Field Settings from Remote Controller
Si30-408
46
Field Settings from Remote Controller
Examples of Settings of Group No.
Method for Address Setting for Individual Units
When setting the address in indoor units unit such as adjustment of charges, select mode No.
30. Then, make settings as the following procedure.
Procedure
���
Turn on the power supply.
Turn on the power supply of indoor unit (+ Rate control unit). (Setting is available only with
turning on the power supply.)
Check installation and electric wiring again before turning on the power.
(In turning on the power supply after all LCDs are displayed, the operation is occasionally
not accepted displaying "88" for a period of about one minute.)
���
Put the system into setting mode.
While in normal mode, press and hold the
button for a period of four seconds or more
to put the system into "Field Setting Mode".
���
Select mode No.
Select mode No. 30 using
button.
���
Select unit No.
Select unit No. using
button.
���
Select group No.
Select group No. using the upper and lower button of
.
(Group No. increases such as 1-00, 1-01 to 1-15, 2-00, to 4-15)
���
Determine group No.
Determine the content using
button.
���
Return to normal mode.
Press
button.
Note:
Refer to installation manual for using simple remote controller.
Refer to attached information for the settings of group No. of HRV or various kinds of adapters.
When setting the address in indoor units unit such as adjustment of charges, select mode No.
30. Then make settings as the following procedure.
Centralized remote controller
ON/OFF controller
Indoor unit
No remote
controller
HRV
Group control using remote controller
(automatic address)
Group No.
for centralized control
1-00
1-01
1-03
1-04
1-02
Group control using remote controller
(automatic address)