...em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enlig...

Page 4: ...Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as a...

Page 5: ...asures Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical a...

Page 6: ...fasten to the wall using the holes provided or fasten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement m...

Page 7: ...propriate tightening torque Overtightening may damage the flare and cause leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turn...

Page 8: ...ne A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that...

Page 9: ...the terminals Keep wiring in neat order so that they do not obstruct other equipment such as popping open the control box cover Make sure the cover closes tight Incomplete connections could result in...

Page 10: ...g rods or crossground with telephones Improper grounding could result in electric shock 1 Control box 2 Power supply wiring field supply 3 Remote controller wiring field supply 4 Transmission wiring f...

Page 11: ...the wiring again MAINTENANCE Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25 mm2 Length Max 100 m External terminal Contact that can ensure the minimum applicable load of 15 V D...

Page 12: ...g the front as a leverage To install use the opposite method How to clean the drain strainer The drain strainer clears dirt out of the drain water and prevents the piping from clogging However if the...

Page 13: ...d of other parts must be done in accordance with relevant local and national legislation WIRING DIAGRAM A1P PRINTED CIRCUIT BOARD C1 CAPACITOR M1F F1U FUSE B 5 A 250 V HAP LIGHT EMITTING DIODE SERVICE...

Page 14: ...4PW53089 1B Copyright Daikin...

Reviews: