Installation and operation manual

5

FXLQ20~63P7VEB

VRV System air conditioners

4PW53089-1B

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

D

RAIN

 

PIPING

 

WORK

Rig the drain pipe as shown below. Improperly rigged piping could
lead to leaks and eventually wet furniture and belongings.

1

Carry out the drain piping

Connect the drain hose (accessory part) using the attached
hose and parts, as shown in the figure below.

2

If converging multiple drain pipes, install according to the
procedure shown below. Use a slope downwards at a gradient of
at least 1/100.

Select converging drain pipes with a size that is suitable for the
operating capacity of the unit.

3

After piping work is finished, check if drainage flows smoothly.

Pour approximately 1 liter of water slowly in the air outlet and
check drainage flow.

4

Be sure to insulate all indoor pipes.

E

LECTRIC

 

WIRING

 

WORK

General instructions

All field supplied parts and materials and electric works must be
conform to local and national regulations.

All wiring must be performed by an authorized electrician.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit to wire the
outdoor unit, indoor units and the remote controller. For details
on hooking up the remote controller, refer to the "Installation
manual of the remote controller".

Attach the earth leakage circuit breaker and fuse to the power
supply line.

A main switch or other means for disconnection, having a
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main
power supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal block wiring to
the outdoor unit and BS unit are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
-

gas pipes: might cause explosions or fire if gas leaks.

-

telephone ground wires or lightning rods: might cause 
abnormally high electric potential in the ground during 
lightning storms.

-

plumbing pipes: no grounding effect if hard vinyl piping is 
used.

Make sure electrical wires are stripped
equally.

Precautions

1

Observe the notes mentioned below when wiring to the power
supply terminal board.

-

Use a round crimp-style terminal for insulation sleeve for 
connection to the terminal block for wiring the units. When 
none are available, follow the instructions below.

-

Do not connect wires of different gauge to the same power 
supply terminal. (Looseness in the connection may cause 
overheating.)

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

Drip pan

2

Drain hose (accessory part)

3

Metal clamp (accessory part)

4

3/4" drain pipe

5

Cut to a suitable length 

6

Slope

1

2

3

4

5

6

6

2

3

1

5

4

6

Piping process inside unit

1/100

Drain piping connections

Do not connect the drain piping directly to sewage
pipes that smell of ammonia. The ammonia in the
sewage might enter the indoor unit through the drain
pipes and corrode the heat exchanger.

Keep in mind that the drain pipe will become blocked if
water remains in the drain pipe.

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

Summary of Contents for VRV

Page 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P7VEB FXLQ25P7VEB FXLQ32P7VEB FXLQ40P7VEB FXLQ50P7VEB FXLQ63P7VEB System air conditioners...

Page 2: ...UT D F1 F2 F1 F2 Control box L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 NOTES L N IN D OUT D...

Page 3: ...em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enlig...

Page 4: ...Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as a...

Page 5: ...asures Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical a...

Page 6: ...fasten to the wall using the holes provided or fasten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement m...

Page 7: ...propriate tightening torque Overtightening may damage the flare and cause leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turn...

Page 8: ...ne A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that...

Page 9: ...the terminals Keep wiring in neat order so that they do not obstruct other equipment such as popping open the control box cover Make sure the cover closes tight Incomplete connections could result in...

Page 10: ...g rods or crossground with telephones Improper grounding could result in electric shock 1 Control box 2 Power supply wiring field supply 3 Remote controller wiring field supply 4 Transmission wiring f...

Page 11: ...the wiring again MAINTENANCE Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25 mm2 Length Max 100 m External terminal Contact that can ensure the minimum applicable load of 15 V D...

Page 12: ...g the front as a leverage To install use the opposite method How to clean the drain strainer The drain strainer clears dirt out of the drain water and prevents the piping from clogging However if the...

Page 13: ...d of other parts must be done in accordance with relevant local and national legislation WIRING DIAGRAM A1P PRINTED CIRCUIT BOARD C1 CAPACITOR M1F F1U FUSE B 5 A 250 V HAP LIGHT EMITTING DIODE SERVICE...

Page 14: ...4PW53089 1B Copyright Daikin...

Reviews: